Skip to content
Boilers.caby ROMA Heating & Cooling

Raypak · Delta Limited

Raypak Delta Limited H8-1259B

The Raypak Delta Limited H8-1259B is an indoor non-condensing copper-fin commercial hydronic boiler rated 1,260 MBTUH input and 1,058 MBTUH Type H output at 84% thermal efficiency, with 3-stage firing and a 12 in flue.

CurrentCanadian status unknown

Key figures

Max input
1,260 MBH
Max CSA output
1,058 MBH
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Raypak Delta Limited H8-1259B in practice

The H8-1259B is the 1,260 MBTUH size of the Delta Limited, Raypak's indoor non-condensing copper-fin boiler based on the same basic design as the Hi Delta with a reduced feature set at reduced cost. The official submittals print 1,260 MBTUH input and 1,058 MBTUH Type H output at 84% thermal efficiency, with 3-stage firing, a 68-1/2 in casing width, 2-1/2" NPT water connections, a 2" NPT gas connection, a 12 in flue, 1010 lb approximate shipping weight and <12 A boiler amp draw.

The model-number key in the I&O manual (241330) reads H for hydronic and the following digit for firing mode — 4 for on-off, 3 for 2-stage, 8 for 3-stage and 9 for 4-stage — which is how the page's H4/H3/H8/H9 prefixes match the printed stage counts. Submittals 242015 (399B-899B) and 242016 (989B-2339B) carry the rating tables above.

Best suited to

  • Commercial hydronic loads near 1,260 MBTUH input
  • Budget-sensitive plants wanting the Hi Delta design with a reduced feature set
  • Indoor installations on Category I or III venting

Applicability and support

Model number
H8-1259B
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Raypak. Units are shown with every value; notes flag conflicting sources or missing figures.

Raypak Delta Limited H8-1259B specifications
SpecificationValueNote
Input
Input1,260 MBHRated input 1,260 MBTUH printed in the Delta Limited submittals (242015/242016) and the product page model rows.
Output
Output1,058 MBHType H (hydronic) output 1,058 MBTUH printed in the Delta Limited submittals at 84% thermal efficiency.
Efficiency
AHRI thermal efficiency84 %84% Type H thermal efficiency per the Delta Limited submittals and product page model rows.
Venting and air
Flue outlet12 inFlue connection (K) per the Delta Limited submittals.
Venting categoryCategory I & IIINon-condensing Category I or III venting per the product page model rows.
Physical and connections
Width (A)68-1/2 inDimension A printed in the Delta Limited submittals.
Water connection2-1/2" NPTWater connection (H NPT) per the Delta Limited submittals.
Gas connection2" NPTGas connection (G NPT, natural gas) per the Delta Limited submittals; propane connection sizes are printed separately.
Weight1,010 lbApproximate shipping weight 1010 lb printed in the Delta Limited submittals.
Electrical
Electrical120 VAC, 1-phase; <12 A boiler drawOperating voltage and boiler amp draw from the Delta Limited submittals and product page model rows.
Operating limits and other
Firing stages3 firing stagesFiring stages printed in the Delta Limited submittals; the manual's model-number key maps the first digit (4 = on-off, 3 = 2-stage, 8 = 3-stage, 9 = 4-stage).
Turndown3:1Turndown from the product page model rows, matching the printed firing-stage count.
Maximum water flow132 GPMMaximum water flow from the product page model rows.
FuelNatural gas or propaneNatural gas or propane; the submittals print natural-gas and propane rates.

Frequently asked questions

What are the Delta Limited H8-1259B ratings?

The official submittals print 1,260 MBTUH input, 1,058 MBTUH Type H output at 84% thermal efficiency, with 3-stage firing.

What does the model number H8-1259B mean?

The I&O manual's key reads H for hydronic heating and the following digit for firing mode: 4 = on-off, 3 = 2-stage, 8 = 3-stage and 9 = 4-stage, followed by the approximate MBTUH size.

Can the H8-1259B run on propane?

Yes — the submittals print natural-gas and propane rates and connection sizes for this size.

Questions about the Raypak Delta Limited H8-1259B?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate