An automatic air vent is a float-operated valve that lets air escape from a heating system by itself and closes the moment water arrives, so air leaves at high points without anyone bleeding a radiator. This page explains how the vent works, how it fails, and what a licensed technician checks.
What it does in a hydronic system
Air collects at the highest points of a hydronic system, and those points are exactly where a person cannot conveniently stand with a bleed key every week. An automatic air vent does the job unattended: inside a small brass housing a float sits in a chamber; when air fills the chamber the float drops and opens a tiny valve that lets the air out, and when water arrives the float rises and seals the vent again. Mounted at a high point — the top of an air separator, the crown of a supply main, or a boiler's unused supply connection — it quietly removes the air that would otherwise find its way into radiators and pumps.
The installation rules come from the physics of the air cushion that sealed systems rely on. Weil-McLain's Ultra manual tells the installer to fit an automatic air vent on top of the air separator for diaphragm-tank systems, and where the boiler sits above the system main, an automatic air vent in the top of the outgoing boiler piping to prevent air pocketing. The same manual is explicit about the reverse case: on closed-type expansion tank systems, automatic air vents must not be installed, because the air must stay in the system and return to the tank to provide its cushion. Weil-McLain's CGa manual summarizes the modern arrangement: systems with a diaphragm or bladder tank need at least one automatic air vent, preferably on top of an air eliminator.
Some boilers use automatic air venting as part of their own piping. IBC's SL G3 manual, for example, lists an auto air vent (part P-195C) or a flushing valve for the supply connections when the heating loads are all on one side, and the service checklist confirms the trap and venting path are clear after work. On a typical Greater Vancouver installation, the vents a homeowner can see are small brass caps with a tiny outlet hole, sitting at pipe high points or on the separator.
How it fails
An automatic air vent fails in one of two directions. Stuck closed — the common failure as mineral deposits and sludge seize the float or the valve seat — and the vent silently stops venting, so air builds up exactly as if the vent were not there. Stuck open, and water weeps or streams from the vent cap, which shows up as drips, staining under the vent, and a system that needs pressure topped up more often than it should.
The failure is rarely dramatic. Weil-McLain's Ultra start-up checklist treats the vents as a regular item — automatic air vents, if used, are opened one full turn at start-up and left to work — and the corrosion of the cap and seat over years is what usually ends their service life. A vent that leaks onto a boiler top can also do secondary damage, since water finds its way into seams and electrical fittings over time.
Safe things to check
Look at the small vent caps you can see — usually on the air separator or the boiler's high points — for drips, staining, or a constant fine spray of water, which means the valve is passing water instead of sealing. Listen for the hiss of air releasing right after the boiler fires; a little air at start-up is normal on some systems, but air that hisses out for days after a fill is a sign the system is pulling air in.
Do not unscrew or pry open an automatic vent cap while the system is hot and under pressure, and do not cap a vent that leaks as a temporary fix, because sealing a vent that is meant to release air changes how the system behaves. Note what you saw and let a technician decide whether the vent or something upstream is the problem.
What a licensed technician will check
During annual servicing the vents get a deliberate check rather than a glance. The technician confirms each automatic vent opens and reseats, cleans or replaces a cap assembly that has fouled, and verifies that the vent location matches the system's expansion tank type — the rule Weil-McLain states plainly that closed-type tank systems must not have automatic vents fitted, since they would bleed away the air cushion the tank needs.
Where a vent sits on a boiler's internal supply connection, the work follows the boiler manual — IBC's SL G3 service section has the technician confirm the air path, trap and venting are in place and clear after any heat-exchanger work. A leaking vent is usually replaced rather than rebuilt, and the system pressure is re-verified afterwards. If a vent is dripping steadily or air keeps returning after bleeding, call ROMA Heating & Cooling — it is a small part with a simple fix when it is actually the problem.
Frequently asked questions
Water is dripping from the cap of an automatic air vent. What causes that?
A vent that weeps or sprays water has usually failed open: debris or wear has stopped the float from seating. It is a service item — the cap assembly is cleaned or replaced — and the system pressure is re-checked afterwards.
Can I just cap an automatic air vent to stop the drip?
No. The vent is part of how air leaves the system at that point, and sealing it can push air problems back into the radiators and pump. A vent that needs capping to stop a leak needs replacing.
Why does air keep hissing out of my vent weeks after the system was filled?
A system should release a burst of air after a fill and then go quiet. Continuous air means air is being drawn in somewhere — usually a leak on the return side or constant topping-up — and the technician should find the source rather than let the vent work overtime.
Book a consultation
A technician reviews your building and options. Requests are confirmed by ROMA.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Weil-McLain Ultra Series 4 gas-fired water boiler — boiler manual · 550-100-440/1025 · accessed September 8, 2026
- Weil-McLain CGa Series 4 gas-fired water boiler — boiler manual · 550-100-223/0425 · accessed September 8, 2026
- IBC SL 10-85 G3 / SL 14-115 G3 / SL 20-160 G3 / SL 30-199 G3 Installation & Operating Manual · 120-276E13 · accessed September 8, 2026
- FortisBC — Appliance maintenance and safety · accessed September 8, 2026
Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.