Dunkirk Boilers · PSB Plymouth Steam Boiler
Dunkirk PSB-9D
The Dunkirk PSB-9D is a current cast-iron gas steam boiler: 299 MBH natural-gas input (280 MBH propane) for 245/229 MBH NG/LP heating capacity, a 184/172 MBH net AHRI steam rating (766/717 sq ft) at 82% AFUE, with a 7" flue and 736 lb shipping.
Key figures
- Max input
- —
- Max CSA output
- —
- AFUE
- 82 %
- Min input
- —
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Dunkirk PSB-9D in practice
The PSB-9D is one of the seven sizes in Dunkirk's current PSB (Plymouth Steam Boiler) line. Its sell-sheet ratings row prints 299 MBH natural-gas input (280 MBH propane), 245/229 MBH NG/LP heating capacity, a 184/172 MBH net AHRI steam rating (766/717 sq ft at a 1.333 pickup allowance) and 82% AFUE, with a 7" flue diameter and 736 lb shipping.
The boiler is atmospheric cast iron with an integral draft diverter and vertical venting, connecting on 2-1/2 in. NPT return/supply tappings with a 1/2 in. NPT gas inlet (3/4 in. NPT on 187 MBH and larger) at 120 V AC, less than 12 A. The control module provides an electronic low-water cut-off with a 3/4 in. probe, pressure limit control, steam pressure gauge and glass water level gauge; combustion uses titanium composite burners, an intermittent pilot control, a flame roll-out safety shut-off and a blocked-vent safety shut-off.
Boilers.ca records the printed row for the PSB-9D; the current documents carry the PSB Series 6-era IOM (Rev. C) and 10/16/24 sell sheet, while the nav card prints 'PSB Series 2' — the record follows the current documents. No official Canadian-sales statement was found, so canadianStatus stays 'unknown', and gas, combustion and steam work belongs with a licensed contractor.
Best suited to
- 299-MBH-class residential steam systems (766 sq ft of radiation)
- Steam replacements needing a probe LWCO, pressure limit and gauge glass package
- Buildings comparing natural gas and propane steam ratings
Applicability and support
- Model number
- PSB-9D
- Canadian availability
- unknown
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Dunkirk Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input (natural gas) | 299 MBH | Natural-gas input per the PSB sell sheet ratings table. |
| Input (propane) | 280 MBH | Propane input per the PSB sell sheet's dual NG/LP ratings table. |
| Output | ||
| Heating capacity (natural gas) | 245 MBH | Heating capacity per the sell sheet (DOE test procedures). |
| Heating capacity (propane) | 229 MBH | Propane heating capacity per the sell sheet. |
| Net AHRI steam rating (natural gas) | 184 MBH | Net steam rating 184 MBH (766 sq ft) based on a pickup allowance of 1.333 per the sell sheet. |
| Net AHRI steam rating (propane) | 172 MBH | Propane net steam rating 172 MBH (717 sq ft). |
| Efficiency | ||
| Efficiency (AFUE) | 82 % | AFUE per the PSB sell sheet and product page (up to 82.7% on the PSB-3D). |
| Venting and air | ||
| Flue diameter | 7" | Vertical vent with an integral draft diverter per the product page; flue diameter per the sell sheet. |
| Physical and connections | ||
| Dimensions (W x H x D) | 30-3/4" x 36-3/8 in. x 26-1/2 in. | Cabinet dimensions per the sell sheet. |
| Shipping weight | 736 lb | Shipping weight per the sell sheet. |
| Connections | Return/supply 2-1/2 in. NPT; gas 1/2 in. NPT (75/112/150) or 3/4 in. NPT (187 MBH and larger) | As printed in the sell sheet connections block. |
| Electrical | ||
| Electrical | 120 V AC / 60 Hz / 1 phase, less than 12 A (15 A circuit recommended) | Per the sell sheet connections block. |
| Operating limits and other | ||
| Control | Electronic low-water cut-off with 3/4 in. probe, pressure limit control, steam pressure gauge and glass water level gauge | Per the sell sheet standard equipment; combustion uses titanium composite burners, intermittent pilot and an integral draft diverter. |
| Fuel | Natural gas or propane | Dual NG/LP rating columns are printed for every size. |
Manuals
- PSB Sell Sheet 240009797 (10/16/24) — ratings table240009797 (10/16/24)
- PSB Steam Boiler Manual Rev. C (240013806)240013806 Rev. C · 2025-04-24
Alerts documented for this model
None documented yet.
Frequently asked questions
What are the PSB-9D's ratings?
299 MBH natural-gas input (280 MBH propane), a 184/172 MBH net AHRI steam rating (766/717 sq ft) and 82% AFUE per the PSB sell sheet.
Is the PSB-9D a steam boiler?
Yes — the PSB is a cast-iron gas steam boiler with an electronic low-water cut-off, pressure limit, steam gauge and glass water level gauge, vented vertically.
What gas connection does the PSB-9D need?
3/4 in. NPT gas inlet and 2-1/2 in. NPT return/supply tappings per the sell sheet.
Questions about the Dunkirk PSB-9D?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Dunkirk — PSB Plymouth Steam Boiler (PSB-9D ratings) · accessed September 9, 2026
- PSB Sell Sheet 240009797 (10/16/24) · accessed September 9, 2026
- PSB Steam Boiler Manual Rev. C (240013806) · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.