Bosch Thermotechnology
Buderus G315/5
- Input
- —
- Output (max)
- —
- AFUE
- —
The Buderus G315/5 is a discontinued commercial cast-iron boiler block with 5 sections, 433 MBtu/h gas input (3 GPH oil) and a 304 MBtu/h IBR rating.
Canada-wide gas boiler information · On-site service in Greater Vancouver, BC
Boilers.ca is a brand of ROMA Heating & Cooling · Licensed gas contractor LGA0202903
Comparison
Verdict in brief
The discontinued G315/5 and G315/9 are commercial cast-iron boiler blocks with 3" supply/return, 87 psig MAWP and Thermostream return-water mixing. The /5 has 5 sections, 433 MBtu/h gas input, 350 MBtu/h gross output and 304 MBtu/h IBR at 1,197 lb shipping; the /9 has 9 sections, 924 MBtu/h input, 768 MBtu/h gross, 668 MBtu/h IBR and 1,973 lb shipping.
Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.
| Specification | Buderus G315/5 | Buderus G315/9 |
|---|---|---|
| Boiler sections | 5 | 9 |
| Gas input | 433 MBtu/h | 924 MBtu/h |
| Oil input | 3 GPH | 6.4 GPH |
| Rated gross output | 350 MBtu/h | 768 MBtu/h |
| IBR rating | 304 MBtu/h | 668 MBtu/h |
| Boiler horsepower | 10.4 HP | 22.9 HP |
| Water content | 37.8 gal | 67.4 gal |
| Weight, shipping (approx.) | 1,197 lb | 1,973 lb |
| Weight, operating (approx.) | 1,512 lb | 2,545 lb |
Both sizes are documented in the G315/5 through G315/9 engineering submittal sheets, which share the ASME Section IV construction, GL-180M high-silicon cast iron, full three-pass design, 87 psig maximum working pressure and 3" supply/return connections.
Capacity scales with sections: 5 to 9 sections, 3.00 to 6.40 GPH oil input, 433 to 924 MBtu/h gas input, 350 to 768 MBtu/h rated gross output, 304 to 668 MBtu/h IBR rating and 10.4 to 22.9 boiler horsepower. AHRI efficiencies are 84.2-84.5% natural-gas combustion / 80.8-83.1% thermal and 86.8-87.1% oil combustion / 83.3-85.7% thermal.
Physical rows: heating surface 50.6 to 96.9 sq ft, water content 37.8 to 67.4 gal, shipping weight 1,197 to 1,973 lb and operating weight 1,512 to 2,545 lb. Both are boiler blocks for field-supplied oil, gas or combination burners and are discontinued with per-size submittal sheets in Bosch's US commercial-discontinued archive.
Bosch Thermotechnology
The Buderus G315/5 is a discontinued commercial cast-iron boiler block with 5 sections, 433 MBtu/h gas input (3 GPH oil) and a 304 MBtu/h IBR rating.
Bosch Thermotechnology
The Buderus G315/9 is a discontinued commercial cast-iron boiler block with 9 sections, 924 MBtu/h gas input (6.4 GPH oil) and a 668 MBtu/h IBR rating.
No - they are boiler blocks for forced-draft firing; allowable fuels are natural gas, LP and oil #2, with approved burners listed by Bosch and burner-dependent voltages and pressures.
The /9 is 1,973 lb shipping / 2,545 lb operating against 1,197 / 1,512 lb for the /5, per the engineering submittal sheets.
It is Buderus's return-water preheat and mixing design inside the cast-iron block that avoids condensate forming in the combustion chamber; the submittal sheets note no minimum return-water temperature or minimum flow requirement.
A consultation includes a heat-loss review so the size is right the first time.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.