Skip to content
Boilers.caby ROMA Heating & Cooling

Laars Heating Systems · Mighty Therm2

Laars Mighty Therm2 MT2H 2000

The Laars Mighty Therm2 MT2H 2000 is a non-condensing commercial hydronic boiler rated 2,000,000 BTU/hr input and 1,704,000 BTU/hr output at 85.1% thermal efficiency with two-stage firing.

CurrentSold in Canada

Key figures

Max input
2,000,000 BTU/hr
Max CSA output
1,704,000 BTU/hr
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Laars Mighty Therm2 MT2H 2000 in practice

The MT2H 2000 is the 2,000,000 BTU/hr hydronic size of Laars' Mighty Therm2 replacement-market line, documented in the Document 1560 submittal and the Document 1211M I&O. The submittal sizing table lists 2,000,000 BTU/hr input, 1,704,000 BTU/hr output, 85.1% thermal efficiency, a 2" gas connection, 2-1/2" water connections and a 1200 lb shipping weight.

The Mighty Therm2 is designed for the replacement market with simple, straightforward controls and two-stage firing up to 4:1, a modular construction that separates burner trays, gas train and blower assembly, and fan-assisted Category I venting (Category III with a listed vent system). Model MT2H is the hydronic boiler and MT2V is the volume water heater, with heat-exchanger configuration letters printed in the I&O.

Best suited to

  • Commercial hydronic loads near 2,000,000 BTU/hr input
  • Buildings replacing a legacy atmospheric boiler with a fan-assisted unit
  • Plants that want simple staged controls rather than full modulation

Applicability and support

Model number
MT2H 2000
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Laars Heating Systems. Units are shown with every value; notes flag conflicting sources or missing figures.

Laars Mighty Therm2 MT2H 2000 specifications
SpecificationValueNote
Input
Input2,000,000 BTU/hrPer the printed Mighty Therm2 submittal sizing table.
Output
Output1,704,000 BTU/hrPer the printed Mighty Therm2 submittal sizing table.
Efficiency
Efficiency (thermal)85.1 %Per the printed Mighty Therm2 submittal sizing table.
Venting and air
VentingCategory I fan-assisted; Category III with a listed vent systemPer the Mighty Therm2 I&O venting sections.
Physical and connections
Gas connection2"Per the printed Mighty Therm2 submittal sizing table.
Water connection2-1/2"Per the printed Mighty Therm2 submittal sizing table.
Shipping weight1,200 lbPer the printed Mighty Therm2 submittal sizing table.
Operating limits and other
FiringTwo-stage, up to 4:1Printed on the Mighty Therm2 product page.

Frequently asked questions

What are the Mighty Therm2 MT2H 2000 ratings?

The Document 1560 submittal lists 2,000,000 BTU/hr input, 1,704,000 BTU/hr output and 85.1% thermal efficiency.

What is the difference between MT2H and MT2V?

MT2H is the hydronic boiler and MT2V is the volume water heater; both share the Mighty Therm2 platform and the submittal's efficiency and connection data.

Does the Mighty Therm2 modulate?

It fires in two stages up to 4:1 rather than full modulation, which the product page describes as part of its replacement-market simplicity.

Questions about the Laars Mighty Therm2 MT2H 2000?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate