Skip to content
Boilers.caby ROMA Heating & Cooling

Raypak · XVers L

Raypak XVers L H7-406L

The Raypak XVers L H7-406L is a condensing firetube commercial hydronic boiler rated 399 MBTUH input and 391 MBTUH output at 98% AHRI thermal efficiency, with 10:1 turndown, Category IV venting and a maximum water flow of 73 gpm per the 241896 submittal.

CurrentCanadian status unknown

Key figures

Max input
399 MBH
Max CSA output
391 MBH
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Raypak XVers L H7-406L in practice

The H7-406L is the 399 MBTUH size of the XVers L, the condensing firetube line Raypak markets as the 399-850 MBTUH expansion of the XVers family. Product submittal 241896 prints 399 MBTUH input, 391 MBTUH output, 98% AHRI thermal efficiency and 10:1 turndown for this size, with 2" NPT water connections, a 4 in flue, a 4 in combustion-air intake, a 1" NPT gas connection, 547 lb operating weight and 13 gal water content.

Like the rest of the XVers L range it runs on the VERSA IC control with cascade capability up to eight boilers and Raymote connectivity, vents as a Category IV condensing appliance, and carries ASME construction with indoor/outdoor rating per the product page model data. The I&O manual is Raypak 241782, published in English and French, and the rating data above comes from submittal 241896.

Best suited to

  • Commercial hydronic loads near 399 MBTUH input
  • Plants standardising on the XVers L condensing firetube platform
  • Retrofit or new builds needing Category IV condensing venting and up to 8-boiler cascade

Applicability and support

Model number
H7-406L
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Raypak. Units are shown with every value; notes flag conflicting sources or missing figures.

Raypak XVers L H7-406L specifications
SpecificationValueNote
Input
Input399 MBHRated input 399 MBTUH printed in the 241896 product submittal's AHRI ratings table.
Output
Output391 MBHRated output 391 MBTUH printed in the 241896 submittal.
Efficiency
AHRI thermal efficiency98 %AHRI thermal efficiency 98% at full rate per the 241896 submittal.
Venting and air
Venting categoryCategory IVCondensing Category IV venting per the product page model data.
Flue outlet4 inFlue diameter (PVC/CPVC) per the 241896 submittal.
Combustion air intake4 inAir intake diameter per the 241896 submittal.
Physical and connections
Water connection2" NPTWater inlet/outlet connection per the 241896 submittal's dimensions table.
Gas connection1" NPTGas connection (natural gas) per the 241896 submittal; the submittal notes the unit is field-convertible to propane.
Weight547 lbApproximate operating weight 547 lb printed in the 241896 submittal.
Water content13 galWater content 13 gal printed in the 241896 submittal.
Electrical
Electrical120/208 VAC, 1-phaseOperating voltage from the product page model data.
Operating limits and other
Turndown10:1Turndown printed for the H7-406L in the 241896 submittal.
Maximum water flow73 GPMMaximum water flow from the product page model data.
CascadeUp to 8 boilersVERSA IC control with cascade up to 8 boilers per the product page model data.
FuelNatural gas or propaneNatural gas is the factory configuration; the 241896 submittal covers propane field conversion.

Frequently asked questions

What are the H7-406L ratings?

Product submittal 241896 prints 399 MBTUH input, 391 MBTUH output and 98% AHRI thermal efficiency at 10:1 turndown.

What size are the H7-406L connections?

2" NPT water connections, a 1" NPT gas connection, a 4 in flue and a 4 in combustion-air intake, per the 241896 submittal's dimensions table.

Which manual covers the XVers L?

Raypak publishes the XVers L I&O manual as 241782 in English and 241782-FR in French, with submittal 241896 for the rating table.

Questions about the Raypak XVers L H7-406L?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate