Problem
High boiler pressure
Why a sealed gas boiler's pressure can climb too high when hot, the role of the expansion tank and fill valve, and why a dripping relief valve means the system needs measurement, not a wedge.
What is happening
As a boiler heats the water in a sealed loop, the water expands and the pressure climbs. That expansion is supposed to be absorbed by the expansion tank, a small vessel with an air cushion that compresses as the water grows. When the tank is doing its job, the rise from cold to running pressure stays within the system's design range; when it is not, the pressure can climb toward the setting of the pressure-relief valve.
A high reading on the gauge, a relief valve that drips or blows water, or both together are the usual signs. The number to compare is the cold pressure against the running pressure: the difference between them, more than either reading alone, tells a technician whether expansion is being absorbed or not.
Safe things to check at home
Read the gauge cold, then again after the boiler has run for a while, and write down both numbers; the pair is the useful measurement. Check whether the pressure-relief valve's discharge tube has been dripping or has clearly discharged water recently.
Look for any alert on the boiler's display and note the text or code, then look it up on this site's brand error-code pages. Do not open the relief valve to let water out, do not wedge it, and do not adjust the fill valve or anything on the gas side. If water is actively discharging, place a container under the tube and keep the area dry and clear until a technician arrives.
Common causes
The most common cause is an expansion tank that has failed: the air cushion has leaked away or the diaphragm has ruptured, leaving the tank full of water with nothing to compress, so the system pressure tracks the water's expansion almost directly. Expansion tanks also need to be sized to the system, and a tank that was always too small behaves the same way.
On the fill side, an automatic fill valve that is stuck open can slowly add water until the system is simply overfilled, and a fill valve set to feed at too high a pressure does the same. Less often, a boiler that runs away on temperature, or a fault that keeps the burner on with no heat being delivered, expands the water past what any tank can hold. The relief valve itself can also fail and drip without an overpressure cause, which is why the diagnosis measures the system before blaming the valve.
When to call
Call when the running pressure approaches or passes the relief valve's rating, when the relief valve is dripping or discharging, or when pressure keeps climbing higher each season. A relief valve that has discharged once will often keep passing afterwards, and every discharge wastes water and can mask a real overpressure problem.
If the pressure climbs only when hot and settles when cold, the expansion tank is the first suspect, and that is a technician's repair. Call ROMA Heating & Cooling at 778-909-5731 during business hours with both gauge readings and whether the relief valve has discharged.
What a licensed technician will do
A technician compares the cold and running pressures, verifies the expansion tank's air charge with a gauge, and checks whether the tank is the right size for the system's water volume, which the manual or the system design determines. The fill valve's feed pressure is measured and compared with the boiler's specification, since a fill valve set too high keeps the whole loop overfilled.
The fix is usually re-charging or replacing the expansion tank, resetting or replacing the fill valve, or replacing a relief valve that has passed and will not reseat. The system is then run through a full cycle to confirm the pressure stays inside the design range, and the technician checks that nothing on the gas side needed attention along the way, under the same permit rules that govern all gas work in BC.
Frequently asked questions
What pressure is too high for a boiler?
It depends on the system, but the relief valve's rating is the ceiling the design expects never to reach. If running pressure approaches that rating, the expansion or fill side needs attention.
Why does my relief valve drip only when the boiler is hot?
That pattern usually means expansion is not being absorbed, classically a failed expansion tank. The water expands, pressure climbs, and the relief valve does its job by discharging.
Is it safe to open the relief valve to lower the pressure?
No. Letting water out treats the symptom once and can leave the valve leaking afterwards. The cause is a failed tank or overfilling, and both need a technician.
Talk to a boiler technician
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Related
Sources and verification
- Installation and Service Instructions — Viessmann Vitodens 100-W B1HE/B1KE · 6167 818 - 22 · accessed September 7, 2026
- FortisBC — appliance maintenance and safety · accessed September 7, 2026
Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.