Smith Cast Iron Boilers · 19HE Series
Smith 19HE-4
The Smith 19HE-4 is a 12.5 HP cast-iron sectional power-burner boiler rated 421 MBH gross output — 520 MBH gas or 3.6 GPH No. 2 oil burner capacity — with a 7" flue connection and printed thermal efficiencies of 84.1% (oil) and 81.5% (gas).
Key figures
- Max input
- 520 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- —
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Smith 19HE-4 in practice
The 19HE-4 is the 4-section size of Smith's 19HE Series, a wet-base cast-iron power-burner boiler for light-commercial hot water or steam heating. BSG-10 prints 421 MBH gross output, 520 MBH gas burner capacity and a 3.6 GPH No. 2 oil firing rate; the G19HE-5 brochure adds net I=B=R ratings of 316 MBH steam and 366 MBH water, 35.8 sq ft of heating surface and a 3.5 cu ft furnace volume.
The 19IOM-8R manual prints 41 GPM at a 20 °F system drop for this size, with recommended 2" supply and 2" return piping and 3" supply/return tappings on the tapping diagram. The boiler is rated 15 psi steam / 80 psi water and is fired by a choice of Beckett, Carlin or Power Flame burners (S-19PBF-4 documents the Power Flame fit). Smith's official nav lists the 19HE as a current commercial line; no Canada-specific product statement was found, so canadianStatus stays unknown.
Best suited to
- Light-commercial hot water or steam plants whose calculated load fits 421 MBH gross output
- Smaller buildings and additions where a 3–6 section block fits the boiler room
- Retrofits that keep a chimney and can use oil, gas or gas/oil power-burner firing
Applicability and support
- Model number
- 19HE-4
- Canadian availability
- unknown
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Smith Cast Iron Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Gas burner capacity (as printed) | 520 MBH | I=B=R gas burner capacity printed in BSG-10 and G19HE-5. |
| Oil firing rate (as printed) | 3.6 GPH | No. 2 fuel oil at 140,000 BTU/gal, printed in BSG-10 and G19HE-5. |
| Output | ||
| Gross output (as printed) | 421 MBH | I=B=R gross output printed in BSG-10 and G19HE-5. |
| Net I=B=R steam rating | 316 MBH | Net steam rating (pickup allowance 1.333) printed in G19HE-5. |
| Net I=B=R water rating | 366 MBH | Net water rating (allowance 1.15) printed in G19HE-5. |
| Efficiency | ||
| Thermal efficiency — oil | 84.1 % | Printed in BSG-10 and G19HE-5. |
| Thermal efficiency — gas | 81.5 % | BSG-10 prints 81.5% gas thermal efficiency for this size. |
| Venting and air | ||
| Flue pipe diameter | 7" | Printed in BSG-10; the 19IOM-8R prints 11- and 12-section units requiring a 12" vent with a transition collar. |
| Physical and connections | ||
| Boiler tappings | 3" supply taps / 3" return tap (tapping diagram); supplied with 4" water supply tapping and 3" return tapping | 19IOM-8R tapping diagram and the NOTE under Table 6. |
| Recommended supply / return piping | 2" supply / 2" return | 19IOM-8R Table 6 at 20 °F system temperature drop, 41 GPM. |
| Heating surface | 35.8 sq ft | Printed in G19HE-5. |
| Furnace volume | 3.5 cu ft | Printed in G19HE-5. |
| Water content — steam | 41 gal | Printed in G19HE-5. |
| Water content — water | 49 gal | Printed in G19HE-5. |
| Working weight — steam | 2,057 lb | Printed in G19HE-5. |
| Working weight — water | 2,122 lb | Printed in G19HE-5. |
| Maximum allowable working pressure | 15 psi steam / 80 psi water | Printed in BSG-10. |
| Operating limits and other | ||
| Boiler horsepower | 12.5 | Printed in G19HE-5. |
| Fuel | Natural gas; oil and gas/oil firing available | BSG-10 prints gas burner capacities and No. 2 fuel-oil firing rates; the product page says the 19HE is a power-burner boiler 'fired with oil, gas or both'. The schema's fuel enum has no oil value, so oil capability is carried here. |
Manuals
Alerts documented for this model
None documented yet.
Frequently asked questions
What output does the Smith 19HE-4 produce?
BSG-10 prints 421 MBH gross output for the 19HE-4, with 316 MBH net steam and 366 MBH net water I=B=R ratings in the G19HE-5 brochure. Size from a heat-loss calculation, not from the model number.
Is the 19HE-4 gas or oil?
Both are documented: 520 MBH gas burner capacity and a 3.6 GPH No. 2 oil firing rate are printed for this size, and the product page calls the 19HE a boiler 'fired with oil, gas or both'.
What connections does the 19HE-4 use?
The tapping diagram shows 3" supply taps and a 3" return tap, and Table 6 of 19IOM-8R recommends 2" supply and 2" return piping for 41 GPM at 20 °F ΔT. The manual note also states the boiler is supplied with a 4" water supply tapping and 3" return tapping.
Questions about the Smith 19HE-4?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Smith 19HE-4 vs 19HE-6Comparison
- Smith 19HE-3 vs Smith 19HE-4Comparison
- Smith 19HE-3Same series
- Smith 19HE-5Same series
- Smith 19HE-6Same series
- Smith 19HE-7Same series
- Smith 19HE-8Same series
- Smith 19HE-9Same series
- Smith 19HE-10Same series
- Smith 19HE-11Same series
- Smith 19HE-12Same series
- 19HE Series series hub
- Buying guide
Sources and verification
- Smith Cast Iron Boilers — 19HE Series product page · accessed September 9, 2026
- Smith Cast Iron Boilers — Commercial catalogue · accessed September 9, 2026
- Smith — Boiler Selection Guide BSG-10 (19HE, RTS HE/28HE, GBX/GVX tables) · BSG-10 · accessed September 9, 2026
- Smith — 19HE Series brochure G19HE-5 (dimensions, technical table, tankless heaters) · G19HE-5 · accessed September 9, 2026
- Smith — 19HE Series Installation & Operation Manual 19IOM-8R (Table 6 piping, tapping diagram) · 19IOM-8R · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.