Skip to content
Boilers.caby ROMA Heating & Cooling

Laars Heating Systems · Pennant

Laars Pennant PNCH 750

The Laars Pennant PNCH 750 is a fan-assisted, non-condensing commercial hydronic boiler rated 750,000 BTU/hr input and 638,000 BTU/hr output at 85% thermal efficiency, with stage firing up to 4:1.

CurrentSold in Canada

Key figures

Max input
750,000 BTU/hr
Max CSA output
638,000 BTU/hr
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Laars Pennant PNCH 750 in practice

The PNCH 750 is the 750,000 BTU/hr hydronic size of Laars' Pennant modular boiler line, documented in the Document 1558 submittal and the Document 1373 I&O. The submittal sizing table lists 750,000 BTU/hr input, 638,000 BTU/hr output, 85% AHRI-certified thermal efficiency, a 1-1/4" gas connection, 2" water connections and a 735 lb shipping weight.

The Pennant is a fan-assisted, non-condensing design with a 10-tube heat exchanger using finned copper or cupronickel tubing, glass-lined cast iron or bronze headers and non-ferrous waterways, running on natural or LP gas with NOx below 10 ppm and stage firing up to 4:1. It uses the Laars Linc control with cascade and auto redundancy, and its Category I or III fan-assisted venting can connect from the top or back of the unit.

Best suited to

  • Commercial hydronic loads near 750,000 BTU/hr input
  • Buildings that need staged, non-condensing capacity with the Laars Linc control
  • Retrofit plants with existing Category I or III venting

Applicability and support

Model number
PNCH750
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Laars Heating Systems. Units are shown with every value; notes flag conflicting sources or missing figures.

Laars Pennant PNCH 750 specifications
SpecificationValueNote
Input
Input750,000 BTU/hrPer the Document 1558 Pennant submittal sizing table.
Output
Output638,000 BTU/hrPer the Document 1558 Pennant submittal sizing table.
Efficiency
Efficiency (thermal)85 %AHRI-certified combustion and thermal efficiency per the Document 1558 submittal.
Venting and air
VentingCategory I or III fan-assistedPer the Pennant brochure; vent connections can be from the top or back.
Physical and connections
Gas connection1-1/4"Per the Document 1558 Pennant submittal sizing table.
Water connection2"Per the Document 1558 Pennant submittal sizing table.
Shipping weight735 lbPer the Document 1558 Pennant submittal sizing table.
Operating limits and other
FiringStaged, up to 4:1Printed on the Pennant product page and brochure.

Frequently asked questions

What are the Pennant PNCH 750 ratings?

The Document 1558 submittal lists 750,000 BTU/hr input, 638,000 BTU/hr output and 85% AHRI thermal efficiency.

Is the Pennant condensing?

No. The Pennant is a non-condensing, fan-assisted staged boiler at 85% thermal efficiency; Laars offers the optional factory low-temperature configuration for systems with cold return water.

What fuel does the Pennant use?

The product page says Pennant boilers and water heaters run on natural or LP gas, with NOx below 10 ppm.

Questions about the Laars Pennant PNCH 750?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate