Skip to content
Boilers.caby ROMA Heating & Cooling

Comparison

Camus Dynaforce DR300 vs DR350

Verdict in brief

Both the Camus Dynaforce DR300 and the Camus Dynaforce DR350 belong to the Camus Hydronics Dynaforce Series line of condensing boilers. The Camus Dynaforce DR300 is documented at 300 MBTU/hr input, 282 MBTU/hr output and 99% efficiency, while the Camus Dynaforce DR350 is documented at 350 MBTU/hr input, 329 MBTU/hr output and 99% efficiency. Camus Dynaforce DR350 lists 50 MBTU/hr more input than Camus Dynaforce DR300 (350 MBTU/hr against 300 MBTU/hr). Both list the same published efficiency of 99%. Both list the same published shipping weight of 500 lb.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of Camus Dynaforce DR300 and Camus Dynaforce DR350
SpecificationCamus Dynaforce DR300Camus Dynaforce DR350
Input, maximum300 MBTU/hr350 MBTU/hr
Output, maximum282 MBTU/hr329 MBTU/hr
Turndown ratio5:15:1
Heat-exchanger water content5.7 US gal5.7 US gal
Weight500 lb500 lb
VentingCategory II or IV (SS / AL29-4C, PPE / polypropylene; PVC and CPVC for select systems — consult factory)Category II or IV (SS / AL29-4C, PPE / polypropylene; PVC and CPVC for select systems — consult factory)
Water connections1 1/2" NPT1 1/2" NPT
Gas connection3/4" NPT3/4" NPT
Electrical requirement120 VAC, 60 Hz — 20 A max (boiler only)120 VAC, 60 Hz — 20 A max (boiler only)
IgnitionDirect igniter, 3 ignition tries then lockoutDirect igniter, 3 ignition tries then lockout
Modulation drivePulse-width modulation (DR300–DR1000)Pulse-width modulation (DR300–DR1000)
Efficiency99 %99 %
Max. working pressure160 psig160 psig
System return temperature40 °F40 °F
Heat exchanger439 SS welded 12-pass watertube, 316L waterways439 SS welded 12-pass watertube, 316L waterways
ControlHoneywell SOLA touchscreen; Modbus RTU; cascade up to 8Honeywell SOLA touchscreen; Modbus RTU; cascade up to 8
CertificationCSA (ANSI Z21.13 / CSA 4.9); ASHRAE 90.1CSA (ANSI Z21.13 / CSA 4.9); ASHRAE 90.1

What actually separates them

Published ratings: the Camus Dynaforce DR300 is rated 300 MBTU/hr input, 282 MBTU/hr output and 99% efficiency; the Camus Dynaforce DR350 is rated 350 MBTU/hr input, 329 MBTU/hr output and 99% efficiency. Camus Dynaforce DR350 lists 50 MBTU/hr more input than Camus Dynaforce DR300 (350 MBTU/hr against 300 MBTU/hr). Both list the same published efficiency of 99%.

Both records print the same turndown (5:1), boiler water content (5.7 US gal), shipping weight (500 lb) and venting (Category II or IV (SS / AL29-4C, PPE / polypropylene; PVC and CPVC for select systems — consult factory)), per the cited sources.

Camus Hydronics

Camus Dynaforce DR300

Status unknownSold in Canada
Input
Output (max)
282 MBTU/hr
AFUE

The Camus Dynaforce DR300 is the 300 MBH hydronic-heating size of Camus' fully condensing watertube line: 300 MBTU/hr input, 282 MBTU/hr output, up to 99% thermal efficiency and 5:1 turndown on the Honeywell SOLA control.

Natural gasPropaneHeating-only

Camus Hydronics

Camus Dynaforce DR350

Status unknownSold in Canada
Input
Output (max)
329 MBTU/hr
AFUE

The Camus Dynaforce DR350 is the 350 MBH hydronic-heating size of Camus' fully condensing watertube line: 350 MBTU/hr input, 329 MBTU/hr output, up to 99% thermal efficiency and 5:1 turndown on the Honeywell SOLA control.

Natural gasPropaneHeating-only

Frequently asked questions

Which of the two has the higher maximum input?

The Camus Dynaforce DR350 lists 350 MBTU/hr, against 300 MBTU/hr on the Camus Dynaforce DR300, per the cited documentation.

Which model is more efficient?

Both list the same efficiency of 99%.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate