Component
Flow switch
A flow switch proves that water is actually moving through the boiler before it fires and while it runs. This page explains where flow switches are used in hydronic systems, how they fail, and what a licensed technician checks before repairing or replacing one.
What it does in a hydronic system
Heat has to be carried away from the boiler as fast as the burner makes it. A flow switch is a small device installed in the boiler's water piping that closes an electrical contact when it senses movement, proving to the control that water is circulating. If flow stops — a failed pump, a closed valve, an air lock — the switch opens and the boiler shuts down instead of overheating.
Flow switches appear in a few roles. Some boilers accept one as an additional safety limit: NTI's Trinity TFT and FTG manuals describe an external limit input that is factory-jumpered, and instruct the installer to remove the jumper and wire the normally open contacts of an additional safety switch such as a flow switch when the installation needs one. Other manufacturers list a flow switch as an option where local code requires mechanical proof of flow: Lochinvar's Crest manual states that the boiler can be equipped with a field-supplied outlet flow switch if a mechanical switch is required to meet local requirements, alongside the boiler's own low-flow protection.
On many modern condensing boilers, the same job is done electronically by a flow sensor that reports flow rate to the control rather than a switch that simply opens or closes. Both approaches exist, and both answer the same question: is water moving?
How it fails
Mechanical flow switches fail the way any moving part does. A paddle or vane can collect scale and debris until it no longer swings freely; the pivot or spring can wear; a magnet or reed contact can weaken; and wiring or connectors corrode. Electronic flow sensors fail too, usually through contamination or a sensor circuit fault.
The result is either a boiler that refuses to fire while the pump is clearly running, or one that fires intermittently and locks out on flow-related faults. Weil-McLain's Evergreen fault tables show the pattern: when a proof-of-closure fault appears, the technician is directed to check that the correct pump is on, that the flow switch wiring is sound, and that the switch is actually closing. A switch that never closes protects nothing, but a switch that sticks closed is worse — it can let the boiler fire with no flow at all, which is exactly the condition it exists to prevent.
Safe things to check
Homeowners can confirm the basics. When the thermostat calls for heat, listen at the boiler for the circulator and note whether the boiler fires; then check that any zone valves you control are open. If the boiler is trying to run but shutting down, write down the display message — a fault that names flow or the pump is valuable information.
Do not remove or jumper a flow switch, and do not open the boiler to inspect one. Safety inputs like these are wired into the boiler's firing sequence, and bypassing them removes the protection. If the boiler locks out repeatedly, call for service rather than resetting it into another failure.
What a licensed technician will check
A technician starts with the pump, because a flow fault is more often a circulation problem than a switch problem. They confirm the circulator is powered and running, verify the impeller is actually moving water, check for air locks and closed valves, and measure the temperature difference across the boiler to confirm real flow. Only then do they test the switch itself: verifying power and continuity, checking that it closes and opens at the right times, inspecting the wiring, and comparing behaviour against the manual.
Where the switch has failed, it is replaced with the correct part and the boiler is re-tested through several cycles. Where flow was the real problem, the technician corrects that — purging air, repairing a pump, opening a stuck valve — and the flow switch simply did its job. Either way the repair ends with proof that the boiler fires and runs with proper circulation. If your boiler is locking out on a flow fault, call ROMA Heating & Cooling for diagnosis and repair.
Frequently asked questions
The pump is running, so why does the boiler say there is no flow?
A running pump does not guarantee moving water: air locks, a closed valve, a failing impeller or a clogged strainer can stop circulation while the motor still spins. The technician checks flow first, then the switch.
Is a flow switch the same as a flow sensor?
No. A flow switch is a mechanical device that opens or closes a contact; a flow sensor measures flow rate and reports it to the control. Both can trigger boiler faults, but they are tested and replaced differently.
Can a flow switch be bypassed to get heat back on?
No. Jumpering a flow switch removes protection the boiler depends on and can lead to overheating and heat exchanger damage. If the switch has failed, it should be tested and replaced by a technician.
Book a consultation
A technician reviews your building and options. Requests are confirmed by ROMA.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- NTI Trinity Tft 60-399 Installation and Operation Instructions · 99984535 (2024-04-08) · accessed September 9, 2026
- Lochinvar Crest with Hellcat (FCB) Installation & Operation Manual — Models 1000–6000 · 100343224 · Rev U · accessed September 9, 2026
- Weil-McLain Evergreen Pro 110-155 gas-fired water boiler — boiler manual · 550-100-210/D 1222 · accessed September 9, 2026
- FortisBC — Appliance maintenance and safety · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.