A concentric vent kit runs a condensing boiler's exhaust and combustion air through one pipe-within-a-pipe and one wall or roof penetration, using only components approved for that boiler. This page explains how the kits work, why part selection matters, and what a licensed technician checks.
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call ROMA about the boiler. Official guidance: FortisBC gas leaks and odour.
Venting safety first
If a carbon-monoxide alarm sounds, leave the building with everyone inside and call 911 from outside. If you smell gas, leave and call FortisBC at 1-800-663-9911 or 911 from outside. A venting system that is assembled from the wrong parts can leak flue gas into the home or fail to carry it away.
Never mix vent components from different manufacturers, never substitute plumbing pipe or fittings for certified venting, and never modify a kit in the field. In Canada, plastic venting for a condensing appliance must be a certified system under ULC S636, installed as a complete system according to the manufacturer's instructions.
In British Columbia, installing or replacing a boiler vent system is permitted gas work under Technical Safety BC, and the contractor applies for the permit on the homeowner's behalf.
What it does in a gas boiler
A condensing boiler needs both combustion air in and flue gas out. A concentric vent kit combines those two paths into a single assembly: one pipe runs inside the other, with the exhaust discharging through the centre and combustion air drawn through the outer annulus, or the reverse depending on the kit. One hole in the wall or roof serves both, which is neater, simpler to seal and often the preferred look on a finished exterior.
Kits are appliance-specific. Peerless documents optional concentric termination kits for its PureFire boilers, with a 3-inch sidewall kit and a 4-inch sidewall kit for the larger models, plus vertical kits for roof terminations, and its manual counts the concentric kit at three equivalent feet in the vent-length calculation. The same manual warns that the appliance uses a positive-pressure venting system, so all joints must be sealed completely to prevent leakage of flue products into living spaces.
The kit is part of a certified system, and Canadian rules are strict about what may be used. Weil-McLain's GV90+ manual states that when a concentric vent termination is used, do not use DWV, CPVC or ABS pipe; use only PVC schedule 40, and it notes that IPEX PVC concentric terminations use pipe and fittings certified to ULC S636, so where ULC S636 compliance is required, only the matching certified pipe, fittings and cement may be used. Lochinvar's Knight XL manual likewise documents an optional concentric vent termination as a defined sidewall configuration with its own installation requirements.
How it fails
The most serious failure is an unapproved assembly: a kit from one brand fitted to another boiler, ordinary plumbing fittings mixed in, the wrong cement, or a field-made terminal. These combinations are not certified together, and the venting system's seals and clearances are no longer guaranteed, which is how flue gases end up where they should not be.
Installation faults follow: joints not fully cemented or sealed, inadequate support that lets the pipe sag and collect condensate, the wrong slope, an unsealed wall penetration that leaks air or water, or a terminal too close to a window, intake or neighbouring vent. Because the system runs under positive pressure, even a small leak at a joint can push flue gas into a wall cavity or room.
Ice and blockage affect concentric terminals too. The exhaust plume can freeze on the terminal or nearby surfaces in cold weather, and snow can bury a low terminal. When the intake or exhaust is restricted, the boiler reports pressure or airflow faults and stops firing, which is the safety system working.
Safe things to check
From outside, check that the terminal is clear of snow, ice and obstructions and that the pipes are not visibly damaged, separated or sagging. Keep plants, stored items and screens away from it, and do not add decorative covers or extend the pipe yourself.
Note any vent, airflow or pressure alerts on the boiler display and whether they appear in cold or windy weather. If a CO alarm sounds, leave the building and call 911 from outside; if you smell gas, leave and call FortisBC.
If you are planning a renovation near the terminal, or a fence, deck or shed is going up, have the venting checked before the work begins so the clearances and the boiler's air supply are not compromised.
What a licensed technician will check
A technician verifies that the installed kit is the approved one for the boiler and that every component in the run is certified and matched: pipe, fittings, cement and terminal. They measure the installed vent length against the manual's limits, including the equivalent-length value of the kit itself, check support, slope and the wall or roof penetration, and confirm the terminal's clearances to openings and other vents.
The technician also leak-checks the joints and measures combustion with an analyser while the boiler runs, because a positive-pressure vent system must be proven sealed and the appliance must be proven to be burning cleanly. Where a kit is wrong or damaged, it is replaced with the correct certified system rather than patched.
Concentric venting is efficient and tidy when it is done to the manual, and a safety question when it is not. If your boiler's venting was installed or modified by someone other than a licensed contractor, call ROMA Heating & Cooling to have it verified.
Frequently asked questions
Can I use any concentric vent kit on my boiler?
No. The kit must be approved for your boiler model, and in Canada the plastic venting must be a certified system under ULC S636. Mixing brands or using plumbing pipe is not a certified installation.
Why does my vent kit need to be sealed so carefully?
Condensing boiler venting operates under positive pressure, so any unsealed joint can push flue gases into a wall cavity or living space. Peerless's manual warns specifically that all joints must be sealed completely.
Is a concentric kit better than two separate pipes?
It is one approved option. A concentric kit uses a single penetration and a cleaner exterior, while two-pipe venting can offer more routing flexibility. The choice depends on the boiler's manual and the building, and both must meet the same certification and clearance rules.
Book a consultation
A technician reviews your building and options. Requests are confirmed by ROMA.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Peerless PureFire PF-50–PF-399 installation, operating & service manual · IOM PF8248-R9 · accessed September 9, 2026
- Weil-McLain GV90+ Series 2 gas-fired water boiler — boiler manual · 550-143-010/0324 · accessed September 9, 2026
- Lochinvar Knight XL (KBX) installation & operation manual · 100383073 Rev E · accessed September 9, 2026
- Technical Safety BC — homeowner gas permits · accessed September 9, 2026
- FortisBC — Carbon monoxide safety · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.