Fulton · ENDURA

Fulton ENDURA EDR-750

The Fulton ENDURA EDR-750 is a condensing duplex-stainless firetube commercial hydronic boiler rated 750,000 BTU/hr input and 728,250 BTU/hr output at 97.1% thermal efficiency, with 8:1 turndown per the official Endura TDS.

CurrentCanadian status unknown

Key figures

Max input
750,000 BTU/h
Max CSA output
728,250 BTU/h
AFUE
Min input
90,000 BTU/h
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Fulton ENDURA EDR-750 in practice

The EDR-750 is the 750 MBH size of Fulton's ENDURA condensing boiler, built on a fully-wetted three-pass duplex-stainless firetube heat exchanger. The official Technical Data Sheet (EDR-PURE_TDS_221110) prints 750,000 BTU/hr rated input, a 90,000 BTU/hr low fire, 728,250 BTU/hr rated output at 97.1% thermal efficiency and 8:1 burner turndown, with 2" NPT water connections, a 1" NPT gas train inlet, a 6 in combustion-air inlet and a 6 in minimum flue vent.

The boiler holds 50 gal in the pressure vessel and weighs 1,430 lb dry and 1,848 lb operating. Fulton publishes the Endura I&O manual (EDR-PURE-IOM-260219), the TDS and the guide specification as public documents, and the line is designed for variable primary flow hydronic systems.

Best suited to

  • Commercial hydronic loads near 750,000 BTU/hr input
  • Plants wanting a high-water-volume firetube design tolerant of variable flow
  • Retrofit boiler rooms needing a compact condensing footprint with low NOx

Applicability and support

Model number
EDR-750
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Fulton. Units are shown with every value; notes flag conflicting sources or missing figures.

Fulton ENDURA EDR-750 specifications
SpecificationValueNote
Input
Rated input750,000 BTU/hRated input 750,000 BTU/hr printed in the Endura TDS (EDR-PURE_TDS_221110).
Minimum input90,000 BTU/hMinimum input at low fire 90,000 BTU/hr printed in the Endura TDS.
Output
Rated output728,250 BTU/hRated output 728,250 BTU/hr (BTS-2000) printed in the Endura TDS.
Boiler horsepower (BTS-2000)21.8Boiler horsepower 21.8 (BTS-2000) printed in the Endura TDS.
Efficiency
AHRI thermal efficiency97.1 %Thermal efficiency 97.1% (BTS-2000) printed in the Endura TDS.
Venting and air
Combustion air intake6 inCombustion air inlet (adapter required) per the Endura TDS.
Flue gas exhaust6 inMinimum flue gas exhaust vent (adapter required) per the Endura TDS.
Physical and connections
Water connections2" NPTBoiler supply and return connection per the Endura TDS.
Gas connection1" NPTNatural gas train inlet per the Endura TDS; propane is a documented option with the EDR-1500 exception noted in the TDS.
Dry weight1,430 lbDry weight 1,430 lb printed in the Endura TDS; operating weight 1,848 lb.
Water volume50 galPressure vessel water volume 50 gal printed in the Endura TDS.
Operating limits and other
Turndown8:1Burner turndown 8:1 printed in the Endura TDS.
FuelNatural gas or propaneThe Endura TDS is written for standard natural gas and documents propane operation, with the EDR-1500 not available for propane (a derated EDR-2000 is offered for those applications).

Frequently asked questions

What are the ENDURA EDR-750 ratings?

The official TDS prints 750,000 BTU/hr input, 728,250 BTU/hr output, 97.1% thermal efficiency and 8:1 turndown.

Does the EDR-750 run on propane?

Yes — the TDS documents propane operation for this size, alongside natural gas.

Which manual covers the ENDURA?

Fulton publishes the Endura I&O manual (EDR-PURE-IOM-260219) and the Technical Data Sheet (EDR-PURE_TDS_221110) as public documents.

Questions about the Fulton ENDURA EDR-750?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification