Skip to content
Boilers.caby ROMA Heating & Cooling

Miura · EX Series Steam Boiler

Miura EX-250-07

The Miura EX-250-07 is a dual-fuel industrial steam boiler rated 250 BHP and 8625 lb/hr equivalent output at up to 170 PSIG, with 85% fuel-to-steam efficiency and a 8000 lb shipping weight in Miura's published EX table.

CurrentCanadian status unknown

Key figures

Max input
Max CSA output
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Miura EX-250-07 in practice

Miura's EX standard-pressure table prints the EX-250-07 at 250 utilization horsepower, 170 PSIG maximum pressure, 8625 lb/hr equivalent output (calculated from and at 212°F feed water at 212°F steam) and 8.369 MMBTU/hr heat output at 85% efficiency.

The same row lists a 9900 lb operational weight, 110 gallons of operational water content, a 8000 lb shipping weight, dimensions of 68 1/2" wide × 135 1/8" long × 145 1/4" high, 68.7 gal/hr No. 2 oil consumption, 3-5 PSIG gas supply pressure and a 20" OD chimney.

The EX uses a floating header design on an upright drum-shaped pressure vessel and reaches full steam output in under five minutes from a cold start. Miura markets the line for facilities that need a secondary fuel source, with the BL Controller providing online monitoring of steam pressure, flue gas temperature, feedwater temperature, scale and overheat monitors, flame current, time to blowdown and water conductivity. No official Canadian-sales statement was found.

Best suited to

  • Facilities that require a secondary fuel source (natural gas, propane or No. 2 oil)
  • Industrial steam loads in the 8625 lb/hr class
  • Compact installations that need quick cold-start steam

Applicability and support

Model number
EX-250-07
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Miura. Units are shown with every value; notes flag conflicting sources or missing figures.

Miura EX-250-07 specifications
SpecificationValueNote
Output
Equivalent output8,625 LB/HREquivalent output calculated from and at 212°F feed water at 212°F steam, per the table note.
Heat output8.369 MMBTU/HRAs printed in the EX standard-pressure rating table.
Efficiency
Efficiency (fuel to steam)85 %Thermal efficiencies are based on high heating values of fuels at 68°F feed water, per the table note.
Venting and air
Chimney diameter (ID)20" ODAs printed in the EX standard-pressure rating table.
Physical and connections
Operational weight9,900 LBSAs printed in the EX standard-pressure rating table.
Operational water content110 galAs printed in the EX standard-pressure rating table.
Shipping weight8,000 LBSAs printed in the EX standard-pressure rating table.
Width68 1/2"As printed in the EX standard-pressure rating table.
Length135 1/8"As printed in the EX standard-pressure rating table.
Height145 1/4"As printed in the EX standard-pressure rating table.
Operating limits and other
Utilization horsepower250 BHPAs printed in the EX standard-pressure rating table.
Maximum pressure170 PSIGAs printed in the EX standard-pressure rating table; optional EXH-SGO series noted at 250 PSIG MAWP.
No. 2 oil consumption68.7 gal/hrAs printed in the EX standard-pressure rating table.
Gas supply pressure3-5 PSIGAs printed in the EX standard-pressure rating table.
Fuel typeNatural Gas, Propane, No. 2 OilUL and c-UL approved for natural gas or propane, per the table note.

Frequently asked questions

What are the EX-250-07 ratings?

Miura's EX table prints 250 BHP, 170 PSIG maximum pressure, 8625 lb/hr equivalent output and 85% efficiency.

What fuel does the EX-250-07 use?

Natural gas, propane or No. 2 fuel oil; the table notes UL and c-UL approval for natural gas or propane.

How quickly does the EX-250-07 make steam?

Miura states the EX Series goes from a cold start to full steam output in less than five minutes.

Questions about the Miura EX-250-07?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate