Component
Air separator (automatic air eliminator)
An air separator — also called an automatic air eliminator — removes the tiny air bubbles that form as heating water warms, protecting a hydronic system from air locks, noisy pipes and corrosion. This page explains what the component does, how it fails, and what a licensed technician checks before servicing one.
What it does in a hydronic system
Tap water holds dissolved air, and as that water warms in a boiler the dissolved gas comes out of solution as tiny bubbles. In a sealed hydronic loop the bubbles rise to high points, where they grow into air pockets that block radiators, make circulators hum against air locks, and leave oxygen sitting against steel piping and fittings. Getting air out of the water is part of a hydronic system's normal operation, and the air separator is the component built for that job.
An air separator works by slowing the water and letting the smallest bubbles coalesce and rise out of the flow, where an air vent at the top releases them. Separators are installed in the boiler piping rather than somewhere invisible, and the manuals are specific about where. IBC's SL G3 manual directs that microbubble air eliminators be installed as close as reasonably possible to the supply outlet of the boiler, and Navien's NCB-H manual gives the companion rule: connect an air separator to the expansion tank only if the separator is located on the suction side of the system pump, and the make-up water connection may attach at the same location as the expansion tank's connection. The two rules matter because a separator on the wrong side of a pump can pull air back in instead of removing it.
In the wall-hung condensing installations that dominate Greater Vancouver, the separator is usually a compact in-line unit in the near-boiler piping, sharing its location with the expansion tank and the fill connection. On older systems it may be a larger tank-style air scoop on the supply main, and some boilers manage air internally with their own automatic vents and purge routines.
How it fails
Air separators fail slowly, and usually from neglect rather than a single defect. Sludge and magnetite carried in the system water can coat the internal baffles or media until the unit stops slowing the flow effectively, and the float mechanism in the vent at the top can stick closed — so air collects inside the unit and stops being released — or stick open, dribbling water onto the floor. A separator that has never been inspected on a dirty system is doing progressively less of its job.
The symptoms look like the symptoms of air anywhere in a hydronic system: radiators that need bleeding again a few weeks after the last bleed, gurgling or rushing sounds in the pipes, a circulator that hums when a zone calls, and heating that is uneven room to room. None of these proves the separator itself is at fault, because air has other entry points: a leak on the return side can pull air in continuously, fresh fill water brings new dissolved air every time the system is topped up, and a failing air vent upstream can feed air back in. That is why technicians diagnose the air path rather than swapping the separator on sight.
Safe things to check
Listening and looking covers the homeowner's job. Note whether the pipes gurgle shortly after the boiler fires, whether the same radiators need bleeding week after week, and whether the pressure gauge drops between fills — that combination points at air entering the system somewhere. Look at the floor under the separator and its vent for water staining or drips, which suggest the vent is passing water instead of air.
Do not open the separator's vent cap, loosen fittings, or bleed the unit itself while the system is hot and pressurized; an automatic vent that needs attention is a service item, not a DIY one. Keep the area around the boiler and the separator clear so a technician can reach them, and if the problem is recurring air, tell the technician when it started and whether any recent work touched the piping or fill valve.
What a licensed technician will check
A technician treats air complaints as a system diagnosis. They confirm the separator is positioned the way the manuals require — close to the boiler supply outlet as IBC directs, and on the suction side of the pump where the expansion tank ties in, as Navien describes — then inspect the unit's internals and vent, cleaning or replacing what has fouled. The system is purged properly through its drain and air-vent points, which clears the pockets the separator could not reach on its own.
The technician also looks for the air sources a separator cannot fix: leaks that draw air in, an under-charged or waterlogged expansion tank, or a fill connection that keeps introducing air with fresh water. Where the vent assembly is worn it is replaced, and the system is refilled to its correct cold pressure and observed through a heating cycle. Recurring air in a system that has been properly de-aerated is worth a call to ROMA Heating & Cooling rather than another season of bleeding radiators.
Frequently asked questions
Why do I keep bleeding radiators even though my boiler has an air separator?
A separator removes air that is already in the water, but it cannot keep up with a system that is continuously drawing in fresh air through a leak, or with constant topping-up from the fill valve. Recurring air means the technician should look for the source, not just the separator.
Does every hydronic system need an air separator?
Not every system is piped with a separate one — some boilers handle air with internal vents and purge routines — but where a separator is installed, its position matters. IBC's manual calls for it close to the boiler supply outlet, and Navien's manual ties its location to the pump suction side and the expansion-tank connection.
Can trapped air actually damage a heating system?
Yes, in a slow way. Air pockets block heat delivery and starve circulators, and oxygen left against steel components accelerates corrosion, which is why hydronic water is supposed to stay in a closed, de-aerated loop rather than being refreshed constantly.
Book a consultation
A technician reviews your building and options. Requests are confirmed by ROMA.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- IBC SL 10-85 G3 / SL 14-115 G3 / SL 20-160 G3 / SL 30-199 G3 Installation & Operating Manual · 120-276E13 · accessed September 8, 2026
- Navien NCB-H Installation and Operation Manual · accessed September 8, 2026
- FortisBC — Appliance maintenance and safety · accessed September 8, 2026
Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.