Skip to content
Boilers.caby ROMA Heating & Cooling

RBI · Futera III

RBI Futera III 1250

The RBI Futera III 1250 is a gas-fired copper-fin commercial boiler rated 1250 MBH input and 1066 MBH boiler output in RBI's published ratings table, with 4:1 full modulation, Category I/II/IV venting and a 850 lb shipping weight.

CurrentCanadian status unknown

Key figures

Max input
1,250 MBH
Max CSA output
1,066 MBH
AFUE
Min input
Natural gasHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

RBI Futera III 1250 in practice

RBI's Futera III product page prints the 1250 row as 1250 MBH (366 kW) input and 1066 MBH (312 kW) boiler output, in a 44" × 29.125" × 55.5" cabinet (1118 × 740 × 1409 mm) with a 850 lb (386 kg) shipping weight.

The row lists Category I 10", Category II 8" and Category IV 6" flue options, a 10" air intake, 1 1/4" gas and 2 1/2" water connections. The Futera III is a gas-fired copper 4-pass heat exchanger (160 psi) with HEATNET 3.0 integrated controls, Modbus/LonWorks/BACnet integration and full modulation with 4:1 turndown, per the product page.

RBI rates the Futera III line at 85.6% AHRI Boiler Efficiency. Boilers.ca prints the rating-table row exactly as published and does not estimate values RBI does not print; the I&O manual (FTIII-IOM-15) and the series brochure are linked from the official literature library. No official Canadian-sales statement was found, so canadianStatus stays unknown.

Best suited to

  • Commercial plants documenting an installed Futera III 1250 against RBI's rating table
  • Hydronic systems in the 1250 MBH input class
  • Primary/secondary piping layouts with Category II or IV venting

Applicability and support

Model number
MB/MW 1250
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by RBI. Units are shown with every value; notes flag conflicting sources or missing figures.

RBI Futera III 1250 specifications
SpecificationValueNote
Input
Input, maximum1,250 MBH366 kW, as printed in the Futera III ratings table.
Output
Boiler output1,066 MBH312 kW boiler output, as printed in the Futera III ratings table.
Efficiency
Efficiency (AHRI boiler)85.6 %85.6% AHRI Boiler Efficiency is printed for the Futera III line on the product page; no per-model efficiency row is printed in the ratings table.
Venting and air
Flue ventCat I 10" / Cat II 8" / Cat IV 6"As printed in the Futera III ratings table.
Air intake10"As printed in the Futera III ratings table.
Physical and connections
Unit depth44 in1118 mm, as printed in the ratings table.
Unit width29.125 in740 mm, as printed in the ratings table.
Unit height55.5 in1409 mm, as printed in the ratings table (the source prints 1938 mm for the 1750 row).
Gas connection1 1/4"As printed in the Futera III ratings table; connection type not printed.
Water connection2 1/2"As printed in the Futera III ratings table; connection type not printed.
Shipping weight850 lb386 kg, as printed in the Futera III ratings table.
Operating limits and other
Turndown4:1Full modulation with 4:1 turndown printed for the Futera III line on the product page.

Frequently asked questions

What are the Futera III 1250 ratings?

RBI's ratings table prints 1250 MBH (366 kW) input and 1066 MBH (312 kW) boiler output for the MB/MW 1250, with a 850 lb (386 kg) shipping weight.

What venting does the Futera III 1250 allow?

The rating row prints Category I 10", Category II 8" and Category IV 6" flue options; final venting design is a licensed contractor's responsibility.

Is the Futera III 1250 condensing?

RBI's product page presents the Futera III as a copper-fin line at 85.6% AHRI Boiler Efficiency; the condensing Futera offerings are the Futera Fusion and Infinite Energy² lines.

Questions about the RBI Futera III 1250?