Burnham · Error codes
Burnham error codes and alerts
Identical code numbers can mean different things on different controllers, so every entry is tied to the documented series, controller and manual version. A code is never a diagnosis.
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call ROMA about the boiler. Official guidance: FortisBC gas leaks and odour.
Burnham Alpine condensing boilers (Sage2.X control; soft and hard lockout codes, I&O 103448-12)
1
Anti Short Cycle. Minimum time between starts has not been reached, a normal delay used to avoid excessive cycles. The table classifies it a…
Lockout
2
Boiler Safety Limit Open. A boiler safety limit wired to terminals J6-1, 2 or 3 is open, so check the limit devices for loose wiring and the…
Lockout
3
Boiler Safety Limit (External) Open. The boiler safety limit or external limit wired to terminals J5-1 is open, so check for loose wiring or…
Lockout
4
Supply High Limit. The Sage2.X supply sensor detected water temperatures in excess of 210°F, typically from a heating load far below minimum…
Lockout
5
DHW High Limit. The Sage2.X DHW sensor detected temperatures in excess of the setpoint, typically from a DHW load far below the minimum firi…
Lockout
6
Stack High Limit. The Sage2.X flue gas stack sensor detected temperatures in excess of 204°F, so check whether the heat exchanger needs clea…
Lockout
7
Return Sensor Fault. The return temperature sensor is shorted or open, so check for shorted or mis-wired return sensor wiring and replace a …
Lockout
8
Supply Sensor Fault. The supply temperature sensor is shorted or open, so check for shorted or mis-wired supply sensor wiring and replace a …
Lockout
9
DHW Sensor Fault. The Domestic Hot Water temperature sensor is shorted or open, so check for shorted or mis-wired DHW sensor wiring and repl…
Lockout
10
Stack Sensor Fault. The flue gas stack temperature sensor is shorted or open, so check for shorted or mis-wired flue temperature sensor wiri…
Lockout
11
Ignition Failure. Models ALP080B through ALP285B suffered flame failure after 5 tries to restart, so check gas pressure, purge the gas line,…
Lockout
12
Flame Detected Out of Sequence. A flame signal was present when there should be no flame, so check the gas valve before replacing it and ver…
Lockout
13
Flame Rod Shorted to Ground. The flame rod is shorted to ground, so check for shorted or mis-wired flame rod wiring and replace a defective …
Lockout
14
ΔT Inlet/Outlet High. The temperature rise between supply and return is too high, so verify the circulator is operating and that circulator …
Lockout
15
Return Temp Higher than Supply. The return sensor temperature reads higher than the supply sensor for at least 75 seconds, so check flow dir…
Lockout
16
Supply Temp Risen Too Quickly. The supply water temperature has risen too quickly, so check for inadequate boiler water flow and verify the …
Lockout
17
Blower Speed Not Proved. The control is waiting for blower speed to match the purge and light-off set point, indicating a normal sequencing …
Lockout
18
Light-off Rate Proving Failed. The blower is not running at light-off rate when it should or its speed signal is not detected, so check the …
Lockout
19
Purge Rate Proving Failed. The blower is not running at purge rate when it should or its speed signal is not detected, so check the 120 VAC …
Lockout
20
Invalid Safety Parameters. An unacceptable Sage2.X control safety related parameter was detected, so check the parameter selection, reset th…
Lockout
21
Invalid Modulation Parameter. An unacceptable Sage2.X control modulation related parameter was detected, so reset the control to clear the l…
Lockout
22
Safety Data Verification Needed. A safety related parameter change was detected and a verification has not been completed, so verify the cha…
Lockout
23
24VAC Voltage Low/High. The Sage2.X control 24 VAC power is high or low, so check the 24 VAC power wiring, harness, and transformer for loos…
Lockout
24
Fuel Valve Error. Power was detected at the fuel valve output when the fuel valve should be off, so check the gas valve harness connections …
Lockout
25
Hardware Fault. An internal control failure was detected, so reset the control and replace the Sage control if the problem reoccurs. The tab…
Lockout
26
Internal Fault. An internal control failure was detected, so reset the control and replace the Sage control if the problem reoccurs. The tab…
Lockout
27
Unknown Fault. An unknown fault was detected by the control, so reset the control and replace the Sage control if the problem reoccurs. The …
Lockout
ER0011
Adjustment Mode Password Timeout. The control and display are not defective but the password timed out, so cycle power to the display to res…
Details
ER0012
Control Failed. A control failure was detected by the display, so replace the defective Sage control. The table classifies it as Display Fau…
Details
Burnham ES2 cast-iron boilers (IQ control; boiler and IQ Option Panel codes, I&O 103780-11)
4
Flame Current Lower than Threshold. The flame current is lower than the threshold, so check the pilot assembly per Troubleshooting Section 6…
Lockout
6
Flame Sensed Out of Normal Sequence. Flame was sensed out of normal sequence before opening the gas valve or after closing it, so check the …
Details
18
Electronics Failure. The control electronics failed, so cycle power to the control and replace the control if the problem persists. The tabl…
Details
23
Flame Sensed During Pre-purge. Flame was sensed during post-purge before the gas valve signaled open, so check the gas valve and replace it …
Details
32
Temperature Sensor Failure. A temperature sensor or interface failure occurred from an open or short connection, so check the sensor connect…
Details
35
Duplicate Zone Alarm. A duplicate zone condition was detected, so refer to the IQ Zone Panel Instructions to resolve the alarm. The table cl…
Details
55
Damper Failed to Open. The atmospheric damper end switch failed to close with its contacts stuck open, so refer to Troubleshooting Section 5…
Details
56
Damper Failed to Close. Voltage should not be present on P6-5 when the damper is open, so test for 24 VAC to isolate a defective control, ha…
Details
57
Flame Rod Shorted to Burner Ground. The flame rod is shorted to burner ground from excessive flue gas condensation, so check for condensate,…
Lockout
58
AC Line Frequency. The AC signal is too noisy or the frequency is incorrect, so check the supply voltage to the boiler. The table classifies…
Details
59
Line Voltage Error. The AC voltage is out of specification high or low, so check the supply voltage to the boiler. The table classifies it a…
Details
60
Thermostat Input Higher than Threshold. The thermostat input was detected higher than the threshold, so check the thermostat wiring for a pr…
Details
61
Line Voltage Unstable. Too many heavy loads switching on and off may be causing erratic supply voltage, so check the supply voltage to the b…
Details
63
Soft Lockout - Recycles Exceeded. The maximum number of recycles was exceeded, so refer to Troubleshooting Section 6 for corrective action. …
Details
64
Soft Lockout - Internal Failure. The electronics detected an internal fault or wiring fault, so check the vent damper, pilot assembly, and r…
Details
89
Communication Lost. Communication was lost, so check the wiring between the control and the IQ Zone Panel or IQ Reset Card. The table classi…
Details
1
Low Input Voltage. The IQ Option Panel reports low input voltage when the AC voltage supplied to the panel is too low. The table classifies …
Details
2
IQ Option Card Type Change without Re-Learn. A different IQ Option Card was installed in a slot without the panel being manually re-Learned …
Details
3
IQ Option Card Communications Error. The IQ Option Card is not installed properly or has an internal fault, so remove the card and check for…
Details
4
IQ Option Card Hardware Interface Error. The IQ Option Card is not installed properly or there is an option card or panel fault, so straight…
Details
5
Limit Output OFF in ON State. A limit output was off when it should be on, so check the limit string wiring and replace the IQ Option Panel.…
Details
6
Incorrect Wiring. The IQ Option Panel detected incorrect wiring, so check the boiler wiring to the panel. The table classifies it as IQ Opti…
Details
7
Internal IQ Option Panel Error. An internal IQ Option Panel error occurred, so replace the IQ Option Panel to correct the fault. The table c…
Details
8
Limit Output ON in OFF State. A limit output was on when it should be off, so check the limit string wiring and replace the IQ Option Panel.…
Details
9
Hard Lockout due to Repeated Err 8. A hard lockout occurred after repeated Err 8 conditions, so check the limit string wiring and replace th…
Details
Burnham Series 2 cast-iron water boilers (IQ control Err codes, I&O 109443-05)
4
Flame Current Lower than Threshold. The flame current is lower than the threshold, so check the pilot assembly per the troubleshooting secti…
Lockout
6
Flame Sensed Out of Normal Sequence. Flame was sensed out of normal sequence, before opening the gas valve or after closing it, so check the…
Details
18
Electronics Failure. The control electronics reported a failure, so cycle power to the control and replace it if the problem persists. The t…
Details
23
Flame Sensed During Pre-purge. Flame was sensed during pre-purge before the gas valve was signaled open, so check the gas valve for proper o…
Details
32
Temperature Sensor Failure. Temperature sensor or interface failure (open or short connection, increased connection resistance, dual sensor …
Details
55
Damper Failed to Open. The atmospheric damper end switch failed to close (end switch contacts stuck open); refer to the damper troubleshooti…
Details
56
Damper Failed to Close. The damper is open so voltage should not be present on P6-5, indicating a defective control, vent damper or wire har…
Details
57
Flame Rod Shorted to Burner Ground. The flame rod is shorted to burner ground, which can result from excessive flue gas condensation; check …
Lockout
58
AC Line Frequency. The AC signal is too noisy or its frequency is incorrect, so check the supply voltage and check the sensor for common sho…
Details
59
Line Voltage Error. The AC voltage is out of specification high or low, so check the supply voltage. The table classifies it as Error.…
Details
60
Thermostat Input Higher than Threshold. The thermostat input is higher than the threshold, so check the thermostat wiring. The table classif…
Details
61
Line Voltage Unstable. Heavy loads switching on and off may cause an erratic supply voltage, so check the supply voltage. The table classifi…
Details
63
Soft Lockout - Maximum Recycles Exceeded. The maximum number of recycles was exceeded; refer to the troubleshooting section for recycles. Th…
Lockout
64
Soft Lockout - Internal Failure. The electronics detected an error, which can be caused by an actual controller internal fault or a wiring f…
Lockout
Burnham PVG power-vented cast-iron boilers (IQ Boiler Control error codes, I&O 103997-07)
2
Pressure Switch Failed to Open. While the blower is off the pressure switch failed to open (contact stuck closed); listed causes are wiring,…
Details
4
Flame Current Lower than Threshold. The flame current is lower than the threshold, so check the pilot assembly per the troubleshooting secti…
Lockout
6
Flame Sensed Out of Normal Sequence. Flame was sensed out of normal sequence, before opening the gas valve or after closing it, so check gas…
Details
18
Electronics Failure. The control electronics reported a failure, so cycle power to the control and replace it if the problem persists. The t…
Details
23
Flame Sensed During Pre-Purge. Flame was sensed during post-purge before the gas valve was signaled open, so check the gas valve for proper …
Details
29
Pressure Switch Failed to Close. While the blower is on the pressure switch failed to close; listed causes are a differential pressure below…
Details
32
Temperature Sensor Failure. Temperature sensor or interface failure (open or short connection, increased connection resistance, dual sensor …
Details
35
Duplicate Zone Alarm. A duplicate zone alarm was reported; refer to the IQ Zone Panel instructions. The table classifies it as Error.…
Details
57
Flame Rod Shorted to Burner Ground. The flame rod is shorted to burner ground, which can result from excessive flue gas condensation; check …
Lockout
58
AC Line Frequency Error. The AC signal is too noisy or its frequency is incorrect, so check the supply voltage. The table classifies it as E…
Details
59
Line Voltage Error. The AC voltage is out of specification high or low, so check the supply voltage. The table classifies it as Error.…
Details
60
Thermostat Input Higher than Threshold. The thermostat input is higher than the threshold, so check the thermostat wiring. The table classif…
Details
61
Line Voltage Unstable. Heavy loads switching on and off may cause an erratic supply voltage, so check the supply voltage. The table classifi…
Details
63
Soft Lockout - Maximum Recycles Exceeded. The maximum number of recycles was exceeded; refer to the troubleshooting section for recycles. Th…
Lockout
64
Soft Lockout - Internal Failure. The electronics detected an error, which can be caused by an actual controller internal fault or a wiring f…
Lockout
89
Communication Lost. Communication was lost, so check the wiring between the control and the IQ Zone Panel or IQ Reset Card. The table classi…
Details