Skip to content
Boilers.caby ROMA Heating & Cooling

Component

Gaskets and seals

Gaskets and seals are the small parts that keep a boiler's gas, flue gases, water and condensate where they belong. They harden and compress with every heating cycle, and the manuals are clear that damaged gaskets are replaced rather than reused — especially on the combustion side, where a failed seal is a flue-gas leak. This page explains what gaskets and seals do, how they fail, and what a licensed technician checks.

Safety first

If you smell gas, leave the building and call FortisBC at 1-800-663-9911 or 911 from outside before anything else. If a carbon-monoxide alarm sounds, leave the building and call 911 from outside. Combustion gaskets seal the boundary between the burner and the room, so a failed gasket there can release flue gases indoors — an odourless hazard that alarms detect and people cannot.

NTI's TFT manual states the risk directly in its venting instructions: improper gasket seating can cause leakage and eventual failure of the sealing gasket, and gasket failure and flue gas leakage may result in serious injury or death. That is why gasket work is done by licensed gas contractors under the rules Technical Safety BC sets for gas appliances in British Columbia.

What they do in a hydronic system

A boiler is assembled from parts that must seal against each other, and gaskets and seals are what make those joints tight. On the combustion side, gaskets seal the burner plate, the combustion chamber lid, the fan and the ignitor, and the vent pipe adapters — NTI's manual notes that its vent adapters incorporate three separate seals, one for each pipe material, and shows how each gasket must be positioned. On the water side, gaskets and O-rings seal sensor fittings, unions, plate heat exchangers and maintenance ports.

The manuals treat these parts as consumables, not permanent fixtures. NTI's annual maintenance procedure instructs the technician to remove the burner, clean it if necessary, and reattach it ensuring the gasket is in perfect condition and reinstalled, replacing it if necessary. Its combustion-chamber cleaning instructions end with a blunt rule: replace any gaskets or insulation discs that show any signs of damage and do not re-use them. Viessmann's combi service procedure removes and disposes of the plate heat exchanger gaskets and installs new ones, with a specified screw torque.

Gaskets also seal places that are easy to forget. IBC's SL G3 troubleshooting guide tells the technician inspecting a rollout-switch fault to inspect the lid, fan and ignitor gaskets, because a combustion-chamber seal that has failed lets heat and flue gases escape into the cabinet. Navien's maintenance instructions have the technician check that the gasket is properly installed under the maintenance port cover, warning that harmful exhaust gas may leak if it is not installed or not installed properly.

How they fail

Heat cycling is the main enemy. A gasket that is compressed when the boiler is cold expands when it is hot, and over hundreds of cycles it hardens, takes a set and loses its resilience. Once that happens, the joint can weep even if the fasteners are tight, and the leak grows as the material continues to degrade. Over-torqued fasteners crush gaskets; under-torqued fasteners let them shift; and either mistake can damage a new gasket during installation.

The failures show up differently on each side of the boiler. A water-side gasket leaks where you can usually see it — staining or drips at a fitting, or pressure that slowly falls. A combustion-side gasket leaks where you often cannot see it: a rollout switch trip, an exhaust smell, soot staining around a joint, or a CO alarm. IBC's DC manual ties a heat exchanger front panel that has come loose to a flue-temperature warning and directs the technician to check bolt torque, which is the same message from a different angle.

Reused gaskets are a failure mode of their own. A gasket that has already taken a set will not reseal reliably when it is put back, which is why both NTI and Viessmann instruct technicians to install new gaskets after opening a joint rather than reusing what came out.

Safe things to check

Water leaks are the visible ones: look for drips or staining at boiler fittings, sensor connections and the maintenance port, and note whether the boiler loses pressure over weeks. On the combustion side, trust your nose and your alarms — an exhaust smell near the boiler, soot or discolouration at a joint, or a CO alarm is a prompt call, and the alarm response is to leave the building and call 911 from outside.

Never try to stop a leak by tightening a fitting hard, wrapping tape around a joint or applying sealant to a combustion gasket. Those shortcuts can damage the sealing surface and make the leak worse, and on the combustion side they can mask a serious problem. Keep the area around the boiler clear so joints can be inspected, and report what you saw.

What a licensed technician will check

A technician replaces gaskets and seals as a matter of procedure whenever a joint is opened. The manuals set the standard: NTI says to install a burner gasket in perfect condition and to replace, not reuse, any gasket or insulation disc that shows damage; Viessmann installs new plate heat exchanger gaskets and tightens to a specified torque; and Navien's maintenance steps check that gaskets under covers and orifices are properly seated before reassembly.

Torque and seating matter as much as the parts. The technician follows the manual's torque values for the joint being closed, confirms the gasket is positioned correctly — NTI's vent adapters, for example, have different gaskets for different pipe materials and depths — and then verifies the repair. On combustion joints that means a combustion analyser check and a leak test; on water joints it means pressure and leak checks through a heating cycle.

The annual service visit is when most gasket and seal problems are caught, because the technician has the covers open and the checklist in hand. If you see water at a fitting, smell exhaust near the boiler, or get a CO alarm, call ROMA Heating & Cooling — and for a gas smell or a CO alarm, leave the building first.

Frequently asked questions

Why can't a gasket just be reused after a repair?

A gasket that has been compressed and heat-cycled takes a set and loses its resilience, so it will not seal reliably again. NTI's TFT manual is explicit: replace any gaskets or insulation discs that show damage and do not re-use them.

How would I know if a combustion gasket is leaking?

You might not see it. Warning signs include an exhaust smell near the boiler, soot or discolouration at a joint, a rollout-switch lockout, or a carbon-monoxide alarm. If an alarm sounds, leave the building and call 911 from outside, and have the appliance checked before re-entry.

Are gaskets checked during annual servicing?

Yes, on the components the service covers. NTI's annual checklist inspects the flue sensor grommet seal and test port plug, checks the burner plate for leaks, and replaces gaskets when the burner is removed — which is why annual servicing catches seal problems before they grow.

Book a consultation

A technician reviews your building and options. Requests are confirmed by ROMA.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate