Viessmann · Vitodens 222-F (B2TA)
Viessmann Vitodens 222-F B2TA 35
The Vitodens 222-F B2TA 35 is the larger of the two earlier-generation 222-F combis: 19 to 125 MBH NG/LPG input at 93.3% AFUE with an integrated 26.5 USG (100 L) DHW tank and a 3.3 USG/min continuous draw at a 70°F rise.
Key figures
- Max input
- 125 MBH
- Max CSA output
- —
- AFUE
- 93.3 %
- Min input
- 19 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Viessmann Vitodens 222-F B2TA 35 in practice
The B2TA 35 is the larger B2TA combi: 19-125 MBH (5.5-37 kW) NG/LPG input, 17.4-114 MBH (5.1-33 kW) output, a 99 MBH (29 kW) Net AHRI rating and 93.3% AFUE. It carries the same 26.5 USG (100 L) integrated stainless steel DHW tank as the B2TA 19, with a 150 psig maximum allowable potable-water pressure.
Its DHW delivery is nearly double the smaller model's: a 3.3 USG/min continuous draw and a 60 USG maximum 10-minute draw at a 70°F rise, with the same 4,435 BTU/24h standby loss. Weight (282 lb / 128 kg) and dimensions (595 x 600 x 1625 mm) are identical to the B2TA 19, and the model must not be common-vented with any other appliance.
Best suited to
- Owners of existing B2TA 35 combis checking printed ratings and DHW figures
- Homes whose hot-water demand needs the 3.3 USG/min continuous draw
- Comparing the B2TA 35 against the later B2TB-125 and the B2HE boilers
Applicability and support
- Model number
- B2TA 35
- Canadian availability
- historical
- Production status
- discontinued
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| CSA input, minimum (NG/LPG) | 19 MBH | 5.5 kW, per the technical data manual |
| CSA input, maximum (NG/LPG) | 125 MBH | 37 kW, per the technical data manual |
| Output | ||
| CSA output / DOE heating capacity | 17.4-114 MBH | 5.1-33 kW, based on 140°F / 120°F supply/return |
| Net AHRI rating | 99 MBH | 29 kW; based on piping and pick-up allowance of 1.15. |
| Efficiency | ||
| Efficiency (AFUE) | 93.3 % | 93.3% AFUE on both B2TA models per the technical data manual. |
| Domestic hot water | ||
| Integrated DHW tank | 26.5 USG (100 L) | Stainless steel tank; 150 psig maximum allowable potable-water pressure. |
| Continuous DHW draw at 70°F rise | 3.3 USG/min | Based on a 70°F (21K) rise, 50°F to 120°F, per the technical data manual. |
| Maximum DHW draw over 10 minutes | 60 USG | Based on a 70°F (21K) rise. |
| DHW standby loss | 4,435 BTU/24h | 184 BTU/h, 0.8°F/h at 68°F room and 149°F DHW. |
| Domestic hot water | Combi: space heating and DHW with an integrated storage tank | |
| Physical and connections | ||
| Weight | 282 lb | 128 kg |
| Width | 600 mm | |
| Depth | 595 mm | |
| Height | 1,625 mm | 64 in; add 40 mm with the optional seismic bracket kit. |
| Operating limits and other | ||
| Fuel | Natural gas or liquid propane gas | |
| Boiler water content | 0.87 USG | 3.27 L |
| Maximum operating pressure | 45 psig | At 210°F (99°C); 3 bar. |
Manuals
- Technical Data Manual — Vitodens 222-F B2TA Series 19 and 35, doc 5683 719 - 095683 719 - 09 · 2016-12
- Installation Instructions — Vitodens 222-F B2TA, rev 1111 · 2016-12
- Service Instructions — Vitodens 222-F B2TA, rev 1515 · 2016-12
Alerts documented for this model
None documented yet.
Frequently asked questions
What is the input range of the B2TA 35?
19-125 MBH (5.5-37 kW) NG/LPG input, 17.4-114 MBH (5.1-33 kW) output, a 99 MBH Net AHRI rating and 93.3% AFUE, per the technical data manual.
How much hot water does the B2TA 35 deliver?
A 3.3 USG/min continuous draw and a 60 USG maximum 10-minute draw at a 70°F rise, from its integrated 26.5 USG (100 L) DHW tank.
How does the B2TA 35 differ from the B2TA 19?
Both share the tank, weight and cabinet; the 35 fires to 125 MBH against the 19's 67 MBH and doubles the continuous DHW draw from 1.8 to 3.3 USG/min.
Questions about the Viessmann Vitodens 222-F B2TA 35?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Technical Data Manual — Vitodens 222-F B2TA Series 19 and 35, doc 5683 719 - 09 · 5683 719 - 09 · accessed September 9, 2026
- Viessmann Canada — Historic manuals · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.