Buderus G515/350

The Buderus G515/350 is a discontinued commercial cast-iron boiler block with 9 sections and a nominal output range of 1,010-1,194.2 MBH for oil, gas or combination burners.

DiscontinuedHistorically in Canada

Key figures

Max input
Max CSA output
1,194.2 MBH
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Buderus G515/350 in practice

Best suited to

    Applicability and support

    Model number
    G515/350
    Canadian availability
    historical
    Production status
    discontinued
    ROMA supplies
    Confirmed at consultation
    ROMA services
    Confirmed at consultation
    Warranty
    Not verified

    Where ROMA provides on-site service

    On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

    See all service areas

    Specifications

    Published specifications

    Values as published by Bosch Thermotechnology. Units are shown with every value; notes flag conflicting sources or missing figures.

    Buderus G515/350 specifications
    SpecificationValueNote
    Input
    Combustion output, lower value1,080.3 MBH
    Combustion output, upper value1,286.7 MBH
    Output
    Nominal output, lower value1,010 MBHThe technical table prints a nominal-output range per size; both ends are given.
    Nominal output, upper value1,194.2 MBH
    Physical and connections
    Number of boiler sections9
    Weight, net3,506 lbWeight with packaging approx. 6-8% higher.
    Boiler water content87.2 US gal330 l.
    Maximum permissible supply temperature248 °FSafety limit (high limit safety cut-out); 120 °C.
    Maximum permissible operating pressure87 psi6 bar.
    Operating limits and other
    FuelsHeating oil, liquid propane or natural gasOil/gas-fired boiler block; approved burners listed by Bosch.

    Questions about the Buderus G515/350?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate