Skip to content
Boilers.caby ROMA Heating & Cooling

Comparison

P-K THERMIFIC VELOX N750 vs N1000

Verdict in brief

The THERMIFIC VELOX N750 and N1000 share the same 54" × 32" × 52" shipping box, 800 lb operating weight, 6.2-gallon water content, 116 sq. ft. heated surface, 1-1/4" gas and 2-1/2" water connections; the N1000 adds 250 MBH of input and 212 MBH of output, raises minimum input from 604,000 to 610,000 BTU/hr and turndown from 1.2:1 to 1.6:1.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of P-K THERMIFIC VELOX N750 and P-K THERMIFIC VELOX N1000
SpecificationP-K THERMIFIC VELOX N750P-K THERMIFIC VELOX N1000
Minimum input604 MBH610 MBH
Turndown ratio1.2:11.6:1
Input750 MBH1,000 MBH
Output638 MBH850 MBH
Efficiency (CSA certified)85 %85 %
Main gas connection1 1/4" NPT-F1 1/4" NPT-F
Boiler supply / return2 1/2" NPT (supply F / return M)2 1/2" NPT (supply F / return M)
Operating weight800 lb800 lb
Shipping weight820 lb820 lb
Boiler water content6.2 gal6.2 gal
Boiler HP1925.4
Heated wet surface area116 sq. ft.116 sq. ft.
Flow rate @ 20°F ΔT63.8 GPM85 GPM
Combustion air inlet8" dia. stub8" dia. stub
Exhaust vent6"6"
Shipping width32 in32 in
Shipping length54 in54 in
Shipping height52 in52 in

What actually separates them

P-K's submittal prints the N750VX at 750,000 BTU/hr input / 638,000 BTU/hr output with a 604,000 BTU/hr minimum and 1.2:1 turndown, and the N1000VX at 1,000,000 / 850,000 with a 610,000 BTU/hr minimum and 1.6:1 turndown. The VELOX is a non-condensing, Category I appliance, so its turndown is far shallower than the MODU-FIRE FD's.

The package is identical: 54" × 32" × 52" shipping dimensions, 800 lb operating and 820 lb shipping weights, 6.2 gallons of water, 116 sq. ft. heated surface, 8" combustion-air stub, 6" exhaust, 1-1/4" NPT gas and 2-1/2" NPT supply/return.

Flow at a 20°F ΔT rises from 63.8 to 85 GPM. Both operate at a CSA certified 85% thermal efficiency as Category I non-positive, non-condensing appliances.

Patterson-Kelley

P-K THERMIFIC VELOX N750

CurrentCanadian status unknown
Input
604–750 MBH
Output (max)
638 MBH
AFUE
—

The P-K THERMIFIC VELOX N750 is a packaged non-condensing commercial boiler rated 750 MBH input and 638 MBH output in Patterson-Kelley's published submittal, with a 604 MBH minimum input and a 800 lb operating weight.

Natural gasHeating-only
CurrentCanadian status unknown
Input
610–1000 MBH
Output (max)
850 MBH
AFUE
—

The P-K THERMIFIC VELOX N1000 is a packaged non-condensing commercial boiler rated 1000 MBH input and 850 MBH output in Patterson-Kelley's published submittal, with a 610 MBH minimum input and a 800 lb operating weight.

Natural gasHeating-only

Frequently asked questions

How much turndown does each have?

1.2:1 for the N750VX and 1.6:1 for the N1000VX, per the submittal.

What venting category is required?

VELOX requires Category I (non-condensing) venting per the submittal.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate