Viessmann Vitocrossal 300 CT3-46

The Vitocrossal 300 CT3-46 is the mid-size CT3 wide-chassis model: 1726 MBH input (506 kW), 1675 MBH output and 97.1% combustion and thermal efficiency.

DiscontinuedHistorically in Canada

Key figures

Max input
—
Max CSA output
—
AFUE
—
Min input
—
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Viessmann Vitocrossal 300 CT3-46 in practice

The CT3-46 is rated 1726 MBH (506 kW) input and 1675 MBH (491 kW) output at 97.1% combustion and thermal efficiency. It shares the wide 800 mm shell and 10 in. vent pipe with the CT3-37 while growing to 1,829 mm (72⅛ in) as shipped.

The boiler shell weighs 1,759 lb (798 kg) and the complete unit 2,064 lb (936 kg), with 140.8 USG (533 L) of boiler water. It keeps the range's 30 psig maximum operating pressure and 210°F maximum supply temperature.

Best suited to

  • Existing CT3-46 installations needing printed ratings
  • Commercial loads between the CT3-37 and CT3-57
  • Documentation for mid-size wide-chassis CT3 builds

Applicability and support

Model number
CT3-46
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.

Viessmann Vitocrossal 300 CT3-46 specifications
SpecificationValueNote
Input
Input1,726 MBH506 kW, per the technical data manual
Output
Output1,675 MBH491 kW; tested to AHRI BTS-2000.
Efficiency
Combustion efficiency97.1 %Per the printed rating table.
Thermal efficiency97.1 %Per the printed rating table.
Venting and air
Vent pipe internal diameter10 in251 mm per the technical data manual.
Physical and connections
Weight, boiler shell1,759 lb798 kg
Overall weight (with insulation and control, less burner)2,064 lb936 kg
Boiler length as shipped (door removed)1,829 mmPrinted as 72⅛ in
Width 1 (maximum shell width)800 mmPrinted as 31½ in
Maximum height2,023 mmPrinted as 79⅝ in
Operating limits and other
FuelNatural gas or liquid propaneGas-fired condensing boiler; maximum supply temperature 210°F (99°C).
Boiler water content140.8 USGPer the technical data manual.
Maximum operating pressure30 psig207 kPa; maximum operating temperature 210°F (99°C).
Boiler supply / returnPer modelSupply and return connections 2½ to 5 in. depending on size; boiler drain 1 in.

Frequently asked questions

What is the CT3-46 rated at?

1726 MBH (506 kW) input and 1675 MBH (491 kW) output, with 97.1% combustion efficiency and 97.1% thermal efficiency.

How much water does the CT3-46 hold?

140.8 USG (533 L) of boiler water, with a heat exchanger surface of 200.2 ft² (18.6 m²) water-cooled.

What vent size does the CT3-46 use?

A 10 in. (251 mm) internal-diameter vent pipe, shared with the CT3-37 and CT3-57.

Questions about the Viessmann Vitocrossal 300 CT3-46?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate