Skip to content
Boilers.caby ROMA Heating & Cooling

Raypak · MVB Category I & III

Raypak MVB H7-2004A

The Raypak MVB H7-2004A is a non-condensing modulating vertical commercial hydronic boiler rated 1999 MBTUH input and 1679 MBTUH output at 84% thermal efficiency, with Category I & III venting and a 14 in flue.

CurrentCanadian status unknown

Key figures

Max input
1,999 MBH
Max CSA output
1,679 MBH
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Raypak MVB H7-2004A in practice

The H7-2004A is the 1999 MBTUH size of the MVB Category I & III line, the non-condensing member of Raypak's modulating vertical boiler platform. Product submittal 241864 prints 1999 MBTUH input, 1679 MBTUH output and 84% thermal efficiency, with 2-1/2" NPT water connections, a 2" NPT gas connection, a 14 in flue, a 8 in combustion-air connection, 940 lb operating weight and a 1.7:1 turndown on the product page.

The boiler vents as a Category I or III appliance, runs on the VERSA IC control with cascade up to eight units, and is documented by I&O manual 241512 in English and French. Submittal 241864 provides the rating and dimensions data used above.

Best suited to

  • Commercial hydronic loads near 1999 MBTUH input
  • Buildings with existing Category I or III venting where a condensing boiler is not required
  • Plants standardising on the modulating vertical MVB platform

Applicability and support

Model number
H7-2004A
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Raypak. Units are shown with every value; notes flag conflicting sources or missing figures.

Raypak MVB H7-2004A specifications
SpecificationValueNote
Input
Input1,999 MBHRated input 1999 MBTUH printed in the 241864 product submittal.
Output
Output1,679 MBHRated output 1679 MBTUH printed in the 241864 submittal.
Efficiency
AHRI thermal efficiency84 %84% thermal efficiency at full rate per the product page and the 241864 submittal.
Venting and air
Venting categoryCategory I & IIINon-condensing Category I or III venting per the product page model data.
Flue outlet14 inFlue outlet diameter per the 241864 submittal.
Combustion air intake8 inCombustion-air connection diameter per the 241864 submittal.
Physical and connections
Water connection2-1/2" NPTWater connection per the 241864 submittal's dimensions table.
Gas connection2" NPTGas connection (natural gas) per the 241864 submittal; the submittal notes propane models use a 1 in NPT connection.
Weight940 lbOperating weight 940 lb printed in the 241864 submittal.
Electrical
Electrical120 VAC, 1-phaseOperating voltage from the product page model data.
Operating limits and other
Turndown1.7:1Turndown printed for the MVB Category I & III sizes in the product page model data.
Maximum water flow113 GPMMaximum water flow from the product page model data.
CascadeUp to 8 boilersVERSA IC control with cascade up to 8 boilers per the product page model data.
FuelNatural gas or propaneNatural gas or propane; the 241864 submittal prints propane connection sizes separately.

Frequently asked questions

What are the MVB H7-2004A ratings?

Product submittal 241864 prints 1999 MBTUH input, 1679 MBTUH output and 84% thermal efficiency.

Is the H7-2004A condensing?

No. The MVB Category I & III models are the non-condensing version of the MVB platform, vented as Category I or III appliances; the MVB Category IV models are the condensing members.

Which manual covers the MVB Category I & III?

Raypak publishes I&O 241512 in English and 241512-FR in French for the H WH P 504A-2004A models.

Questions about the Raypak MVB H7-2004A?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate