Problem
Boiler ignition failure
A gas boiler that tries to light and fails: what happens during an ignition sequence, the gas, spark and flame-sensing faults behind repeated failures, and why ROMA treats gas smell as the first priority.
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call ROMA about the boiler. Official guidance: FortisBC gas leaks and odour.
Safety first
If you smell gas, leave the building and call FortisBC at 1-800-663-9911 or 911 from outside before anything else. A boiler that is failing to light is not itself a gas emergency, but repeated failed ignition attempts are a reason to stop the sequence and get a diagnosis rather than to keep trying.
Modern boilers are designed to fail safe: after a limited number of ignition trials the control locks out and waits, and it does not open the gas valve without proof that the burner has lit. When the boiler is in that lockout, the safest action is to note the alert, leave the boiler to its lockout, and call a technician.
What is happening
When a boiler receives a call for heat it runs a sequence: the fan purges the combustion chamber, the igniter sparks, the gas valve opens briefly, and the control checks for a flame signal. If the flame is not confirmed within the safety window, the gas valve closes, the boiler tries again, and after the manufacturer's set number of trials it locks out and shows an alert.
Ignition failure is the visible end of that sequence, and it can feel identical from the living room whether the cause is no spark, no gas, or a flame that lights and is not sensed. The boiler's display usually records the outcome, with plain-language alerts on some controls, such as the V-10 touchscreen on IBC boilers, and numbered codes on others, such as the E-codes on Navien appliances. Look the exact alert up on this site's brand error-code pages; a code is not a diagnosis, but it records which step failed.
Safe things to check at home
Write down the exact alert text or code and whether the boiler has locked out more than once. Confirm other gas appliances in the home are working, which can suggest a supply problem at the meter, and check that the boiler's service switch and breaker are on, since a power fault can masquerade as an ignition failure.
Check the outdoor vent terminal from a safe distance to confirm it is not blocked by debris or, in winter, by ice and snow, and confirm there is no gas smell anywhere in the building. If your boiler's manual documents a user reset, you may reset once and watch a single sequence; if the boiler does not stay running, stop resetting and call. Never open the casing, move the igniter or adjust anything in the combustion chamber.
Common causes
Ignition failures trace back to the conditions the boiler needs to light. On the gas side: a shut-off valve left closed after servicing, air in a newly installed line, or supply pressure below what the appliance requires. On the ignition side: a spark electrode that is fouled, worn or out of position, or wiring that has deteriorated. On the sensing side: a flame ionization probe that cannot confirm the flame, often because of contamination, a poor ground or an electrical fault.
Beyond the boiler itself, a blocked condensate drain, a restricted combustion-air path or a flue problem can upset the conditions the control expects, and some fault tables list these among the checks for flame faults. A weak spark, no flame, or a flame that is present but not sensed all end in the same lockout, which is why the first visit is about measurement, not parts.
Ignition failure versus flame loss
Two different faults share the same visible result, and telling them apart is the first thing an alert does for a technician. In an ignition failure the burner never establishes a flame at all: the sequence reaches its trial for ignition and the control proves no flame within the allowed window. In a flame loss the burner does light, but the flame signal disappears while the boiler is running, so the control closes the gas valve and tries again. Documented examples of the distinction are already on this site's code index: a Navien NCB-H manual describes E003 as an ignition failure shown after ten attempts with no flame detected, while E012 is described as flame loss during combustion, displayed after twenty consecutive losses.
The difference is not academic. An ignition fault points toward the ignition and gas-delivery side of the appliance, while a flame-loss fault points toward flame sensing and grounding, gas pressure that is stable enough to light but not to stay, or a flame that becomes unstable once it is established. If the display shows a code, match it to the brand, series and controller before interpreting it, because this site's error-code index records each documented meaning against the exact manual that states it.
The sequence the boiler runs before it lights
The alerts make more sense against the sequence they come from. When a call for heat arrives, the control starts the inducer or blower and confirms that air is moving, then allows the gas valve to open for a short trial period while the igniter sparks. If the flame-sensing circuit confirms a flame inside that window, the valve stays open and the boiler modulates to match demand. If it does not, the valve closes, the control purges the combustion chamber and tries again, and after its set number of trials it locks out.
Each step is a permission the control must receive before the next one is allowed, which is why a blocked vent, a pressure switch that has not made, a fouled igniter or a flame-sensing fault can all end in the same lockout message. Read that way, the alert is not vague: the control is reporting that a permission in the sequence was missing. The manufacturer's manual documents the sequence and the checks for each step, and a technician measures those permissions in order instead of guessing at parts.
Why a boiler can light and then go out
A flame that lights and then disappears has its own family of causes. Flame is often proved by ionization: a flame rod sits in the burner flame and the control reads a small current through it to confirm that the flame is real. That signal is easily upset. A rod coated with contamination, a poor electrical ground, moisture around the burner or a wiring fault can all make a steady flame look absent to the control, so the boiler shuts the gas valve for safety even though a flame was present. This is why a technician tests the sensing circuit and its grounding before replacing a gas valve.
On the gas side, a supply that is present but unstable can light a burner and then starve it: a partly closed valve, air working through a recently installed or serviced line, or supply pressure that drops when other appliances run. On the air and flue side, a restriction that changes once the boiler warms, a condensate trap that drains slowly, or a vent that is partly blocked can disturb combustion after a successful light. Any of these can produce a light-and-go-out pattern that the display reports much like an ignition failure.
Intermittent ignition faults that will not reproduce on demand
The hardest ignition faults to diagnose are the ones that clear before anyone arrives. A boiler that fails to light three mornings out of seven, or only when the wind is from one direction, is still reporting a real condition; it is reporting it intermittently. The pattern itself is the evidence. Note whether the failure happens on the first firing of the day, only after the boiler has been running, only on cold mornings, or only when other gas appliances are in use, because each of those points at a different part of the ignition chain.
Several causes behave exactly this way. A flame rod with light contamination can sense a healthy flame on some firings and miss it on others, especially as moisture and temperature change. A gas supply that is marginally low can light a burner at part load but starve it when the boiler ramps up or when another appliance draws. A vent terminal that is partly obstructed can work in calm air and fail when wind pressurizes it. None of these shows up in a single test on a mild afternoon, which is why the log a homeowner keeps between visits matters as much as the readings a technician takes on site.
Modern controls help here because they store a fault history. A failed ignition attempt that the homeowner never saw is often recorded in the control, with the time and the number of trials, and reading that history is where ROMA's diagnostics visits begin. A pattern in the log, such as repeated failures on cold starts but none during the day, can point at the likely cause before a single part is replaced.
What a normal ignition sequence sounds and looks like
A homeowner who can describe the start-up sequence gives a technician a head start, because an ignition fault is diagnosed by finding the step that does not happen. On a typical condensing boiler, a call for heat starts the inducer or blower, which runs through a pre-purge period and is usually the first thing you hear, a low hum or whirr. The control then proves that air is moving, the igniter sparks, and the gas valve opens for a short trial. A healthy light is quick and quiet: a soft whoosh or a low rumble as the flame establishes, after which the blower settles into its running speed and the boiler modulates to match demand.
What is missing is as informative as what is present. A boiler that hums but never clicks or whooshes may be stopping before it ever tries to light, often on an air-proving or vent condition. A boiler that clicks repeatedly without a whoosh is sparking without gas, or without a flame the control can sense. A boiler that whooshes and then goes quiet has lit and lost its flame. A single hard bang at light-up is a different event again, a delayed ignition, and it is treated as a safety matter rather than a nuisance. Describing which of those you heard, and whether the display showed an alert at that moment, is the most useful thing to have ready when you call.
After a service, gas work or a long idle
An ignition fault that appears soon after gas work or a service is worth describing to the technician as exactly that, because the sequence of events narrows the search before anyone opens a panel. Work such as a line replacement, a meter change or a new appliance connection can leave air in the piping that has to be purged before a burner lights reliably, and a shut-off valve that was left closed or opened only part way has the same effect. When the boiler reaches its trial for ignition and finds air or low pressure instead of gas, it does what it is designed to do: closes the valve, tries again, and locks out. This is not a homeowner repair. The gas side is purged and its pressures verified with instruments by a licensed gas fitter, which is the standard of practice in British Columbia.
A long idle has its own version of the same result. A boiler that has sat unused through a mild Greater Vancouver summer can return to service in the fall with a vent terminal that has collected debris, a condensate trap that has dried out or gathered material, or a combustion-air path that is no longer clear. Manufacturer manuals document the vent terminal clearances, the condensate trap and drain requirements, and the commissioning checks an installer performs, and those same items are where an idle-related ignition fault is usually found. A boiler that refuses to light on the first cold morning after a quiet season is often reporting one of them rather than a failed component.
Ignition failure on a combination boiler
A combination boiler runs its ignition sequence for two different reasons: a call for space heating, and a call for domestic hot water when a tap opens. That means an ignition fault on a combi can first appear at the sink rather than at the thermostat. In the middle of summer, with the heating off, a combi that will not light shows up as cold water from the tap, because the same burner and the same flame-proving circuit that heat the radiators also heat the domestic supply.
The visible symptom can therefore be misleading. A homeowner may describe a hot-water problem when the appliance is failing at ignition, and the display code is what separates the two. The sequence is the same regardless of what started it: the fan proves air, the igniter sparks, the gas valve opens briefly and the control looks for a flame. The difference between a combi and a heating-only boiler is only in what asked it to fire, so the appliance-side checks, the gas supply, the igniter and flame rod, and the venting and condensate paths, follow the same order on both designs.
Winter venting and condensate
Cold weather adds two conditions a condensing boiler has to survive. A sidewall vent terminal can be covered by snow, ice or drifting debris, and a blocked terminal changes the air the burner sees; the appliance's manual lists the clearances the installer must maintain, and clearing the terminal from a safe distance is one of the few ignition-related checks a homeowner can make. The condensate drain is the other: condensate that freezes in an exposed run or trap can back up and hold the boiler off, and the manual documents the trap and drain requirements for the model. Neither is a gas-side repair, but both show up as a boiler that will not stay lit in the coldest weeks of a Greater Vancouver winter.
Is it the gas supply or the boiler? A first look
When a boiler will not light, the first useful question is whether the fault is inside the appliance or upstream in the gas supply. The two look identical at the boiler, because the control only knows that no flame appeared. What separates them is evidence from elsewhere in the home. If other natural-gas appliances, such as a range, a fireplace or a second boiler, are also out, the interruption is likely at the meter, the utility supply or a shut-off valve rather than in this appliance. If every other gas appliance is working normally and only the boiler has failed, the fault is more likely within the boiler or its dedicated supply line.
A few details sharpen the picture. A boiler whose fan runs through its pre-purge but never reaches a flame, or that lights on some days and not others, points at the appliance's ignition, sensing or venting side. A boiler that failed at the same time as a utility interruption, a meter change or work on the gas line points upstream, and gas work can leave air in the piping that has to be purged before a burner lights reliably. A shut-off valve at the appliance that was closed for service and not fully reopened has the same effect, and its position is one of the few gas-side things a homeowner can look at without touching, because it can be seen without being operated.
What a homeowner must not do is test the gas side. Do not open or close gas valves to experiment, do not try to light the burner by hand, and never use a flame to look for a leak. If every gas appliance in the building is out, contact FortisBC as the gas utility about a supply interruption; if you smell gas at any point, leave the building and call FortisBC's emergency line at 1-800-663-9911 or 911 from outside. Purging a line and verifying supply pressures are licensed gas fitter work, done with instruments under Technical Safety BC's permit system.
The distinction matters because it changes who does what and how quickly. A boiler-side ignition fault is a service or repair visit to the appliance; a supply-side interruption is a utility or gas-fitment matter that no amount of resetting will fix. The evidence lines up in a few familiar patterns. Other gas appliances that are also out of service, a fault that began with a utility interruption or gas-line work, and a whole building or several appliances affected all point upstream. A boiler that is the only appliance affected, that may light on some days and not others, and that shows an ignition, flame-sensing, venting or condensate alert on its display points at the appliance itself. None of that decides the question on its own, because the answer is made by measurement on site rather than by a symptom list.
Ignition failure and combustion safety: what is not connected
It is worth separating two things homeowners often run together. A boiler that fails to light is not burning, so a failed ignition attempt does not itself produce carbon monoxide; the control closes the gas valve when it cannot prove a flame, and the appliance is designed to fail safe. A boiler locked out for ignition is therefore a heat-and-hot-water problem and a repair, not a carbon-monoxide event in the making.
The safety concern sits on the other side of the line, in how the burner behaves when it does light. Combustion problems, such as a delayed light that arrives with a bang, a yellow or lifting flame, soot or scorch marks, or a flame that rolls out of the burner area, are the conditions that can put carbon monoxide into a home, and FortisBC lists delayed ignition, a yellow or wavering flame, soot and flame roll-out among the warning signs that mean a service call rather than a wait. A boiler that lights cleanly and then locks out on flame loss is reporting a sensing or supply condition, not a combustion hazard, though it still needs diagnosis.
The practical rules follow from that split. Treat a failed light as a repair to arrange, and treat a carbon-monoxide alarm, a gas smell, or a burner that bangs, burns yellow or leaves soot as a safety event that comes first: leave the building and call 911 or FortisBC from outside. Do not keep resetting a boiler that bangs or smells at light-up, because each attempt can leave unburned gas in the combustion chamber. Technical Safety BC and FortisBC both direct combustion work to a licensed technician, and FortisBC recommends a carbon-monoxide alarm wherever gas appliances burn, which is a homeowner task that takes minutes.
For the service call, the distinction is still useful. A technician diagnosing a failed light verifies the ignition and sensing circuits and the gas supply; a technician diagnosing a combustion concern measures the flue gases with an analyser and checks the burners, the heat exchanger and the venting against the manual. Saying which of the two you actually saw, a boiler that never lit, or one that lit badly, tells the technician what to bring and how urgently to treat the visit.
What to note when the boiler will not light
Four notes turn a vague ignition complaint into a diagnosis. First, the exact alert text or code, written down as shown rather than paraphrased. Second, how many times the boiler tried before it locked out and whether it has lit at all in between. Third, whether the appliance is completely off or powered and failing to prove flame, because those two stories send a technician to different places. Fourth, whether other gas appliances in the home are working, which narrows the gas-supply picture without proving it.
Add the weather and whether the vent terminal was recently covered by snow, plus any service, repair or power interruption in the days before the fault appeared. With those notes a technician can judge whether the visit is likely an ignition-component repair, a flame-sensing or grounding issue, a venting or condensate restriction, or a gas-supply question, and can arrive with the right tools. Without them, the first part of the visit is spent rediscovering what the display already recorded.
When to call
Call when the boiler is locked out for ignition, when it lights only after many attempts, or when the fault recurs after a single allowed reset. An ignition fault will not cure itself by repetition, and each extra attempt past the lockout just adds wear and delays the diagnosis.
If the boiler is off and the home is cold, that is exactly what ROMA's emergency service line exists for. Call ROMA Heating & Cooling at 778-909-5731 during business hours with the alert text, the brand and model, and whether other gas appliances work, and you will be told honestly what happens next.
What a licensed technician will do
A technician confirms the supply: static and flow gas pressures are measured, shut-off valves are verified, and the venting and condensate paths are checked against the fault table in the manufacturer's manual. Ignition components are then tested in sequence, including the spark at the electrode, the electrode gap and insulation, and the wiring and grounding of the flame-sensing circuit.
The repair matches the measured fault: reseating or replacing an electrode, correcting a grounding problem, clearing a condensate or venting restriction, or replacing a failed gas valve or control, always within the manual's procedure. Combustion is verified with an analyser after the boiler is back in service, and any gas-side work is performed by licensed contractors under Technical Safety BC's permit system.
A symptom-to-step map for a boiler that will not light
The ignition sequence is a chain of permissions, and the fastest way to narrow an ignition fault is to match what the boiler actually does to the step in that chain where it stops. The observations below are the ones a homeowner can make without opening anything, and each points at a different part of the sequence.
A boiler that is completely dark, with no display, no fan and no sound, stopped before the sequence ever began. That is an electrical or power question, the service switch, the breaker, a fuse or the control's own supply, and it is not an ignition fault at all. A boiler whose display is lit but that sits idle has power and a live control, but no call for heat is reaching it or a safety permission is holding it off, which points at the thermostat, the zone controls or a safety switch rather than the burner.
Once the fan starts, the sequence has begun. A boiler that runs its fan through a pre-purge and then stops without a click or a spark is usually failing an air-proving or vent condition, because the control will not allow the gas valve to open until it is satisfied that air is moving and the flue path is clear. A boiler that clicks repeatedly but never produces the soft whoosh of a flame is reaching its trial for ignition and failing to prove a flame, which can be the gas supply, the igniter's position or the flame-sensing circuit. A boiler that lights and then goes quiet within seconds has proved a flame and then lost it, which is a flame-loss pattern rather than a failure to light. A single hard bang at light-up is a delayed ignition, a combustion-safety concern that is treated differently from all of the others.
Read the observation alongside the alert on the display, if there is one. The observation says which step looked wrong from the living room; the code says which protection the control tripped. Together they tell a technician where to begin measuring, and they are also the two things that are hardest to reconstruct after the fact, so writing them down before the first call is worth more than any description given later. The map also separates the faults that are not ignition faults, which is what keeps a visit from beginning at the burner when the real problem is in the switch or the thermostat.
Repair or replace after repeated ignition faults
Most ignition faults are repairs, not replacements. An electrode, a flame rod, a gas valve, a control board, or a venting or condensate restriction can all be corrected, and the appliance then lights normally again. The question of replacement belongs to a different set of facts: the age of the boiler, the condition of its heat exchanger, whether parts for its exact model and controller are still available, and how often it has needed attention. Those are assessed on site, and a single lockout is not a verdict on the appliance.
The decision is also about pattern rather than one event. A boiler that failed to light once, after a service or a long idle, and then ran reliably is usually a repair of whatever caused that one failure. A boiler that locks out on ignition repeatedly through a heating season, especially alongside other faults or a history of pressure and water-quality problems, is where a conversation about replacement becomes reasonable. Age matters because components and controllers are supported for a period, and an appliance whose parts are no longer supplied can be harder to keep running than one still in production.
What does not decide the question is the price of the failed part on its own. The useful comparison is the cost of the repair against the remaining service life of the appliance and the cost of a replacement installed, which belongs in a written estimate rather than a guess on the phone. Boilers.ca and ROMA Heating & Cooling in Greater Vancouver provide both the repair and the replacement side, so the recommendation is not steered by which service is more profitable. Where a repair is the right answer, that is what is proposed; where the appliance is at the end of its life, the estimate process sets out the options.
A replacement is never only about the burner. A new condensing boiler may need different venting, a condensate route, a gas-supply check and a rebalanced system, and those belong in the installation scope rather than appearing as extras later. Any gas-side work is performed by licensed contractors under Technical Safety BC's permit system, and the estimate follows a site assessment rather than a phone description of the fault.
Frequently asked questions
My boiler tried to light several times and stopped. Is that dangerous?
The boiler's lockout is its safety system working: after its set number of trials it stops trying. Leave it locked out, note the alert, and call; do not defeat the lockout.
Should I reset the boiler after an ignition failure?
Reset once if your manual documents a user reset, then watch one sequence. If the boiler fails again, stop resetting and call. Repeated resets can hide the fault and lengthen lockouts.
Can low gas supply cause ignition failure?
Yes. Insufficient supply pressure, a partially closed valve or air in a new line can prevent the boiler from lighting. Other appliances working narrows the picture but does not rule supply out.
My boiler lights and then goes out within seconds. Is that ignition failure?
Not exactly. A burner that lights and then loses its flame is a flame-loss pattern rather than a failure to establish ignition, and it points at flame sensing, grounding, an unstable gas supply or a venting or condensate condition. Either way the gas valve closes for safety, so note the alert and call.
How many times will a boiler try to light before it locks out?
The number is set by the manufacturer and recorded in the appliance's manual; a Navien NCB-H, for example, is documented as attempting ignition ten times before displaying its ignition-failure code. Repeated resetting beyond that is not a fix and can add wear.
Can snow or ice on the vent stop the boiler from lighting?
Yes. A blocked sidewall vent terminal changes the air the burner sees and can hold a condensing boiler off. Clear the terminal only from a safe distance, never by reaching inside it, and check the condensate drain for freezing as well.
Could a dirty flame sensor really stop the boiler igniting?
A contaminated flame rod, a poor ground or a wiring fault can make a present flame look absent to the control, which then shuts the gas valve. It is confirmed by testing the sensing circuit, not by replacing parts on suspicion.
The boiler was just serviced or the gas was worked on and now it will not light. What could be wrong?
Work on the gas line can leave air in the piping that must be purged, and a shut-off valve can be left closed or only part way open. Both stop the burner from lighting even though nothing in the boiler failed. Do not touch the gas side; call the installer or a licensed gas fitter to verify the supply and purge the line.
Why will my boiler not light on the first cold day after summer?
A boiler that sat idle for months can come back with a blocked vent terminal, a dried or fouled condensate trap, or an air path that is no longer clear, any of which can hold it off at ignition. These are checks a technician makes at the annual service before the heating season, and they are the usual explanations for a first-cold-day failure.
My combi stopped making hot water in summer. Is that an ignition fault?
It can be. A combination boiler fires the same burner for hot water that it uses for heating, so an ignition fault with the heating off shows up as cold water at the tap. Read the display and note the exact code; a code is not a diagnosis, but it records which step of the sequence failed.
My boiler only fails to light some mornings. Can that be diagnosed?
Yes, but the pattern is the evidence. Note which mornings, whether it is the first firing of the day, and what the display shows. Intermittent causes such as a lightly contaminated flame rod, a marginal gas supply or a partly blocked vent often leave a stored fault history a technician can read.
What should a boiler sound like when it lights normally?
A blower hum during pre-purge, a brief spark, then a soft whoosh or low rumble as the flame catches, after which the boiler settles into its running speed. A missing step, repeated clicking with no whoosh, or a hard bang at light-up each point at a different part of the ignition sequence.
The boiler clicks but never lights. What does that mean?
Repeated clicking without a flame usually means the igniter is sparking but the burner is not establishing or not proving a flame, which can be a gas-supply, igniter-position, flame-sensing or venting condition. It is confirmed by measurement, not by replacing parts in turn.
How do I tell if my boiler's ignition failure is a gas supply problem?
Look at the rest of the home. If other natural-gas appliances are also out, the interruption is likely at the meter or supply; if only the boiler has failed, the fault is more likely inside the appliance or its line. Do not test or adjust gas valves yourself; if all gas appliances are out, contact FortisBC, and if you smell gas, leave and call from outside.
Does a boiler that won't light produce carbon monoxide?
A failed light is not a combustion event: the control closes the gas valve when it cannot prove a flame, so the appliance is not burning. Carbon-monoxide concerns belong to how the burner behaves when it does light, such as a delayed bang, a yellow flame, soot or flame roll-out, which are safety matters for a licensed technician.
My boiler lights with a bang. Is that an ignition failure?
Not exactly. A delayed ignition means the burner does light, but late, so a pocket of gas ignites with a bang. It is a combustion-safety concern rather than a failure to light, and it should be measured and corrected by a licensed technician rather than reset repeatedly.
Should I turn the gas valve off if my boiler won't light?
Do not operate gas valves to experiment or to test the boiler. If every gas appliance is out, contact FortisBC about the supply; if you smell gas, leave the building and call FortisBC's emergency line or 911 from outside. Purging and pressure checks are licensed gas fitter work.
Can an ignition fault be repaired, or does it mean a new boiler?
Most ignition faults are repairs. An electrode, flame rod, gas valve, control board or a venting or condensate restriction can usually be corrected, and the boiler lights normally again. Replacement depends on the appliance's age, heat-exchanger condition, parts availability and service history, which are assessed on site.
My boiler has failed to light twice this winter. Should I replace it?
Not on that evidence alone. Two failures in a season, especially after a service or a long idle, are usually a repairable condition. A pattern of repeated lockouts through the season alongside other faults is the point at which a replacement conversation becomes reasonable.
How do I get a written estimate for an ignition repair or a replacement?
Call ROMA Heating & Cooling at 778-909-5731 with the alert text, the brand and model, and whether other gas appliances work. The estimate follows a site assessment, and the repair and replacement options are set out in writing rather than quoted by guesswork on the phone.
Will a boiler that keeps locking out damage itself if I keep resetting it?
Repeated resets do not fix the cause and add wear to the ignition components, and some controls lengthen their lockout after each attempt. Reset once if the manual documents a user reset, then stop and call so the fault can be measured.
Talk to a boiler technician
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- FortisBC — gas leaks and odour · accessed September 7, 2026
- Installation & Operating Manual — IBC SL Series G3 · 120-276E13 · accessed September 7, 2026
- NCB-H Installation and Operation Manual — Navien · accessed September 7, 2026
- NTI FTVN Installation and Operation Manual · accessed September 15, 2026
- Installation and Service Instructions — Viessmann Vitodens 100-W B1HE/B1KE · 6167 818 - 22 · accessed September 15, 2026
- Technical Safety BC — information bulletin: annual servicing for gas appliances (B-G5 071019 3, Revision 1, May 19, 2010) · B-G5 071019 3, Revision 1 · accessed September 15, 2026
Facts checked September 15, 2026. Last updated September 15, 2026. Technical reviewer: not yet assigned.