IBC IFIRE-B Red LED - 10 Flashes — Water Pressure Fault

Red LED - 10 Flashes

Needs attentionIBC IFIRE-B condensing boilers (manual 241941 Rev. 13)

Water Pressure Fault. Check system piping for leaks. Check water pressure switch (if equipped) and connections. Check wiring on PIM at J1, pins 6 and 7 for loose or missing jumper. The table classifies it as fault (PIM LED).

Applies to

This low-water or pressure protection code is displayed by the IFIRE control on IFIRE-B models (300B–1000B), as documented in IFIRE / IFIRE-B Installation & Operating Manual, doc 241941 Rev. 13 (241941 Rev. 13). Codes can differ between controller generations, so always check the manual that matches your unit.

Controller: IFIRE control. Source manual: 241941 Rev. 13.

Why a code is not a diagnosis

A water-pressure or low-water code can mean a genuine leak or empty system, a failed expansion tank, a faulty fill valve, or a sensor problem. The appliance does not distinguish these.

Safe things to observe

  • Read the pressure gauge and compare it with the normal cold-system pressure your installer set.
  • Look for drips or wet spots near the appliance, pipes and the relief-valve discharge.

Do not

  • Do not keep re-pressurizing a system that keeps losing water.
  • Do not cap a relief-valve discharge pipe.

How professional service helps

  1. A technician finds and repairs the leak, checks the expansion tank and fill assembly, and verifies the sensor circuit.

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Frequently asked questions

Can I clear this code myself?

Clearing a code without fixing its cause usually just brings it back. Note the code, check the safe items on this page, then call a licensed technician. If your appliance manual describes a user reset for this exact code and it stays away, no call may be needed.

Boiler locked out? Call with the alert text ready.

The brand, model and this alert are passed along when you request service online, so the technician arrives prepared.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate