Air pressure switch
An air pressure switch proves that the combustion fan is moving air and that the vent path is clear before the boiler is allowed to fire. This page explains what the switch does, how blocked vents and fan faults show up, and what a licensed technician checks.
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call ROMA about the boiler. Official guidance: FortisBC gas leaks and odour.
Safety first
If you smell gas, leave the building and call FortisBC at 1-800-663-9911 or 911 from outside. If a carbon-monoxide alarm sounds, leave immediately with everyone in the building and call 911 from outside; Technical Safety BC and FortisBC give the same instruction, because a vent or air problem can turn a boiler into a CO source.
The air pressure switch is a safety device, and it must never be jumpered, taped closed or bypassed to make a boiler run. It exists precisely to stop the burner when combustion air or venting is not proven, and defeating it removes the protection that keeps flue gases out of the home.
Combustion-air and venting work on a gas appliance is licensed work in British Columbia under Technical Safety BC. Homeowner checks stop at clearing snow from an outdoor terminal and reading the display.
What it does in a gas boiler
Before the gas valve opens, the boiler has to prove that air is moving through the combustion chamber and out the vent. The air pressure switch, sometimes called an air-proving switch or APS, senses the pressure produced by the combustion fan or the difference between the fan's inlet and outlet. Only when its contacts close will the control continue to ignition.
On modern condensing boilers the switch may be a differential pressure switch connected by a small sensing hose, or a pressure sensor read by the control. Navien's NCB-H manual lists the air pressure sensor among its safety appliances alongside the flame rod and ignition detector, and shows the APS on the boiler's internal diagram. Viessmann's Vitocrossal 300 CA3B service instructions document two air pressure switches, LDW1 and LDW2, whose states the control displays during its start-up sequence, when it tests the switches and the fan together.
The air pressure switch works with the control's fan logic. IBC's SL G3 troubleshooting treats low fan speed as an alarm condition, noting that the fan must reach its required speed at the end of pre-purge before the boiler can proceed, and it reports a separate vent high-pressure alarm when a pressure switch opens during pre-purge or heating.
How it fails
Most air pressure faults are not switch failures at all; they are airflow failures. A vent terminal blocked by snow, leaves or a bird nest, a blocked combustion-air intake, a sagging or separated vent joint, or condensate pooled in the flue path all change the pressure the switch sees. Viessmann's CA3B fault table lists flue-gas back pressure and backed-up condensate among the causes of an air pressure switch fault, and wind influence on the terminal among others.
The switch's own parts fail too. The sensing hose can crack, kink or fill with condensate; the hose ports can plug; the diaphragm can stiffen; and the contacts can stick. A fan that slows or stops, whether from a failing bearing or a control fault, produces the same symptom as a blocked vent.
The boiler's response is protective: it will not fire, and it usually locks out with a fault naming air pressure, fan pressure or vent pressure. Viessmann's table distinguishes a switch that never sees pressure, a switch that stays closed when it should open, and a switch that drops out mid-operation, because each points at a different cause.
Safe things to check
The most useful homeowner action is outdoors: keep vent and intake terminals clear of snow, ice, leaves and stored items, and never cover them. Navien's manual puts responsibility for keeping the exhaust and intake terminations free of snow, ice and other blockages on the building owner, along with scheduling routine maintenance.
Note the exact alert text or code, and whether the fan sounds different, stops, or runs on after the boiler shuts down. If a CO alarm sounds at any point, leave the building and call 911 from outside; do not open windows and investigate.
Do not remove the boiler cover to check hoses, and do not reset repeatedly to push the boiler through a vent fault. If the boiler will not fire because of an air or vent alert, it is telling you something is blocking combustion air, and that is a service call.
What a licensed technician will check
A technician verifies the whole air path: the fan runs and reaches its specified speed, the vent and intake are clear from the boiler to the terminal, the sensing hoses are intact and dry, and the switch changes state at the correct pressure. Viessmann's service instructions walk through checking the air pressure switch hose and connections and replacing a switch that tests faulty, and IBC's manual directs the technician to check fan RPM and vent blockage for its air-flow alarms.
Where the switch is sound, the technician looks for the underlying airflow problem, because replacing a switch that is correctly reporting a blocked vent fixes nothing. Combustion is analysed and the boiler is run through a full cycle before it is returned to service.
Air pressure faults are among the most common winter no-heat calls, and many are resolved by clearing a terminal or a blocked condensate path. Call ROMA Heating & Cooling when your boiler reports a vent, fan or air pressure fault.
Frequently asked questions
Can I bypass the air pressure switch to get heat tonight?
Never. The switch is what stops the boiler from firing when combustion air or venting is not proven, and bypassing it can let flue gases into the home. A fault needs diagnosis, not a jumper.
Why does my boiler fail only when it snows?
Snow blocking the vent or intake terminal is a classic cause of air pressure faults. Clear the terminal safely from outside without reaching into the pipe, and if the fault returns, have the venting inspected.
Is the air pressure switch the same as the blocked-vent switch?
No. The air pressure switch proves fan airflow on fan-assisted and condensing boilers. The blocked-vent or spill switch is a different device used on atmospheric boilers to detect flue gas spilling at the draft hood.
Book a consultation
A technician reviews your building and options. Requests are confirmed by ROMA.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Viessmann Vitocrossal 300 CA3B service instructions · 5838 946 - 16 · accessed September 9, 2026
- Navien NCB-H Installation and Operation Manual · accessed September 9, 2026
- IBC SL G3 Commercial Installation & Operating Manual — SL 26-260 G3, SL 40-399 G3 · 120-270E12 · accessed September 9, 2026
- FortisBC — Carbon monoxide safety · accessed September 9, 2026
- Technical Safety BC — Carbon monoxide safety · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.