Spill switch / blocked-vent switch

A spill switch, also called a blocked-vent switch, shuts down an atmospheric boiler when flue gases spill from the draft hood instead of rising up the chimney. This page explains the device, its carbon-monoxide warning, and what a licensed technician checks.

Safety first

A spill switch exists because flue gas spilling into the room is a carbon-monoxide hazard. If a CO alarm sounds, leave the building with everyone inside and call 911 from outside. If you smell gas, leave and call FortisBC at 1-800-663-9911 or 911 from outside.

Never reset a blocked-vent switch repeatedly or disconnect it to keep heat on. The switch has tripped because flue gases are not leaving the appliance properly, and running the boiler without correcting the cause can put carbon monoxide into the home.

In British Columbia, inspecting and correcting the venting that feeds a spill switch is licensed gas work under Technical Safety BC, and the work includes checking combustion air and the chimney or flue.

What it does in a gas boiler

A spill switch is a heat-sensing safety device mounted at the draft hood or draft diverter of an atmospheric, non-condensing boiler. A draft hood is designed to let room air mix with flue gases and to spill safely if draft reverses; the switch watches that opening. If hot flue gas spills there instead of travelling up the vent, the switch opens the safety circuit and stops the burner.

Weil-McLain's CGa manual shows the spill switch and its wire harness as part of the boiler's factory equipment, and its warnings are explicit that the draft hood and vent damper must not be altered or obstructed, because flue gas spillage and carbon monoxide emissions will occur. Crown's Bermuda manual explains the function in its sequence of operation: the blocked vent switch interrupts burner operation when flue gas spills from the draft diverter opening, and it is equipped with a reset button.

Dunkirk's manuals describe the same device for its atmospheric lines. The WPSB manual's service hints list a blown blocked-vent switch and direct the technician to check the venting system and chimney for blockage or a downdraft condition before resetting it, its wiring diagnostics place the spill switch in the ignition circuit, and its installation procedure tests for spillage at the draft hood after five minutes of main-burner operation.

How it fails

Most spill switch trips are venting failures. A blocked or deteriorated chimney liner, a bird nest or debris in the flue, a collapsed section of vent pipe, a disconnected joint, or a chimney that is simply too cold and short to establish draft will all cause spillage. Crown's manual states that an open blocked-vent switch is indicative of a problem with the vent system or the combustion air supply.

House pressure matters too. A tight modern home with powerful kitchen and bathroom exhaust fans can depressurize the mechanical room and pull flue gases down the chimney. Competing appliances on a shared flue, or a blocked combustion-air opening, produce the same effect.

The switch itself can also fail, and its reset mechanism can stick. But a technician does not treat a tripped spill switch as a switch problem until the draft and venting have been tested, because a replacement switch on a blocked chimney will trip again or, worse, hold the boiler on while flue gas spills.

Safe things to check

Note the alert or symptom, whether the boiler has tripped more than once, and whether it happens on cold, still days when chimneys draft poorly. Check from outside, at a safe distance, whether the chimney or vent terminal is blocked by snow, nests or debris, and keep the area around the boiler and its combustion-air openings clear.

Do not press the reset button to force the boiler back on, do not remove the switch, and do not block or tape over a draft hood opening. If a CO alarm sounds, leave the building and call 911 from outside.

FortisBC's appliance guidance is a useful baseline: keep the appliance area clear, keep vents unobstructed, and have the appliance maintained by a licensed contractor, because spillage problems are found by inspection rather than by resetting.

What a licensed technician will check

A technician tests the draft rather than the switch. They inspect the chimney or vent from the boiler to the termination, check for blockage, damage, corrosion and proper slope, verify the combustion-air supply, and measure whether the appliance is drafting correctly under operating conditions. Crown's guidance is that the cause of the venting problem must be found and corrected by a qualified gas service technician before the blocked vent switch is reset.

The technician also checks the boiler's combustion with an analyser and looks for the conditions that create spillage: a cold flue, a competing exhaust fan, a blocked air inlet or an undersized vent. Where the switch itself has failed, it is replaced after the venting is proven sound.

A spill switch that trips repeatedly is a sign the venting system needs more than a reset. Call ROMA Heating & Cooling to have the flue and combustion air inspected before another heating season.

Frequently asked questions

Can I just press the reset button on the spill switch?

Only a technician should reset it, and only after the venting has been checked. The switch tripped because flue gas spilled, and resetting without correcting the cause can let carbon monoxide into the home.

Why does my spill switch trip only on windy days?

Wind can overwhelm a marginal chimney or cause downdraft, especially with a short flue or nearby obstructions. That pattern points to a venting or termination problem that a technician diagnoses on site.

Do condensing boilers have spill switches?

No. Spill switches belong to atmospheric boilers with draft hoods. Sealed condensing boilers prove combustion air and venting electronically through pressure switches and fan monitoring instead.