Skip to content
Boilers.caby ROMA Heating & Cooling

Smith Cast Iron Boilers · 28HE Series

Smith RTS/28HE-4

The Smith RTS/28HE-4 is the 4-section 27 HP size of the 28HE RTS high-efficiency water boiler — 931 MBH gross output, 810 MBH net I=B=R water, 1143 MBH gas or 7.9 GPH oil burner capacity, with 3" supply and return connections.

CurrentCanadian status unknown

Key figures

Max input
1,143 MBH
Max CSA output
AFUE
Min input
Natural gasDHW: unknowncommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Smith RTS/28HE-4 in practice

The RTS/28HE-4 is a 4-section cast-iron wet-base water boiler in Smith's 28HE RTS line, documented in the PDRTSHE-4 product data sheet. It prints 931 MBH gross output, 810 MBH net I=B=R water, 81.2 sq ft of heating surface, a 12.04 cu ft furnace volume and a water working weight of 4,215 lb. Burner capacity is 1143 MBH on gas or 7.9 GPH on light oil, with thermal efficiencies of 83.9% (oil) and 81.4% (gas).

The water piping diagram prints 3" supply and 3" return connections and 90 GPM at a 20 °F ΔT. The RTS (Return Temperature Stabilizer) is standard on all 28HE water boilers and is not a condensing device — the bulletin states the boiler cannot be operated as a condensing boiler. The model number denotes the section count; ordering adds a fuel prefix (LO for light oil, G for gas, GO for gas/oil). Smith lists the 28HE RTS as current; Canadian availability is not stated on the captured pages.

Best suited to

  • Commercial hydronic plants whose calculated load fits 931 MBH gross output
  • Buildings that need the Return Temperature Stabilizer for low-temperature return water protection
  • Oil, gas or gas/oil power-burner installations with a chimney

Applicability and support

Model number
RTS/28HE-4
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Smith Cast Iron Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.

Smith RTS/28HE-4 specifications
SpecificationValueNote
Input
Gas burner capacity (as printed)1,143 MBHI=B=R gas burner capacity printed in PDRTSHE-4.
Oil firing rate (as printed)7.9 GPHLight oil at 140,000 BTU/gal, printed in PDRTSHE-4.
Output
Gross output (as printed)931 MBHI=B=R gross output printed in PDRTSHE-4 and BSG-10.
Net I=B=R water rating810 MBHNet water rating (allowance 1.15) printed in PDRTSHE-4.
Efficiency
Thermal efficiency — oil83.9 %Printed in PDRTSHE-4.
Thermal efficiency — gas81.4 %Printed in PDRTSHE-4.
Combustion efficiency — oil86.2 %Printed in PDRTSHE-4.
Combustion efficiency — gas83.6 %Printed in PDRTSHE-4.
Physical and connections
Supply / return connection3" supply / 3" returnPrinted in the PDRTSHE-4 water piping diagram (SIOM-98).
Cast-iron sections4The model number denotes the section count, per PDRTSHE-4 ordering notes.
Heating surface81.2 sq ftPrinted in PDRTSHE-4.
Furnace volume12.04 cu ftPrinted in PDRTSHE-4.
Water content123.4 galPrinted in PDRTSHE-4.
Water working weight4,215 lbPrinted in PDRTSHE-4.
Maximum allowable working pressure80 psi waterPrinted in PDRTSHE-4 (ASME Section IV).
Operating limits and other
Flow at 20 °F ΔT90 GPMPrinted in the PDRTSHE-4 water piping diagram.
Boiler horsepower27Printed in PDRTSHE-4 and BSG-10.
FuelNatural gas; oil and gas/oil firing availablePDRTSHE-4 prints oil (LO) and gas (G) prefixes plus gas/oil (GO) ordering; the product page says 'fired with oil, gas or both'. Oil capability is carried here because the schema's fuel enum has no oil value.

Frequently asked questions

What is the output of the Smith RTS/28HE-4?

PDRTSHE-4 prints 931 MBH gross output and 810 MBH net I=B=R water for this size, with 90 GPM at 20 °F ΔT.

Is the 28HE RTS a condensing boiler?

No. RTSB-1 states plainly that the boiler cannot be operated as a condensing boiler; the RTS device protects the cast iron from thermal shock at low return temperatures.

What size connections does RTS/28HE-4 use?

The PDRTSHE-4 water piping diagram prints 3" supply and 3" return connections for this size.

Questions about the Smith RTS/28HE-4?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate