Component

Water pressure sensor

The water pressure sensor is the electronic gauge that tells a modern boiler's control how much pressure the heating loop is under. It replaces the mechanical low-water cutoff on many models and drives features like automatic filling, and when it fails the boiler can shut down its space heating entirely. This page explains what the sensor does, how it fails, and what a licensed technician checks.

What it does in a hydronic system

A sealed hydronic system has to hold pressure, and the boiler needs to know what that pressure is at all times. The water pressure sensor measures the pressure inside the boiler's water circuit and reports it to the control. Navien's NCB-H service manual describes the part's function as measuring and providing feedback to the PCB for internal boiler water pressure, and lists the errors it can raise: E351 when the auto feeder valve cannot maintain pressure, E352 for high water pressure, and E353 for an abnormal sensor.

The sensor is also what makes automatic filling possible. On Navien's NCB-H, the auto feeder valve works with the pressure sensor: if the sensor sees a low water level — the manual describes the threshold as a heating system pressure lower than 7.3 psi (0.5 bar) — the system stops the boiler and refills automatically, and if the feeder stays open for more than five minutes it raises E351 and shuts down.

IBC's controls use an inlet pressure sensor in the same way. The SL G3 troubleshooting guide lists an Error - Inlet Pres. Sensor for a sensor that appears shorted or disconnected, and an Error - Low Water Pressure when inlet pressure falls below 4 psi. The DC Series manual goes further: E6 means no pressure sensor is detected — the control sees less than 0.25 volts on the sensor's orange sense wire — and E7 means the sensor is out of range above 4.25 bar (47 psi), and in both cases space heating is disabled.

How it fails

Pressure sensors fail electrically and mechanically. The sensing element can drift, short or go open; the connector can corrode or get wet; and the wiring can be damaged. IBC's SL G3 guide pairs a wiring check with sensor replacement for an inlet pressure sensor error, and Navien's diagnostic for the pressure sensor is a visual check of the sensor wires followed by a voltage check — the signal is a DC voltage that varies with pressure.

A wet connector is a specific hazard on these sensors. Navien's high-water-pressure troubleshooting instructs the technician to check whether the cold water pipe input pressure sensor is wet for any reason, because moisture in the connector can corrupt the reading. Debris and scale in the sensing port can also block the sensor from seeing the true pressure.

The symptoms depend on which way the sensor fails. A sensor reading low can make the boiler stop space heating or trigger automatic filling that never satisfies; a sensor reading high can raise a high-pressure error even when the system gauge looks normal; and an open or shorted sensor produces its own code. Because the control trusts the sensor, the boiler's behaviour follows the false reading — which is why the technician compares the sensor against a real gauge before replacing it.

Safe things to check

The boiler's pressure gauge is your reference. Note where the needle sits when the system is cold and whether it changes much when the boiler heats up; a gauge that agrees with normal operation while the boiler reports a pressure error is useful information. Also look for water under the boiler or at the fill connection, which can explain a real pressure loss.

Do not adjust the fill valve or add water to chase a pressure error, and do not unplug the sensor. If the boiler has disabled space heating and shows a pressure code, note the exact code and call. If you smell gas, leave and call FortisBC at 1-800-663-9911 or 911 from outside — but a pressure error itself is not a gas event.

What a licensed technician will check

A technician separates a real pressure problem from a sensor problem. They read the boiler's mechanical gauge and compare it with the control's reported pressure, then check the sensor's wiring and connector for moisture or damage. Navien's procedure includes a voltage check at the sensor, and IBC's guidance is to check the wiring to the sensor and replace the sensor if the fault persists.

If the pressure itself is wrong, the cause is elsewhere: a leak, a failed expansion tank or a fill valve that will not hold. IBC's low-water-pressure entry directs the technician to check the system for leaks, water pressure and the expansion tank before condemning the sensor. Where the sensor has failed, it is replaced and the auto-fill behaviour — if the boiler has it — is verified through a fill cycle.

Pressure sensor faults are usually quick to confirm and inexpensive to repair, but they can leave a house without heat while the boiler protects itself. If your boiler shows a pressure error or has stopped heating, call ROMA Heating & Cooling.

Frequently asked questions

Why has my boiler stopped heating and shown a pressure error?

Modern controls disable space heating when the pressure sensor reports a condition outside range — IBC's DC manual says E6 and E7 disable space heating, and Navien's control stops the boiler when pressure is below its low threshold. A technician confirms whether the pressure or the sensor is at fault.

The boiler says low pressure but my gauge looks normal. What now?

That mismatch is exactly what a technician checks for: a sensor reading that disagrees with the mechanical gauge points at the sensor, its wiring or a wet connector, while a gauge that agrees points at a real system problem such as a leak or failed expansion tank.

Can I just add water to clear a pressure error?

Adding water may restore pressure temporarily, but if the boiler keeps reporting errors or losing pressure, the cause — a leak, a failed expansion tank or a sensor fault — has not been fixed. Repeated filling also adds fresh oxygenated water to the loop, so the underlying cause should be found.