Viessmann Vitogas 100 (GS1 / GS10)

The Vitogas 100 is a discontinued atmospheric cast-iron gas boiler line documented in Viessmann Canada's historic manuals: the residential GS1 series in six sizes from 90 to 240 MBH and the commercial GS10 series in three sizes from 300 to 380 MBH, all rated in the mid-80s efficiency.

discontinuedhistoricalNatural gasPropaneresidentialcommercial

Series facts

Type
non-condensing
Efficiency
85.6% AFUE
Fuel
Natural gas or propane. The GS1 technical data manual prints 5 in. w.c. minimum supply pressure for natural gas and 11 in. w.c. for propane; the GS10 manual prints 7 and 11 in. w.c. respectively.
Venting
Atmospheric, chimney-vented Category I cast-iron boilers. The GS1 models are vented through a draft hood with a vent damper; the GS10 models use a draft hood with the field-supplied Category II vent system described in their manual.
Models documented
9
Warranty
Not verified

85.4-85.6% AFUE on the GS1 residential models; the GS10 commercial models print 85.6% combustion efficiency.

About the Vitogas 100 (GS1 / GS10)

The Vitogas 100 is a natural gas or propane-fired, cast-iron sectional hot-water boiler with an atmospheric fully premix burner, sold in Canada in two ranges. The residential GS1 series is a fully assembled boiler in six sizes — GS1-22, -29, -35, -42, -48 and -60 — covering 90 to 240 MBH (26 to 70 kW) input with 85.4-85.6% AFUE. The commercial GS10 series is an assembled cast-iron block with separate enclosure panels in three sizes — GS10-72, -84 and -96 — covering 300 to 380 MBH (88 to 111 kW) full-load input with a printed 85.6% combustion efficiency and two-stage firing at 70% partial load.

Both ranges are non-condensing atmospheric designs: GS1 boilers are single-stage, while the GS10 is a two-stage commercial boiler. Printed Net I=B=R ratings run 66 to 177 MBH on the GS1 and 224 to 283 MBH on the GS10; maximum operating pressure is 60 psig on both. The GS10's boiler shell ships as an assembled block (714 to 895 lb / 324 to 406 kg) and the complete boiler weighs 927 to 1,194 lb (420 to 542 kg) with insulation, burner, control and draft hood.

The line has been discontinued and its documentation is kept under Viessmann Canada's historic manuals, including the GS1 technical data manual (doc 5167 462 v1.5, 02/2011), installation, service and operating instructions, and the GS10 technical data manual (doc 5167 466 v1.3, 02/2011). Boilers.ca records the printed per-size rows — inputs, outputs, efficiency, dimensions, weights and water content — for owners and servicers of existing units.

Highlights

  • Discontinued atmospheric cast-iron gas boiler line, documented in Viessmann Canada's historic manuals
  • Residential GS1: six sizes, GS1-22 to GS1-60, 90 to 240 MBH input, 85.4-85.6% AFUE
  • Commercial GS10: three sizes, GS10-72 to GS10-96, 300 to 380 MBH input, 85.6% combustion efficiency
  • GS10 two-stage firing at 70% partial load; 60 psig maximum operating pressure
  • Printed Net I=B=R ratings 66-177 MBH (GS1) and 224-283 MBH (GS10)
  • Technical data, installation, service and operating documents still downloadable

Models

Vitogas 100 (GS1 / GS10) models

One canonical page per model with input, output and efficiency kept separate.

DiscontinuedHistorically in Canada
Input
—
Output (max)
—
AFUE
85.6 %

The Vitogas 100 GS1-22 is the smallest of the discontinued GS1 residential cast-iron boilers: 90 MBH input (26 kW), 76 MBH output and 85.6% AFUE in a two-section atmospheric boiler.

Natural gasPropaneHeating-only
DiscontinuedHistorically in Canada
Input
—
Output (max)
—
AFUE
—

The Vitogas 100 GS10-72 is the smallest commercial GS10 boiler: 300 MBH full-load input (88 kW), 257 MBH output and 85.6% combustion efficiency, two-stage fired at 70% partial load.

Natural gasPropaneHeating-only
DiscontinuedHistorically in Canada
Input
—
Output (max)
—
AFUE
—

The Vitogas 100 GS10-84 is the mid-size commercial GS10: 340 MBH full-load input (100 kW), 291 MBH output and 85.6% combustion efficiency with eight sections and seven burner tubes.

Natural gasPropaneHeating-only
DiscontinuedHistorically in Canada
Input
—
Output (max)
—
AFUE
—

The Vitogas 100 GS10-96 is the largest commercial GS10 boiler: 380 MBH full-load input (111 kW), 325 MBH output and 85.6% combustion efficiency with nine sections.

Natural gasPropaneHeating-only

Compare models in this series

Comparison of Viessmann Vitogas 100 GS1-22 and Viessmann Vitogas 100 GS1-29 and Viessmann Vitogas 100 GS1-35 and Viessmann Vitogas 100 GS1-42 and Viessmann Vitogas 100 GS1-48 and Viessmann Vitogas 100 GS1-60 and Viessmann Vitogas 100 GS10-72 and Viessmann Vitogas 100 GS10-84 and Viessmann Vitogas 100 GS10-96
SpecificationViessmann Vitogas 100 GS1-22Viessmann Vitogas 100 GS1-29Viessmann Vitogas 100 GS1-35Viessmann Vitogas 100 GS1-42Viessmann Vitogas 100 GS1-48Viessmann Vitogas 100 GS1-60Viessmann Vitogas 100 GS10-72Viessmann Vitogas 100 GS10-84Viessmann Vitogas 100 GS10-96
input-min—————————
input-max—————————
output-max—————————
Efficiency (AFUE)85.6 %85.5 %85.5 %85.5 %85.5 %85.4 %———
turndown—————————
vent-max-3—————————
vent-max-2—————————
Weight (boiler with insulation, burner and control)273 lb326 lb375 lb428 lb481 lb582 lb———

Read the full comparison: Viessmann Vitogas 100 GS1-22 vs GS1-29 →

Read the full comparison: Viessmann Vitogas 100 GS1-48 vs GS1-60 →

Read the full comparison: Viessmann Vitogas 100 GS10-72 vs GS10-84 →

Read the full comparison: Viessmann Vitogas 100 GS10-84 vs GS10-96 →

Error codes and alerts

Vitogas 100 (GS1 / GS10) alerts

No alerts documented for this series yet.

Manuals

Official documents

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Frequently asked questions

Is the Vitogas 100 still sold in Canada?

No. The Vitogas 100 GS1 and GS10 lines are discontinued; Viessmann Canada keeps their documentation under the historic manuals downloads. Current Viessmann gas boilers in Canada are the condensing Vitodens and Vitocrossal lines.

What sizes did the Vitogas 100 come in?

The residential GS1 series ran GS1-22, -29, -35, -42, -48 and -60 at 90, 115, 145, 165, 190 and 240 MBH input. The commercial GS10 series ran GS10-72, -84 and -96 at 300, 340 and 380 MBH full-load input.

What efficiency does the Vitogas 100 print?

The GS1 models print 85.4-85.6% AFUE in the technical data manual. The GS10 models print 85.6% combustion efficiency with two-stage firing, with partial-load values based on 70% of rated full-load input.

Is the Vitogas 100 a condensing boiler?

No. It is an atmospheric, non-condensing cast-iron boiler designed for chimney venting. Condensing operation only begins in Viessmann Canada's Vitodens and Vitocrossal lines.