Skip to content
Boilers.caby ROMA Heating & Cooling

Smith Cast Iron Boilers · 28HE Series

Smith RTS/28HE-5

The Smith RTS/28HE-5 is the 5-section 35 HP size of the 28HE RTS high-efficiency water boiler — 1194 MBH gross output, 1038 MBH net I=B=R water, 1458 MBH gas or 10.2 GPH oil burner capacity, with 3" supply and return connections.

CurrentCanadian status unknown

Key figures

Max input
1,458 MBH
Max CSA output
AFUE
Min input
Natural gasDHW: unknowncommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Smith RTS/28HE-5 in practice

The RTS/28HE-5 is a 5-section cast-iron wet-base water boiler in Smith's 28HE RTS line, documented in the PDRTSHE-4 product data sheet. It prints 1194 MBH gross output, 1038 MBH net I=B=R water, 105.3 sq ft of heating surface, a 16.14 cu ft furnace volume and a water working weight of 5,038 lb. Burner capacity is 1458 MBH on gas or 10.2 GPH on light oil, with thermal efficiencies of 84.4% (oil) and 81.9% (gas).

The water piping diagram prints 3" supply and 3" return connections and 116 GPM at a 20 °F ΔT. The RTS (Return Temperature Stabilizer) is standard on all 28HE water boilers and is not a condensing device — the bulletin states the boiler cannot be operated as a condensing boiler. The model number denotes the section count; ordering adds a fuel prefix (LO for light oil, G for gas, GO for gas/oil). Smith lists the 28HE RTS as current; Canadian availability is not stated on the captured pages.

Best suited to

  • Commercial hydronic plants whose calculated load fits 1194 MBH gross output
  • Buildings that need the Return Temperature Stabilizer for low-temperature return water protection
  • Oil, gas or gas/oil power-burner installations with a chimney

Applicability and support

Model number
RTS/28HE-5
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Smith Cast Iron Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.

Smith RTS/28HE-5 specifications
SpecificationValueNote
Input
Gas burner capacity (as printed)1,458 MBHI=B=R gas burner capacity printed in PDRTSHE-4.
Oil firing rate (as printed)10.2 GPHLight oil at 140,000 BTU/gal, printed in PDRTSHE-4.
Output
Gross output (as printed)1,194 MBHI=B=R gross output printed in PDRTSHE-4 and BSG-10.
Net I=B=R water rating1,038 MBHNet water rating (allowance 1.15) printed in PDRTSHE-4.
Efficiency
Thermal efficiency — oil84.4 %Printed in PDRTSHE-4.
Thermal efficiency — gas81.9 %Printed in PDRTSHE-4.
Combustion efficiency — oil86.2 %Printed in PDRTSHE-4.
Combustion efficiency — gas83.6 %Printed in PDRTSHE-4.
Physical and connections
Supply / return connection3" supply / 3" returnPrinted in the PDRTSHE-4 water piping diagram (SIOM-98).
Cast-iron sections5The model number denotes the section count, per PDRTSHE-4 ordering notes.
Heating surface105.3 sq ftPrinted in PDRTSHE-4.
Furnace volume16.14 cu ftPrinted in PDRTSHE-4.
Water content150.3 galPrinted in PDRTSHE-4.
Water working weight5,038 lbPrinted in PDRTSHE-4.
Maximum allowable working pressure80 psi waterPrinted in PDRTSHE-4 (ASME Section IV).
Operating limits and other
Flow at 20 °F ΔT116 GPMPrinted in the PDRTSHE-4 water piping diagram.
Boiler horsepower35Printed in PDRTSHE-4 and BSG-10.
FuelNatural gas; oil and gas/oil firing availablePDRTSHE-4 prints oil (LO) and gas (G) prefixes plus gas/oil (GO) ordering; the product page says 'fired with oil, gas or both'. Oil capability is carried here because the schema's fuel enum has no oil value.

Frequently asked questions

What is the output of the Smith RTS/28HE-5?

PDRTSHE-4 prints 1194 MBH gross output and 1038 MBH net I=B=R water for this size, with 116 GPM at 20 °F ΔT.

Is the 28HE RTS a condensing boiler?

No. RTSB-1 states plainly that the boiler cannot be operated as a condensing boiler; the RTS device protects the cast iron from thermal shock at low return temperatures.

What size connections does RTS/28HE-5 use?

The PDRTSHE-4 water piping diagram prints 3" supply and 3" return connections for this size.

Questions about the Smith RTS/28HE-5?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.