Cleaver-Brooks · ClearFire-W

Cleaver-Brooks ClearFire-W CFW 2000

The Cleaver-Brooks ClearFire-W CFW 2000 is a compact vertically fired firetube hydronic boiler documented by the official Model CFW O&M manual (750-296), with 211 gal water capacity and a 10 in w.c. minimum gas pressure.

Status unknownCanadian status unknown

Key figures

Max input
Max CSA output
AFUE
Min input
Natural gasHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Cleaver-Brooks ClearFire-W CFW 2000 in practice

The CFW 2000 is the 2,000 size of the Model CFW ClearFire-W, a compact vertically fired firetube hydronic boiler with AluFer extended-surface tubes and a single-pass design. The official O&M manual (750-296) prints a 211 gal water capacity in Table 4-1 and a 10 in w.c. minimum gas pressure at the gas train connection in Table 2-3, with a 28 in w.c. maximum supply pressure.

The manual states a nominal fuel-to-water efficiency of up to 88% depending on operating conditions and a 125 psig MAWP to the ASME low-pressure Section IV hot water code, with operating pressure below 112 psig. The line runs the CB Falcon hydronic boiler control with touchscreen and Modbus capability. The captured O&M manual does not print per-model input/output ratings, and the CB-8290 Dimensions and Ratings PDF was not recoverable from the archived official site, so those figures are not recorded here.

Best suited to

  • Commercial hydronic plants served by an existing ClearFire-W boiler
  • Compact vertical firetube installations with AluFer tube construction
  • Buildings wanting a CB Falcon-controlled hydronic boiler

Applicability and support

Model number
CFW 2000
Canadian availability
unknown
Production status
unknown
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Cleaver-Brooks. Units are shown with every value; notes flag conflicting sources or missing figures.

Cleaver-Brooks ClearFire-W CFW 2000 specifications
SpecificationValueNote
Efficiency
Efficiency (manual)88 %The Model CFW O&M manual states a nominal fuel-to-water efficiency of up to 88% depending on operating conditions; no per-model rated efficiency is printed in the captured manual.
Physical and connections
Water content211 galWater capacity 211 gal printed in Table 4-1 of the Model CFW O&M manual (750-296).
MAWP125 psigThe Model CFW O&M manual states a 125 psig MAWP to the ASME low-pressure Section IV hot water code, with operating pressure below 112 psig.
Operating limits and other
Minimum gas pressure at gas train connection10 in w.c.Printed in Table 2-3 of the Model CFW O&M manual; maximum supply pressure 28 in w.c. across the line.
FuelNatural gasThe Model CFW O&M manual states the boiler is designed to fire natural gas.
ControlCB Falcon hydronic boiler control with touchscreenModel CFW O&M manual, section 4.4.

Frequently asked questions

What data is printed for the CFW 2000?

The official Model CFW O&M manual prints 211 gal water capacity (Table 4-1) and a 10 in w.c. minimum gas pressure (Table 2-3), with a 28 in w.c. maximum supply pressure.

Why are input and output not listed?

The captured official Model CFW O&M manual does not print per-model input/output ratings, and the CB-8290 Dimensions and Ratings PDF was not recoverable from the archived official site, so Boilers.ca does not publish unverified figures.

Is the ClearFire-W still catalogued?

Cleaver-Brooks' current condensing-hydronic catalogue lists the ClearFire-CE and SwitchFire; the Model CFW is documented from its official archived manual, so productStatus is recorded as unknown.

Questions about the Cleaver-Brooks ClearFire-W CFW 2000?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.