Triangle Tube · Error codes
Triangle Tube error codes and alerts
Identical code numbers can mean different things on different controllers, so every entry is tied to the documented series, controller and manual version. A code is never a diagnosis.
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call ROMA about the boiler. Official guidance: FortisBC gas leaks and odour.
Triangle Tube Prestige, Excellence and Instinct with the CTRLMax control (E-code fault table)
E1
Failed Ignition. The burner failed to light after 5 ignition attempts. The table classifies it as Manual Reset Lockouts.…
Lockout
E2
False Flame. Flame detected prior to ignition. The table classifies it as Manual Reset Lockouts.…
Lockout
E3
High Boiler Temperature. Boiler temperature has reached 210°F [99ºC] or 102°F [39°C]. The table classifies it as Manual Reset Lockouts.…
Lockout
E5
Blower Speed. Blower is not at correct speed or speed signal is not being received by control module. The table classifies it as Manual Rese…
Lockout
E7
High Flue Temperature. Flue temperature exceeds high limit. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E8
Flame Circuit Error. Flame circuit test failed. The table classifies it as Manual Reset Lockouts.…
Lockout
E9
Gas Valve Circuit Error. Gas valve circuit test failed. The table classifies it as Manual Reset Lockouts.…
Lockout
E12
Internal Control Fault. EEPROM misconfiguration. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E13
Reset Limit Reached. Resets are limited to 5 every 15 minutes. The table classifies it as Manual Reset Lockouts.…
Lockout
E15
Sensor Drift. Supply or return sensor reading has drifted. The table classifies it as Manual Reset Lockouts.…
Lockout
E16
Supply Sensor Stuck. Supply sensor reading is not changing. The table classifies it as Manual Reset Lockouts.…
Lockout
E17
Return Sensor Stuck. Return sensor reading is not changing. The table classifies it as Manual Reset Lockouts.…
Lockout
E18
Sensor Failure. Supply or return sensor reading changed very rapidly. The table classifies it as Manual Reset Lockouts.…
Lockout
E19
Flame Failure During Startup Phase. Flame lost after startup. The table classifies it as Manual Reset Lockouts.…
Lockout
E21
Internal Control Fault. A / D conversion error. The table classifies it as Manual Reset Lockouts.…
Lockout
E25
Internal Control Fault. CRC check error. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E30
Supply Sensor Shorted. A short circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual …
Lockout
E31
Supply Sensor Open. An open circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E32
DHW Sensor Shorted. A short circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Bloc…
Lockout
E33
DHW Sensor Open. An open circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Blockin…
Lockout
E34
Low Voltage. Line voltage has fallen below an acceptable operating level. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E37
Low Water. Water pressure has fallen below 7.2 psi. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E43
Return Sensor Shorted. A short circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual …
Lockout
E44
Return Sensor Open. An open circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E45
Flue Sensor Shorted. A short circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic R…
Lockout
E46
Flue Sensor Open. An open circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E47
Water Pressure Sensor Error. Water pressure sensor is disconnected or broken. The table classifies it as Manual Reset Lockouts.…
Lockout
E76
External Limit Open. An external automatic reset boiler limit has opened. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E77
High Mix Circuit Temperature. Mix circuit temperature exceeds Mix zone high limit setting. The table classifies it as Automatic Reset Blocki…
Lockout
E78
Mix Circuit Sensor Shorted. A short circuit has been detected in the mix circuit temperature sensor circuit. The table classifies it as Auto…
Lockout
E79
Mix Circuit Sensor Open. An open circuit has been detected in the mix circuit temperature sensor circuit. The table classifies it as Automat…
Lockout
E80
Return > Supply. Return temperature is higher than supply temperature. The table classifies it as Manual Reset Lockouts.…
Lockout
E81
Sensor Drift. Supply and return temperatures are not equal. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E82
Delta T Protection. Excessive difference between the boiler supply and return temperatures. The table classifies it as Automatic Reset Block…
Lockout
E83
Delta T Protection. Excessive difference between boiler supply and return temperatures has occured 5 times. The table classifies it as Manua…
Lockout
E84
High Flue Temperature. Flue temperature has exceeded high limit 5 times. The table classifies it as Manual Reset Lockouts.…
Lockout
E87
External Limit Open. An external manual reset limit has opened. The table classifies it as Manual Reset Lockouts.…
Lockout
E89
Incorrect Setting. A parameter setting is in conflict with another setting. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E90
Firmware Mismatch. Control module and display firmware versions are incompatible. The table classifies it as Automatic Reset Blocking Lockou…
Lockout
E91
System Sensor Shorted. A short circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E92
System Sensor Open. An open circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Reset B…
Lockout
E93
Outdoor Sensor Shorted. A short circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Re…
Lockout
E94
Internal Display Fault. Display memory error. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E95
Supply Sensor Error. Supply sensor reading is invalid. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E96
Outdoor Sensor Open. An open circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Reset…
Lockout
E97
Cascade Mismatch. Cascade configuration has changed. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E98
Cascade Bus Error. Communication with other boilers has been lost. The table classifies it as Automatic Reset Blocking Lockouts.…
Lockout
E99
Controller Bus Error. Communication between boiler display and control module has been lost. The table classifies it as Automatic Reset Bloc…
Lockout
Triangle Tube Prestige Solo gen-1 (MCBA control, pre-2011 Solo 110 manual)
E00
Flame Detected Prior to Burner Startup. Flame detected prior to burner startup.…
Lockout
E02
Failed Ignition After 5 Attempts. Failed ignition after 5 attempts.…
Lockout
E03
Gas Valve Harness Not Properly Connected. Gas valve harness not properly connected.…
Details
E04
Power Supply Lost After Lockout Occurred. Power supply lost after lockout occurred.…
Details
E05
Internal Control Failure. Internal control failure.…
Details
E06
Internal Control Failure. Internal control failure.…
Details
E07
Internal Control Failure. Internal control failure.…
Details
E08
Internal Control Failure. Internal control failure.…
Details
E09
Internal Control Failure. Internal control failure.…
Details
E11
Internal Control Failure. Internal control failure.…
Details
E12
External Limit Open (Terminals 13 & 14). External limit (terminals 13 & 14) is open.…
Details
E13
Internal Control Failure. Internal control failure.…
Details
E14
Internal Control Failure. Internal control failure.…
Details
E15
Internal Control Failure. Internal control failure.…
Details
E16
Internal Control Failure. Internal control failure.…
Details
E17
Internal Control Failure. Internal control failure.…
Details
E18
Supply Temperature Exceeds 212 F. Supply temperature exceeds 212 F.…
Details
E19
Return Temperature Exceeds 212 F. Return temperature exceeds 212 F.…
Details
E25
Supply Temperature Increased Too Rapidly. Supply temperature increased too rapidly.…
Details
E28
No Blower Signal Present. No blower signal present.…
Details
E29
Blower Signal Does Not Reset to Zero. Blower signal does not reset to zero.…
Details
E31
Supply Temperature Sensor Short Circuited. Supply temperature sensor is short circuited.…
Details
E32
Return Temperature Sensor Short Circuited. Return temperature sensor is short circuited.…
Details
E35
Flue Temperature Sensor Short Circuit. Flue temperature sensor is short circuit.…
Details
E36
Supply Temperature Sensor Open. Supply temperature sensor is open.…
Details
E37
Return Temperature Sensor Open. Return temperature sensor is open.…
Details
E40
Flue Temperature Sensor Open. Flue temperature sensor is open.…
Details
E44
Internal Control Failure. Internal control failure.…
Details
E52
Flue Temperature Exceeds 250 F. Flue temperature exceeds 250 F.…
Details
E60
Internal Control Error - Failure to Read Parameters. Internal control error - failure to read parameters.…
Details
E61
Internal Control Failure. Internal control failure.…
Details
E65
Inadequate Power Supply to the Fan. Inadequate power supply to the fan.…
Details
E113
Invalid Power Frequency. Invalid power frequency.…
Details
E115
Internal Control Failure. Internal control failure.…
Details
E122
Supply or Return Temperature Sensor Drift. Supply or return temperature sensor drift.…
Details
E123
Supply or Return Temperature Failure. Supply or return temperature failure.…
Details
E124
Supply or Return Temperature Not Changing. Supply or return temperature not changing.…
Details
Triangle Tube Prestige Solo PT-era (TriMax control, 2011-50 manual revised 2012)
E1
Failed Ignition. The burner failed to light after 5 ignition attempts. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E2
False Flame. A flame is being detected prior to ignition. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E3
High Boiler Temperature. Boiler temperature exceeds 212°F [100ºF]. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E5
Blower Speed. Blower is not at correct speed or speed signal is not being received by control module. The table classifies it as Manual Rese…
Lockout
E8
Flame Circuit Error. Flame circuit test failed. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E9
Gas Valve Circuit Error. Gas valve circuit test failed. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E13
Reset Limit Reached. Resets are limited to 5 every 15 minutes. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E15
Sensor Drift. Supply or return sensor reading has drifted. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E16
Supply Sensor Stuck. Supply sensor reading is not changing. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E17
Return Sensor Stuck. Return sensor reading is not changing. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E18
Sensor Failure. Supply or return sensor reading changed very rapidly. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E21
Internal Control Fault. A / D conversion error. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E30
Supply Sensor Shorted. A short circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual …
Lockout
E31
Supply Sensor Open. An open circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E43
Return Sensor Shorted. A short circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual …
Lockout
E44
Return Sensor Open. An open circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E80
Return > Supply. Return temperature is higher than supply temperature. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E87
External Limit Open. An external manual reset limit has opened. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E7
High Flue Temperature. Flue temperature exceeds high limit. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E12
Internal Control Fault. EEPROM misconfiguration. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E25
Internal Control Fault. CRC check error. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E32
DHW Sensor Shorted. A short circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Soft…
Lockout
E33
DHW Sensor Open. An open circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Soft Lo…
Lockout
E34
Low Voltage. Line voltage has fallen below an acceptable operating level. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E37
Low Water. Water level has fallen below an acceptable operating level. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E45
Flue Sensor Shorted. A short circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic R…
Lockout
E46
Flue Sensor Open. An open circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E76
External Limit Open. An external automatic reset boiler limit has opened. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E81
Sensor Drift. Supply and return temperatures are not equal. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E89
Incorrect Setting. A parameter setting is outside the settings range. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E90
Firmware Mismatch. Control module and display firmware versions are incompatible. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E91
System Sensor Shorted. A short circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E92
System Sensor Open. An open circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Reset S…
Lockout
E93
Outdoor Sensor Shorted. A short circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Re…
Lockout
E94
Internal Display Fault. Display memory error. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E95
Supply Sensor Error. Supply sensor reading is invalid. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E96
Outdoor Sensor Open. An open circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Reset…
Lockout
E97
Cascade Mismatch. Cascade configuration has changed. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E98
Cascade Bus Error. Communication with other boilers has been lost. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E99
Controller Bus Error. Communication between boiler display and control module has been lost. The table classifies it as Automatic Reset Soft…
Lockout
Triangle Tube Prestige Excellence PT-era (TriMax control, 2011-61 manual revised 2014)
E1
Failed Ignition. The burner failed to light after 5 ignition attempts. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E2
False Flame. A flame is being detected prior to ignition. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E3
High Boiler Temperature. Boiler temperature has reached 210°F [99ºC]. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E5
Blower Speed. Blower is not at correct speed or speed signal is not being received by control module. The table classifies it as Manual Rese…
Lockout
E8
Flame Circuit Error. Flame circuit test failed. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E9
Gas Valve Circuit Error. Gas valve circuit test failed. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E13
Reset Limit Reached. Resets are limited to 5 every 15 minutes. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E15
Sensor Drift. Supply or return sensor reading has drifted. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E16
Supply Sensor Stuck. Supply sensor reading is not changing. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E17
Return Sensor Stuck. Return sensor reading is not changing. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E18
Sensor Failure. Supply or return sensor reading changed very rapidly. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E21
Internal Control Fault. A / D conversion error. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E30
Supply Sensor Shorted. A short circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual …
Lockout
E31
Supply Sensor Open. An open circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E43
Return Sensor Shorted. A short circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual …
Lockout
E44
Return Sensor Open. An open circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E80
Return > Supply. Return temperature is higher than supply temperature. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E87
External Limit Open. An external manual reset limit has opened. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E7
High Flue Temperature. Flue temperature exceeds high limit. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E12
Internal Control Fault. EEPROM misconfiguration. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E25
Internal Control Fault. CRC check error. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E32
DHW Sensor Shorted. A short circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Soft…
Lockout
E33
DHW Sensor Open. An open circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Soft Lo…
Lockout
E34
Low Voltage. Line voltage has fallen below an acceptable operating level. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E37
Low Water. Water level has fallen below an acceptable operating level. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E45
Flue Sensor Shorted. A short circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic R…
Lockout
E46
Flue Sensor Open. An open circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E76
External Limit Open. An external automatic reset boiler limit has opened. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E81
Sensor Drift. Supply and return temperatures are not equal. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E89
Incorrect Setting. A parameter setting is in conflict with another setting. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E90
Firmware Mismatch. Control module and display firmware versions are incompatible. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E91
System Sensor Shorted. A short circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E92
System Sensor Open. An open circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Reset S…
Lockout
E93
Outdoor Sensor Shorted. A short circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Re…
Lockout
E94
Internal Display Fault. Display memory error. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E95
Supply Sensor Error. Supply sensor reading is invalid. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E96
Outdoor Sensor Open. An open circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Reset…
Lockout
E97
Cascade Mismatch. Cascade configuration has changed. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E98
Cascade Bus Error. Communication with other boilers has been lost. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E99
Controller Bus Error. Communication between boiler display and control module has been lost. The table classifies it as Automatic Reset Soft…
Lockout
Triangle Tube Prestige PA-era (ACVMax control, 2015 user's manual)
E1
Failed Ignition. The burner failed to light after 5 ignition attempts. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E2
False Flame. A flame is being detected prior to ignition. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E3
High Boiler Temperature. Boiler temperature has reached 210°F [99ºC]. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E5
Blower Speed. Blower is not at correct speed or speed signal is not being received by control module. The table classifies it as Manual Rese…
Lockout
E8
Flame Circuit Error. Flame circuit test failed. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E9
Gas Valve Circuit Error. Gas valve circuit test failed. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E13
Reset Limit Reached. Resets are limited to 5 every 15 minutes. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E15
Sensor Drift. Supply or return sensor reading has drifted. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E16
Supply Sensor Stuck. Supply sensor reading is not changing. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E17
Return Sensor Stuck. Return sensor reading is not changing. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E18
Sensor Failure. Supply or return sensor reading changed very rapidly. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E21
Internal Control Fault. A / D conversion error. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E30
Supply Sensor Shorted. A short circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual …
Lockout
E31
Supply Sensor Open. An open circuit has been detected in the boiler supply temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E43
Return Sensor Shorted. A short circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual …
Lockout
E44
Return Sensor Open. An open circuit has been detected in the boiler return temperature sensor circuit. The table classifies it as Manual Res…
Lockout
E47
Water Pressure Sensor Error. Water pressure sensor is disconnected or broken. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E80
Return > Supply. Return temperature is higher than supply temperature. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E87
External Limit Open. An external manual reset limit has opened. The table classifies it as Manual Reset Hard Lockouts.…
Lockout
E7
High Flue Temperature. Flue temperature exceeds high limit. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E12
Internal Control Fault. EEPROM misconfiguration. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E25
Internal Control Fault. CRC check error. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E32
DHW Sensor Shorted. A short circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Soft…
Lockout
E33
DHW Sensor Open. An open circuit has been detected in the DHW temperature sensor circuit. The table classifies it as Automatic Reset Soft Lo…
Lockout
E34
Low Voltage. Line voltage has fallen below an acceptable operating level. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E37
Low Water. Water level has fallen below an acceptable operating level. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E45
Flue Sensor Shorted. A short circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic R…
Lockout
E46
Flue Sensor Open. An open circuit has been detected in the boiler flue temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E76
External Limit Open. An external automatic reset boiler limit has opened. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E81
Sensor Drift. Supply and return temperatures are not equal. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E89
Incorrect Setting. A parameter setting is in conflict with another setting. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E90
Firmware Mismatch. Control module and display firmware versions are incompatible. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E91
System Sensor Shorted. A short circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Rese…
Lockout
E92
System Sensor Open. An open circuit has been detected in the system temperature sensor circuit. The table classifies it as Automatic Reset S…
Lockout
E93
Outdoor Sensor Shorted. A short circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Re…
Lockout
E94
Internal Display Fault. Display memory error. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E95
Supply Sensor Error. Supply sensor reading is invalid. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E96
Outdoor Sensor Open. An open circuit has been detected in the outdoor temperature sensor circuit. The table classifies it as Automatic Reset…
Lockout
E97
Cascade Mismatch. Cascade configuration has changed. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E98
Cascade Bus Error. Communication with other boilers has been lost. The table classifies it as Automatic Reset Soft Lockouts.…
Lockout
E99
Controller Bus Error. Communication between boiler display and control module has been lost. The table classifies it as Automatic Reset Soft…
Lockout