Bosch Thermotechnology · Error codes
Bosch/Buderus GB312 8Y 590 — Pressure Switch in Safety Assembly Has Tripped.
8Y 590
Pressure switch in safety assembly has tripped. Break in pressure switch safety sequence during burner operation. Checks: Check whether low gas pressure switch (accessory) is breaking circuit during operation. Check if the air intake switch or flue gas pressure switch opens while the boiler is operating. Check whether SAFe or high gas pressure switch (accessory) is breaking circuit during operation. Section 10.3, page 87 ff Remedy: Measure the gas pressure at 100 % boiler modulation. Check low gas pressure switch (available separately) setting. Check flue/air supply pipe for blockages. Replacing the gas valve The table classifies it as V (interlocking).
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call ROMA about the boiler. Official guidance: FortisBC gas leaks and odour.
Applies to
This gas-train fault code is displayed by the Logamatic BC10 basic control unit and MC10 control unit (SAFe fault codes) on Logano plus GB312 models (90–280), as documented in Buderus Logano plus GB312 Installation and Service Instructions, doc 6 720 806 273 (01.2013), section 10.2.2 Table 23 Fault displays (6 720 806 273). Codes can differ between controller generations, so always check the manual that matches your unit.
- Bosch Thermotechnology Buderus GB312 (Logano plus GB312)
- Buderus GB312/90
- Buderus GB312/120
- Buderus GB312/160
- Buderus GB312/200
- Buderus GB312/240
- Buderus GB312/280
Controller: Logamatic BC10 basic control unit and MC10 control unit (SAFe fault codes). Source manual: 6 720 806 273 (2013-01).
Why a code is not a diagnosis
A gas-train code involves the gas valve or its electrical circuit. It does not mean there is a leak; the circuit, coils and wiring must be measured by a licensed technician.
Safe things to observe
- If you smell gas, stop, go outside and call your gas utility's emergency line or 911 before anything else.
- Note the exact code and what the appliance was doing when it appeared.
- Check whether other gas appliances in the building are working.
Do not
- Do not reset or run the appliance while the gas valve circuit is suspect.
- Do not touch the gas valve.
How professional service helps
- A technician verifies harness connections and coil resistances against the manual before replacing parts.
- Combustion and safety devices are verified with an analyser and the manufacturer's procedure after any repair.
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Parts and service
Parts commonly involved
These parts appear in the documented text for this alert. A code reports a condition, not a failed part — a technician confirms the cause by testing before anything is replaced.
Gas valve
The gas valve is the boiler's controlled gateway for gas: it opens only when the control has proven safe conditions, meters the fuel to the burner,…
What a technician checks →Gas pressure switch
A gas pressure switch proves that gas pressure at the boiler is within a safe range before the burner is allowed to fire, and it shuts the burner…
What a technician checks →Burner assembly
The burner assembly is where gas and air meet and burn inside a boiler, and its condition decides whether combustion is clean or makes carbon…
What a technician checks →Boiler venting (flue and air intake)
A condensing boiler vents cool, wet flue gases through dedicated plastic pipe that must meet ULC S636 in Canada and the boiler manufacturer's own…
What a technician checks →
Service for this alert
- Gas Boiler Repair
Licensed gas technicians from ROMA Heating & Cooling diagnose and repair residential and light-commercial gas boilers across…
Every boiler part explained — what it does, how it fails and what a technician checks.
Documented for Bosch Thermotechnology Buderus GB312 (Logano plus GB312).
Frequently asked questions
Does this code mean I have a gas leak?
Not by itself. If you smell gas, stop, leave the building and call your gas utility's emergency line or 911 from outside before anything else. Otherwise the code points to a fault a technician confirms on site.
Can I clear this code myself?
Clearing a code without fixing its cause usually just brings it back. Note the code, check the safe items on this page, then call a licensed technician. If your appliance manual describes a user reset for this exact code and it stays away, no call may be needed.
Boiler locked out? Call with the alert text ready.
The brand, model and this alert are passed along when you request service online, so the technician arrives prepared.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Buderus Logano plus GB312 Installation and Service Instructions, doc 6 720 806 273 (01.2013), section 10.2.2 Table 23 Fault displays · 6 720 806 273 · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.