Crown Phantom-X PHNTM210
The Crown Phantom-X PHNTM210 fires 42 to 210 MBH input at 95.0% AFUE with 5:1 modulation: 194 MBH gross output and a 169 MBH net AHRI rating on the Sage2.x control with outdoor reset, at about 206 lb shipping weight.
Key figures
- Max input
- 210 MBH
- Max CSA output
- —
- AFUE
- 95 %
- Min input
- 42 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Crown Phantom-X PHNTM210 in practice
The PHNTM210 is the smaller Phantom-X: 42–210 MBH input for 194 MBH heating capacity (gross output) and a 169 MBH net AHRI water rating at 95.0% AFUE (product ratings table; I&O manual 105357-06, 12/24). It is a stainless steel water-tube condensing boiler with a modulating burner at 5:1 turndown, direct spark ignition, and the Sage2.x control with an included outdoor reset sensor — plus domestic water priority, warm-weather shutdown, freeze protection, pump exercise and multiple-boiler lead/lag for up to 8 units.
The unit measures 23-15/16" (A) by 32-3/16" (B), holds 1.7 gal of water, ships at about 206 lb, and connects on 1" NPT supply/return with 1/2" NPT gas. It offers multiple venting options (two-pipe and concentric per the manual, with derates at maximum vent length) and a stackable design for small mechanical rooms. Ratings reduce 4% per 1,000 ft above 2,000 ft; LP installations above 7,000 ft are not allowed, and the page notes Canadian installations above 4,500 ft should consult the authority having jurisdiction.
Best suited to
- Large homes and light-commercial plants whose load approaches 210 MBH input
- Projects wanting Sage2.x lead/lag cascades of up to 8 boilers
- Mechanical rooms where the stackable Phantom-X chassis saves floor space
Applicability and support
- Model number
- PHNTM210
- Canadian availability
- unknown
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Crown Boiler Co.. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input, minimum | 42 MBH | Minimum input per the product ratings table (42 MBH on the PHNTM210, 57 MBH on the PHNTM285). |
| Input, maximum | 210 MBH | Maximum input per the product ratings table; ratings apply to elevations up to 2,000 ft, reduced 4% per 1,000 ft above. |
| Output | ||
| Heating capacity (gross output) | 194 MBH | Heating capacity marked as gross output per the product ratings table. |
| Net AHRI water rating | 169 MBH | Net water rating based on a piping and pickup allowance of 1.15 per the product ratings table. |
| Efficiency | ||
| Efficiency (AFUE) | 95 % | 95.0% AFUE per the product ratings table. |
| Domestic hot water | ||
| Domestic hot water | Heating-only boiler — domestic hot water comes from a separate indirect tank or water heater | |
| Physical and connections | ||
| Water content | 1.7 gal | Water content per the product ratings table. |
| Shipping weight | 206 lb | Approximate shipping weight per the product ratings table. |
| Dimensions (A × B) | 23-15/16" × 32-3/16" | Dimension A 23-15/16" and dimension B 32-3/16" per the product dimensions table. |
| Supply and return connections | 1" NPT | Supply and return connection size per the product dimensions table. |
| Gas connection | 1/2" NPT | Gas connection size per the product dimensions table. |
| Operating limits and other | ||
| Turndown ratio | 5:1 | Modulating burner with 5:1 turndown ratio per the product page. |
| Control | Sage2.x control with outdoor reset sensor | Domestic water priority with priority protection, warm-weather shutdown, freeze protection, pump exercise, and multiple-boiler lead/lag for up to 8 boilers (product page). |
| Fuel | Natural gas or LPG | Ships as a natural gas boiler, field convertible to LP; no LP installations above 7,000 ft. |
Frequently asked questions
What are the PHNTM210's ratings?
42–210 MBH input, 194 MBH gross heating capacity, a 169 MBH net AHRI water rating and 95.0% AFUE per the product ratings table.
Is the PHNTM210 a combi boiler?
No — domestic water is listed as N/A on the product brief; it is heating-only, so DHW comes from a separate tank or water heater.
Can the PHNTM210 run on propane?
Yes, field-converted from natural gas — but it may not be installed using LP gas above 7,000 ft, per the product page.
Questions about the Crown Phantom-X PHNTM210?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Velocity Boiler Works — Phantom-X 210-285 product page · accessed September 8, 2026
- Phantom-X 210–285 Installation, Operating & Service Instructions, Doc 105357-06 (12/24) (PDF) · 105357-06 · accessed September 8, 2026
Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.