Skip to content
Boilers.caby ROMA Heating & Cooling

Comparison

De Dietrich MCA Pro 45 vs MCA Pro 115

Verdict in brief

The MCA Pro 45 and MCA Pro 115 are the smallest and largest sizes of the condensing wall-hung line: 34–156 versus 82–399 MBH input and 33–146 versus 79–368 MBH output at the same 94.0% CSA thermal efficiency. Both use 1-1/4" male NPT heating connections, 3/4" gas and the same controls; the 115 moves to 4"/100 mm venting where the 45 can use 3"/80 mm.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of De Dietrich MCA Pro 45 and De Dietrich MCA Pro 115
SpecificationDe Dietrich MCA Pro 45De Dietrich MCA Pro 115
Minimum input (as printed)34 MBH82 MBH
Maximum input (as printed)156 MBH399 MBH
Minimum heat output33 MBH79 MBH
Maximum heat output146 MBH368 MBH
Thermal efficiency (CSA certified)94 %94 %
FiringModulating, on/off, remote 0–10 VModulating, on/off, remote 0–10 V
Heating supply / return1-1/4" male NPT1-1/4" male NPT
Vent / combustion air3" single pipe / 80–125 mm concentric4" single pipe / 100–150 mm concentric
Weight (dry / wetted)117 lb dry / 130 lb wetted150 lb dry / 167 lb wetted

What actually separates them

Both models are condensing cast-aluminum wall-hung boilers from the MCA Pro line, documented in the same submittal Rv 5.4. The 45 prints 34–156 MBH input and 33–146 MBH output; the 115 prints 82–399 MBH input and 79–368 MBH output. Both are CSA certified at 94.0% thermal efficiency (94.3% combustion), with usable efficiency up to 98.2% and standby loss under 0.3%.

The firing range is the practical difference. The 45 can modulate down to 33 MBH of output while the 115's floor is 79 MBH, so a small, well-insulated load cycles less on the smaller boiler. At the top end the 115 delivers about 2.5 times the output of the 45, which is the difference between a single large home and a light-commercial load — or between one boiler and a cascade.

Connections and controls are shared: 1-1/4" male NPT supply and return, 3/4" male NPT gas, modulating/on-off/remote 0–10 V firing, and the same 68–190 °F operating range. Venting steps from 3" single pipe / 80–125 mm concentric on the 45 to 4" / 100–150 mm on the 115. Both are certified for installation to 4,500 ft (Canada).

CurrentSold in Canada
Input
34–156 MBH
Output (max)
146 MBH
AFUE
—

The De Dietrich MCA Pro 45 is a condensing wall-hung boiler rated 34–156 MBH input and 33–146 MBH output at 94.0% CSA thermal efficiency, with 1-1/4" heating connections and a 117 lb dry weight.

Natural gasPropaneDHW: unknown
CurrentSold in Canada
Input
82–399 MBH
Output (max)
368 MBH
AFUE
—

The De Dietrich MCA Pro 115 is a condensing wall-hung boiler rated 82–399 MBH input and 79–368 MBH output at 94.0% CSA thermal efficiency, with 1-1/4" heating connections and a 150 lb dry weight.

Natural gasPropaneDHW: unknown

Frequently asked questions

How much more output does the MCA Pro 115 have?

The submittal prints 33–146 MBH output for the 45 and 79–368 MBH for the 115 — the 115 tops out at about 2.5 times the 45's maximum output.

Is efficiency different between them?

No. Both sizes print the same CSA certified 94.0% thermal efficiency and 94.3% combustion efficiency for the MCA Pro line.

Does the venting change?

Yes. The MCA Pro 45 can use 3" single pipe / 80–125 mm concentric venting; the 65, 90 and 115 use 4" / 100–150 mm.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate