Skip to content
Boilers.caby ROMA Heating & Cooling

Comparison

Lochinvar FTXL FTX400 vs FTX500

Verdict in brief

The FTXL FTX400 and FTX500 are the two smallest FTXLs and are twins below the maximum: both fire near 39.9-50 MBH minimum, use 2" water with 4" air/vent, and rate 10:1 turndown. The 500 lifts input to 500 MBH with 489 MBH gross output, at 97.7% submittal thermal efficiency against the 400's 98.0%.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of Lochinvar FTXL FTX400 and Lochinvar FTXL FTX500
SpecificationLochinvar FTXL FTX400Lochinvar FTXL FTX500
Heating input, minimum39.9 MBH50 MBH
Heating input, maximum399 MBH500 MBH
Gross output391 MBH489 MBH
Net AHRI water rating340 MBH425 MBH
Efficiency (thermal)98 %97.7 %
Water content13.2 gal11.9 gal
Space-heating water connections2"2"
Gas connection1"1"
Air inlet size4"4"
Vent size4"4"
Shipping weight478 lb504 lb

What actually separates them

Both are floor-mounted stainless steel fire-tube condensing boilers with the SMART TOUCH control and CON·X·US, ENERGY STAR certification and an ASME H stamp, on 2" water and 1" gas connections with 4" air intake and 4" vent per the I&O ratings table.

The FTXL submittal gives both sizes 10:1 turndown — minimum fire is 39.9 MBH on the 400 and 50 MBH on the 500 — and prints 98.0% thermal efficiency for the 400 against 97.7% for the 500. Gross output rises from 391 to 489 MBH and the AHRI net rating from 340 to 425 MBH.

Water content actually falls at the 500 (13.2 to 11.9 gallons) and shipping weight rises from 478 to 504 lb per the submittal. Both vent in PVC, CPVC, polypropylene or AL29-4C stainless steel to 100 equivalent feet, so the decision reduces to the building's design-day load.

CurrentSold in Canada
Input
39.9–399 MBH
Output (max)
—
AFUE
—

The FTXL FTX400 is the entry commercial FTXL: 39.9 to 399 MBH input with 391 MBH gross output and a 340 MBH AHRI net rating at 98.0% submittal thermal efficiency, with 10:1 turndown.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
50–500 MBH
Output (max)
—
AFUE
—

The FTXL FTX500 fires 50 to 500 MBH with 489 MBH gross output and a 425 MBH AHRI net rating at 97.7% submittal thermal efficiency, keeping 2" water connections and 4" venting.

Natural gasPropaneHeating-only

Frequently asked questions

Which FTXL has the higher efficiency?

The FTX400: 98.0% thermal efficiency per the submittal against the FTX500's 97.7%. Lochinvar's press-release claim of 98.3% for the whole line is contradicted by the per-model submittal figures Boilers.ca uses.

Do the FTX400 and FTX500 vent the same way?

Yes — both use 2" water connections with a 1" gas connection and 4" air and vent, vented to 100 equivalent feet per the submittal.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate