Skip to content
Boilers.caby ROMA Heating & Cooling

De Dietrich · GT Series

De Dietrich GT 228A

The De Dietrich GT 228A is a 8-section eutectic cast-iron 3-pass commercial boiler rated 361 MBH gas input / 307 MBH output (2.5 GPH on oil) at a printed 85.2% gas efficiency (oil +3 points), with R1 1/2 supply and return connections.

CurrentSold in Canada

Key figures

Max input
361 MBH
Max CSA output
307 MBH
AFUE
Min input
Natural gasPropaneDHW: unknowncommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

De Dietrich GT 228A in practice

The GT 228A is the 8-section size of the GT 220A series, a eutectic cast-iron three-pass low-temperature boiler documented in the GT 220A brochure. The printed table gives 361 MBH CSA gas input, 307 MBH CSA output, a 2.5 GPH No. 2 fuel oil input and a dry weight of 827 lb. The boiler is rated ASME IV Class 30 at 60 psi water with an 86–194 °F operating range and 230 °F maximum water temperature.

Supply and return connections are R1 1/2 and the vent connection is 7". The brochure's efficiency note states '85.2% efficiency is the published efficiency (oil is +3%)' — there is no per-model AFUE column for this line. DDR Americas Inc. (Cambridge, Ontario) is the North American arm and the submittal for this line is issued on its letterhead.

Best suited to

  • Commercial buildings whose calculated load fits 307 MBH output
  • Low-temperature hydronic systems with gas, oil or dual-fuel firing
  • Plants replacing a boiler of similar ${r.sections}-section physical size

Applicability and support

Model number
GT 228A
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by De Dietrich. Units are shown with every value; notes flag conflicting sources or missing figures.

De Dietrich GT 228A specifications
SpecificationValueNote
Input
CSA gas input361 MBHPrinted in the GT 220A brochure technical specifications.
CSA No. 2 fuel oil input2.5 GPHPrinted in the GT 220A brochure technical specifications.
Output
CSA output (gas-oil)307 MBHPrinted in the GT 220A brochure; outputs are rounded in the source.
Efficiency
Published efficiency (as printed)85.2% gas (oil +3 points)Brochure note: '85.2% efficiency is the published efficiency (oil is +3%)'. No per-model AFUE column is printed for this line.
Venting and air
Boiler vent connection7 inPrinted in the GT 220A brochure; gas-vent categories I, II, III or IV.
Physical and connections
Cast-iron sections8Printed in the GT 220A brochure dimensions table.
Heating supply / returnR1 1/2 outlet / R1 1/2 returnPrinted in the GT 220A brochure dimensions table (items 1 and 2).
Weight (dry)827 lbPrinted in the GT 220A brochure.
MAWP (water)ASME IV Rating Class 30 (60 psi)Printed in the GT 220A brochure.
Operating limits and other
Operating temperature range86–194 °FPrinted in the GT 220A brochure; max water temp 230 °F.
FuelNatural gas or propane; No. 2 oil firing documentedThe GT 220A brochure describes 'propane firing' and the GT-series pages list gas/oil/dual-fuel options; No. 2 oil input is printed per model.

Frequently asked questions

What is the output of the GT 228A?

The GT 220A brochure prints 361 MBH CSA gas input and 307 MBH CSA output for this size, with a 2.5 GPH No. 2 oil input.

What efficiency does the GT 228A have?

The brochure prints 85.2% published efficiency on gas with oil +3 points. No per-model AFUE column is printed for the GT 220A line.

What connections does the GT 228A use?

The brochure's dimensions table prints R1 1/2 heating outlet and return connections and a 7" boiler vent connection for this size.

Questions about the De Dietrich GT 228A?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate