De Dietrich MCA Pro wall-hung condensing boilers (Comfort Master error codes, ISM section 8.1)
E:00
Storage unit PSU parameter not found. Probable causes: Bad connection. Checking / solution: Check the wiring. The table classifies it as Err…
Details
E:01
The safety parameters are incorrect. Probable causes: Bad connection • PSU defective. Checking / solution: Check the wiring • Replace PSU. T…
Details
E:02
Supply temperature sensor short circuited. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected. Checking / soluti…
Details
E:03
Supply temperature sensor open circuit. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected. Checking / solution:…
Details
E:04
Temperature of heat exchanger too low. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected • No circulation. Chec…
Details
E:05
Exchanger temperature too high. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected • No circulation. Checking / …
Details
E:06
Return temperature sensor short circuited. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected. Checking / soluti…
Details
E:07
Return temperature sensor open circuit. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected. Checking / solution:…
Details
E:08
Return temperature too low. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected • No circulation. Checking / solu…
Details
E:09
Return temperature too high. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected • No circulation. Checking / sol…
Details
E:10
Difference between the supply and return temperatures too great. Probable causes: Sensor fault • Sensor not or badly connected • No circulat…
Details
E:11
Difference between the supply and return temperatures too great. Probable causes: Sensor fault • Sensor not or badly connected • No circulat…
Details
E:12
Temperature of heat exchanger above normal range (high-limit thermostat STB). Probable causes: Bad connection • Sensor fault • Sensor not or…
Details
E:14
5 burner start-up failures. Probable causes: No ignition • Presence of the ignition arc but no flame formation • Defective control SU PCB. C…
Lockout
E:16
False flame signal. Probable causes: Presence of the flame but insufficient ionization (<3 μA) • Ionization current present when there shoul…
Lockout
E:17
Problem on the gas valve SU PCB. Probable causes: Bad connection • Defective SU PCB. Checking / solution: Check the wiring • Inspect the SU …
Details
E:34
Fan fault. Probable causes: Bad connection • Fan defective. Checking / solution: Check the wiring • Replace the fan if need be • Check for a…
Details
E:35
Supply and return reversed. Probable causes: Bad connection • Sensor fault • Sensor not or badly connected • Water circulation direction rev…
Details