Weil-McLain · SVF (Stainless Vertical Firetube)
Weil-McLain SVF 2000 S2
The Weil-McLain SVF 2000 S2 is a current commercial stainless-steel vertical fire-tube condensing boiler: 2000 MBH maximum input, 1920 MBH gross output at 96% thermal efficiency, with a 10:1 turn-down, 3" flange supply/return, 2" NPT gas and a 10"/8" vent connection.
Key figures
- Max input
- 2,000 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- —
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Weil-McLain SVF 2000 S2 in practice
The SVF 2000 S2 is one of the current SVF (Stainless Vertical Firetube) commercial sizes documented on Weil-McLain's official product pages. Its Technical Specs row prints 2000 MBH maximum input, 1920 MBH gross output and 96% thermal efficiency at a 160 psi maximum working pressure with a 10:1 turn-down ratio.
The unit connects on 3" flange supply/return with a 2" NPT gas line and a 10"/8" air-intake/exhaust vent, measures 84 5/16" long x 35 3/8" wide x 80 3/4" high and ships at about 2500 lb with integrated roller casters and a shipping ramp; a 3-in-1 vent adapter is supplied for quick installation. Control is the Unity 2.0 color touchscreen Nuro platform with enhanced diagnostics, troubleshooting and remote monitoring, and the pages position the line as certified ENERGY STAR and heat-pump ready.
Boilers.ca records the printed spec row for the SVF 2000 S2 for commercial service planning. No official Canadian-sales statement was found on the US product pages reviewed, so canadianStatus stays 'unknown'; commercial gas, combustion and venting work belongs with a licensed contractor against the model's own SVF boiler manual.
Best suited to
- 2000-MBH-class commercial heating loads
- Plants comparing vertical fire-tube footprints in the SVF range
- Buildings planning cascade or hybrid boiler systems with the Unity control
Applicability and support
- Model number
- SVF 2000 S2
- Canadian availability
- unknown
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Weil-McLain. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Maximum input | 2,000 MBH | Maximum input per the Technical Specs table on the official SVF product page. |
| Output | ||
| Gross output | 1,920 MBH | Gross output per the Technical Specs table on the official product page. |
| Net AHRI rating | Not printed on the page's Technical Specs table for this group | The 500–600 and 1500–3000 Series 2 pages print gross output and thermal efficiency without a net AHRI column; the record keeps the page's columns as printed. |
| Efficiency | ||
| Thermal efficiency | 96 % | Thermal efficiency per the Technical Specs table; the SVF is certified ENERGY STAR and heat-pump ready per the product pages. |
| Domestic hot water | ||
| Domestic hot water | Heating-only commercial boiler — domestic hot water comes from a separate indirect tank or water heater | |
| Venting and air | ||
| Air intake / exhaust vent diameter | 10"/8" | Vent diameter per the Technical Specs table; Category II/IV venting per the product pages, with a 3-in-1 vent adapter supplied. |
| Physical and connections | ||
| Maximum working pressure | 160 psi | Maximum working pressure per the Technical Specs table. |
| Supply / return water connections | 3" flange | Supply/return water connection size per the Technical Specs table. |
| Gas connection size | 2" NPT | Gas connection size per the Technical Specs table. |
| Length x width x height | 84 5/16" x 35 3/8" x 80 3/4" | Dimensions per the Technical Specs table. |
| Approximate shipping weight | 2,500 lb | Approximate shipping weight per the Technical Specs table; integrated roller casters and a shipping ramp are standard. |
| Operating limits and other | ||
| Turn-down ratio | 10:1 | Turn-down ratio per the Technical Specs table. |
| Control | Unity 2.0 color touchscreen Nuro controls | Per the product pages: enhanced diagnostics, troubleshooting and remote monitoring; Modbus supplement published. |
| Fuel | Natural gas | The SVF product pages list gas only. |
Manuals
- SVF 1000 Series 1 | SVF 1500-3000 Series 2 Boiler Manual, 550100255_0823 (Aug 2023)550100255_0823 · 2023-08
- SVF 725-1000 User Manual
- SVF 725-3000 Advanced Manual, 550143071_0924 (Sep 2024)550143071_0924 · 2024-09
Alerts documented for this model
None documented yet.
Frequently asked questions
What are the SVF 2000 S2's ratings?
2000 MBH maximum input, 1920 MBH gross output and 96% thermal efficiency per the official Technical Specs table.
What vent size does the SVF 2000 S2 use?
The Technical Specs table prints a 10"/8" air intake / exhaust vent diameter; the SVF line uses Category II/IV venting with a supplied 3-in-1 vent adapter.
What control does the SVF 2000 S2 use?
The Unity 2.0 color touchscreen Nuro control with enhanced diagnostics, troubleshooting and remote monitoring, per the official product pages.
Questions about the Weil-McLain SVF 2000 S2?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Weil-McLain SVF 500Same series
- Weil-McLain SVF 600Same series
- Weil-McLain SVF 725Same series
- Weil-McLain SVF 850Same series
- Weil-McLain SVF 1000Same series
- Weil-McLain SVF 1500 S2Same series
- Weil-McLain SVF 2500 S2Same series
- Weil-McLain SVF 3000 S2Same series
- SVF (Stainless Vertical Firetube) series hub
- Buying guide
Sources and verification
- Weil-McLain — SVF Stainless Vertical Firetube (SVF 2000 S2) · accessed September 9, 2026
- SVF 1000 Series 1 | SVF 1500-3000 Series 2 Boiler Manual, 550100255_0823 (Aug 2023) · 550100255_0823 · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.