Skip to content
Boilers.caby ROMA Heating & Cooling

De Dietrich · MCA Pro Series

De Dietrich MCA Pro 115

The De Dietrich MCA Pro 115 is a condensing wall-hung boiler rated 82–399 MBH input and 79–368 MBH output at 94.0% CSA thermal efficiency, with 1-1/4" heating connections and a 150 lb dry weight.

CurrentSold in Canada

Key figures

Max input
399 MBH
Max CSA output
368 MBH
AFUE
Min input
82 MBH
Natural gasPropaneDHW: unknownresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

De Dietrich MCA Pro 115 in practice

The MCA Pro 115 is the 115 kW size of De Dietrich's North American condensing wall-hung line, documented in the MCA Pro submittal Rv 5.4 and specification data. It prints 82–399 MBH input, 79–368 MBH output, 94.0% CSA thermal efficiency (94.3% combustion), usable efficiency up to 98.2% and standby loss below 0.3%.

The boiler uses a cast-aluminum heat exchanger, fires natural gas or propane with modulating, on/off or remote 0–10 V control, and connects to the heating circuit through 1-1/4" male NPT supply and return pipes with a 3/4" male NPT gas connection. Venting is 4" single pipe / 100–150 mm concentric. The MCA Pro page notes cascade configurations of 2 to 8 boilers, and DDR Americas (Cambridge, Ontario) is the North American supplier.

Best suited to

  • Residential and light-commercial loads from 79 to 368 MBH output
  • Wall-hung installations that need a compact condensing boiler with a cast-aluminum heat exchanger
  • Cascade plants of 2 to 8 boilers (page copy)

Applicability and support

Model number
MCA Pro 115
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by De Dietrich. Units are shown with every value; notes flag conflicting sources or missing figures.

De Dietrich MCA Pro 115 specifications
SpecificationValueNote
Input
Minimum input (as printed)82 MBHPrinted in the MCA Pro submittal technical specifications; the source row is labelled 'Minimum Fuel Input'.
Maximum input (as printed)399 MBHPrinted in the MCA Pro submittal; the source repeats the label 'Minimum Fuel Input' for this row — by context (model kW rating and the min/max output pair) it is the maximum. Kept verbatim with this note.
Output
Minimum heat output79 MBHPrinted in the MCA Pro submittal.
Maximum heat output368 MBHPrinted in the MCA Pro submittal.
Efficiency
Thermal efficiency (CSA certified)94 %Printed in the MCA Pro submittal; combustion efficiency 94.3% CSA certified, usable efficiency up to 98.2%, standby loss < 0.3%.
Venting and air
Vent / combustion air4" single pipe / 100–150 mm concentricPrinted in the MCA Pro submittal dimensions notes; gas vent category IV-BH per ANSI Z21.13a / CSA 4.9.
Physical and connections
Heating supply / return1-1/4" male NPTPrinted in the MCA Pro submittal dimensions notes.
Gas connection3/4" male NPTPrinted in the MCA Pro submittal dimensions notes.
Weight (dry / wetted)150 lb dry / 167 lb wettedPrinted in the MCA Pro submittal.
Operating limits and other
FiringModulating, on/off, remote 0–10 VPrinted in the MCA Pro submittal; modulation range 20–100% per the international page.
Operating water temperature range68–190 °F (CPVC / PP / SS)Printed in the MCA Pro submittal; max safety limit 230 °F, water pressure 12–56 psig.
CSA certified installation altitudeMax 4,500 ft / 1,370 m (Canada)Printed in the MCA Pro submittal.
FuelNatural gas or propane (LPG)Printed in the MCA Pro submittal gas and venting data.

Frequently asked questions

What is the input range of the MCA Pro 115?

The MCA Pro submittal prints 82–399 MBH input and 79–368 MBH output for this size, at 94.0% CSA thermal efficiency.

What connections does the MCA Pro 115 use?

The submittal prints 1-1/4" male NPT heating supply and return connections, a 3/4" male NPT gas connection, and 4" single pipe / 100–150 mm concentric venting.

Can MCA Pro boilers be cascaded?

Yes — the product page states cascade configurations of 2 to 8 boilers are standard, with any configuration possible.

Questions about the De Dietrich MCA Pro 115?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate