Viessmann · Vitogas 100 (GS1 / GS10)
Viessmann Vitogas 100 GS1-42
The Vitogas 100 GS1-42 is a five-section GS1 boiler: 165 MBH input (48 kW), 140 MBH output and 85.5% AFUE in the wide chassis.
Key figures
- Max input
- —
- Max CSA output
- —
- AFUE
- 85.5 %
- Min input
- —
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Viessmann Vitogas 100 GS1-42 in practice
The GS1-42 is rated 165 MBH (48 kW) input, 140 MBH (41 kW) output and 122 MBH (36 kW) Net I=B=R at 85.5% AFUE. It uses five cast-iron sections and six burners, weighing 428 lb (194 kg) with 4.2 USG of boiler water.
Dimensions remain the wide-chassis 864 x 840 mm (34 x 33 in) with a 845 mm overall height, and the boiler keeps the series' 60 psig maximum operating pressure. Like the rest of the GS1 range it is an atmospheric, chimney-vented design with a draft hood and vent damper.
Best suited to
- Existing GS1-42 installations needing printed ratings
- Loads between the GS1-35 and GS1-48
- Documentation for five-section GS1 builds
Applicability and support
- Model number
- GS1-42
- Canadian availability
- historical
- Production status
- discontinued
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| CSA input (natural gas) | 165 MBH | 48 kW, per the technical data manual |
| Output | ||
| CSA output / DOE heating capacity | 140 MBH | 41 kW |
| Net I=B=R rating | 122 MBH | 36 kW; based on piping and pick-up allowance of 1.15. |
| Efficiency | ||
| Efficiency (AFUE) | 85.5 % | With intermittent pilot electronic ignition and vent damper. |
| Venting and air | ||
| Vent pipe collar | Per model | 5 to 7 in. outside diameter per the technical data manual. |
| Physical and connections | ||
| Weight (boiler with insulation, burner and control) | 428 lb | 194 kg |
| Overall length | 864 mm | Printed as 34 in; heights 33¼ in (845 mm) with control in operating position. |
| Overall width | 840 mm | Printed as 33 in |
| Overall height (operation) | 845 mm | 33¼ in; 955 mm with control in operation position, 1180 mm for servicing. |
| Operating limits and other | ||
| Fuel | Natural gas or propane | 5 in. w.c. minimum NG supply pressure; 11 in. w.c. for propane. |
| Cast iron sections | 5 | 6 burners. |
| Boiler water content | 4.2 USG | |
| Maximum operating pressure | 60 psig | |
| Boiler supply / return | 1½ in. male thread | Gas supply ½ in. NPT. |
Manuals
- Technical Data Manual — Vitogas 100 GS1 Series, doc 5167 462 v1.55167 462 v1.5 · 2011-02
- Installation Instructions — Vitogas 100 GS1, rev 1.31.3 · 2011-02
- Technical Data Manual — Vitogas 100 GS10 Series, doc 5167 466 v1.35167 466 v1.3 · 2011-02
- Service Instructions — Vitogas 100 GS10, rev 1.11.1 · 2007-11
Alerts documented for this model
None documented yet.
Frequently asked questions
What is the GS1-42 rated at?
165 MBH (48 kW) input, 140 MBH (41 kW) output, a 122 MBH (36 kW) Net I=B=R rating and 85.5% AFUE.
How many sections does the GS1-42 have?
Five intermediate cast-iron sections with six burners, per the Vitogas 100 GS1 technical data manual.
What is the maximum operating pressure of the GS1-42?
60 psig, the same as every GS1 size; boiler water content is 4.2 USG.
Questions about the Viessmann Vitogas 100 GS1-42?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Viessmann Vitogas 100 GS1-22Same series
- Viessmann Vitogas 100 GS1-29Same series
- Viessmann Vitogas 100 GS1-35Same series
- Viessmann Vitogas 100 GS1-48Same series
- Viessmann Vitogas 100 GS1-60Same series
- Viessmann Vitogas 100 GS10-72Same series
- Viessmann Vitogas 100 GS10-84Same series
- Viessmann Vitogas 100 GS10-96Same series
- Vitogas 100 (GS1 / GS10) series hub
- Buying guide
Sources and verification
- Technical Data Manual — Vitogas 100 GS1 Series, doc 5167 462 v1.5 · 5167 462 v1.5 · accessed September 9, 2026
- Viessmann Canada — Historic manuals · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.