Verdict in brief

The BMK 750 and BMK 1000 share the same 50 MBH minimum input, 1" gas and 3" water connections, 28" width and 78" height, but the 1000 adds 250 MBH of maximum input, a deeper 25" cabinet, 31 lb more dry weight and — importantly — a 20:1 turndown against the 750's 15:1, with thermal efficiency of 96.8% vs 95.6%.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of AERCO Benchmark 750 and AERCO Benchmark 1000
SpecificationAERCO Benchmark 750AERCO Benchmark 1000
Min. input50 MBH50 MBH
Max. input750 MBH1,000 MBH
Max. output720 MBH960 MBH
Thermal efficiency (80–180°F)95.6 %96.8 %
Efficiency range87–98 %87–98 %
Turndown ratio15:1 (7%)20:1 (5%)
Gas connection (NPT)1"1"
Water connection (flanged)3"3"
Weight, dry669 lb700 lb
Shipping weight862 lb900 lb
Width (A)28 in28 in
Depth (B)24.5 in25 in
Height (C)78 in78 in

What actually separates them

Both boilers are condensing 439 stainless-steel firetube units on the Edge controller with the same 87%–98% efficiency range and the same 50 MBH minimum fire. The 1000's advantage is headroom: 870–960 MBH of printed output against the 750's 653–720 MBH, which decides plants whose design load sits between the two.

Turndown is the less obvious difference: AERCO prints 20:1 (5%) for the BMK 1000 and 15:1 (7%) for the BMK 750, so the larger boiler can track low loads at least as deeply as the smaller one. The 1000 is also the more efficient row — 96.8% thermal efficiency at 80º–180ºF vs 95.6%.

Installation-wise the pair is nearly identical: 1" NPT gas, 3" flanged water, 28" width, 78" height and only a 0.5" depth difference (24.5" vs 25"). Dry weight rises from 669 lb to 700 lb and shipping weight from 862 lb to 900 lb. Size from a heat-loss calculation rather than the modest physical differences.

AERCO (Watts)

AERCO Benchmark 750

CurrentCanadian status unknown
Input
50–750 MBH
Output (max)
720 MBH
AFUE
—

The AERCO Benchmark 750 (BMK 750) is a condensing gas-fired firetube commercial boiler rated 750 MBH maximum input and a 653–720 MBH output range in AERCO's published ratings table, at 95.6% thermal efficiency (87%–98% range), with 15:1 (7%) turndown and a 669 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
50–1000 MBH
Output (max)
960 MBH
AFUE
—

The AERCO Benchmark 1000 (BMK 1000) is a condensing gas-fired firetube commercial boiler rated 1000 MBH maximum input and a 870–960 MBH output range in AERCO's published ratings table, at 96.8% thermal efficiency (87%–98% range), with 20:1 (5%) turndown and a 700 lb dry weight.

Natural gasPropaneHeating-only

Frequently asked questions

Which Benchmark has the deeper turndown?

The BMK 1000 at 20:1 (5%) versus 15:1 (7%) on the BMK 750, per AERCO's TDS specifications table.

Are the connections the same?

Yes — both print a 1" NPT gas connection and a 3" flanged water connection; the cabinets share the same 28" width and 78" height.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate