Bosch Thermotechnology · Buderus G315 (Logano G315)

Buderus G315/7

The Buderus G315/7 is a discontinued commercial cast-iron boiler block with 7 sections, 678 MBtu/h gas input (4.7 GPH oil) and a 486 MBtu/h IBR rating.

DiscontinuedHistorically in Canada

Key figures

Max input
Max CSA output
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Buderus G315/7 in practice

Best suited to

    Applicability and support

    Model number
    G315/7
    Canadian availability
    historical
    Production status
    discontinued
    ROMA supplies
    Confirmed at consultation
    ROMA services
    Confirmed at consultation
    Warranty
    Not verified

    Where ROMA provides on-site service

    On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

    See all service areas

    Specifications

    Published specifications

    Values as published by Bosch Thermotechnology. Units are shown with every value; notes flag conflicting sources or missing figures.

    Buderus G315/7 specifications
    SpecificationValueNote
    Input
    Gas input678 MBtu/hPer the engineering submittal sheet performance data.
    Oil input4.7 GPHNo. 2 fuel oil; burner selection by Bosch's approved list.
    Output
    Rated gross output559 MBtu/h
    IBR rating486 MBtu/h
    Efficiency
    AHRI natural-gas combustion efficiency84.4 %
    AHRI natural-gas thermal efficiency82.4 %
    AHRI oil combustion efficiency87 %
    AHRI oil thermal efficiency84.9 %
    Physical and connections
    Boiler sections7
    Heating surface74.3 sq ft
    Maximum allowable working pressure87 psigSections labeled for 87 psig; standard relief valve 50 psi.
    Maximum supply water temperature248 °F120 °C.
    Water content52.6 gal
    Weight, shipping (approx.)1,585 lb
    Weight, operating (approx.)2,024 lb
    Operating limits and other
    Boiler horsepower16.6 HP
    Boiler supply and return3"RK return and VK supply.
    Allowable fuelsNatural gas, LP, oil #2Boiler block for forced-draft firing; burner supplied separately.

    Questions about the Buderus G315/7?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate