Skip to content
Boilers.caby ROMA Heating & Cooling

Comparison

RBI Futera XLF 8000 vs Futera XLF 10000

Verdict in brief

The Futera XLF 8000 and 10000 share the same 68-3/8" × 55-1/3" cabinet, 3" natural-gas and 6" water connections and blank LP row; the 10000 adds 2,000 MBH of input and about 1,686 MBH of output, grows 9" taller, steps the flue set up from 14"/14"/14" to 16"/16"/16" and ships 274 lb heavier.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of RBI Futera XLF 8000 and RBI Futera XLF 10000
SpecificationRBI Futera XLF 8000RBI Futera XLF 10000
Input, maximum8,000 MBH10,000 MBH
Boiler output6,824 MBH8,510 MBH
Efficiency (AHRI boiler)85.9 %85.9 %
Turndown5:15:1
Gas connection (natural gas)3"3"
Gas connection (LP)not printednot printed
Water connection6"6"
Flue ventCat I 14" / Cat II 14" / Cat IV 14"Cat I 16" / Cat II 16" / Cat IV 16"
Unit width55.333 in55.333 in
Unit depth68.375 in68.375 in
Unit height68.938 in77.938 in
Shipping weight3,176 lb3,450 lb

What actually separates them

RBI prints 8,000 MBH input / 6,824 MBH boiler output for the MB 8000 and 10,000 MBH / 8,510 MBH for the MB 10000 — the largest copper-fin boilers in the line. Depth, width, 3" gas and 6" water connections are identical.

Height rises from 68-15/16" to 77-15/16" and shipping weight from 3,176 lb to 3,450 lb. Flue options step up from 14" Category I/II/IV to 16" across all three categories.

Neither row prints an LP connection; both are 85.9% AHRI Boiler Efficiency with 5:1 full modulation. At these sizes the mechanical-room plan, rigging and vent design dominate the selection.

CurrentCanadian status unknown
Input
—
Output (max)
6,824 MBH
AFUE
—

The RBI Futera XLF 8000 is a gas-fired copper-fin commercial boiler rated 8000 MBH input and 6824 MBH boiler output in RBI's published ratings table, with 5:1 full modulation, Category I/II/IV venting and a 3176 lb shipping weight.

Natural gasHeating-only
CurrentCanadian status unknown
Input
—
Output (max)
8,510 MBH
AFUE
—

The RBI Futera XLF 10000 is a gas-fired copper-fin commercial boiler rated 10000 MBH input and 8510 MBH boiler output in RBI's published ratings table, with 5:1 full modulation, Category I/II/IV venting and a 3450 lb shipping weight.

Natural gasHeating-only

Frequently asked questions

What is the output difference?

6,824 MBH boiler output for the MB 8000 and 8,510 MBH for the MB 10000, per RBI's ratings table.

What flue sizes are printed?

14" Category I/II/IV on the MB 8000 and 16" on the MB 10000.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate