The AERCO Benchmark 750 (BMK 750) is a condensing gas-fired firetube commercial boiler rated 750 MBH maximum input and a 653–720 MBH output range in AERCO's published ratings table, at 95.6% thermal efficiency (87%–98% range), with 15:1 (7%) turndown and a 669 lb dry weight.

CurrentCanadian status unknown

Key figures

Max input
750 MBH
Max CSA output
720 MBH
AFUE
Min input
50 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

AERCO Benchmark 750 in practice

AERCO's Benchmark 750–6000 with Edge Controller TDS prints the BMK 750 at 50 MBH minimum input, 750 MBH maximum input and a 653–720 MBH output range (Max Output depends on application — see efficiency curves). Thermal efficiency at 80º–180ºF is 95.6% and the efficiency range for every row is 87%–98%.

The specifications table lists 15:1 (7%) turndown, a 1" NPT gas connection, a 3" flanged water connection, 669 lb dry weight (862 lb shipping) and dimensions of 28" wide × 24.5" deep × 78" high. The unit is ASME Section IV and runs on natural gas, propane or dual fuel.

The Benchmark uses a 439 stainless-steel firetube heat exchanger, an integrated O2 monitoring system with TComp air-temperature compensation, up to 20:1 turndown depending on capacity, on-board Boiler Sequencing Technology for plants of 2–16 boilers, and the Edge controller with BACnet/Modbus communications. AERCO's page copy notes NOx capability of 9 ppm or less at all firing rates depending on capacity. No official Canadian-sales statement was found, so canadianStatus stays unknown.

Best suited to

  • Commercial plants documenting an installed Benchmark 750 against AERCO's TDS
  • Hydronic systems in the 750 MBH input class
  • Modular plants using Boiler Sequencing Technology across 2–16 units

Applicability and support

Model number
BMK 750
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by AERCO (Watts). Units are shown with every value; notes flag conflicting sources or missing figures.

AERCO Benchmark 750 specifications
SpecificationValueNote
Input
Min. input50 MBHMin Input MBH per the TDS ratings table.
Max. input750 MBHMax Input MBH per the TDS ratings table.
Output
Max. output720 MBHTDS prints Max Output as 653–720 MBH depending on application (see efficiency curves); the upper figure is recorded here.
Efficiency
Thermal efficiency (80–180°F)95.6 %Thermal Efficiency 80º to 180ºF per the TDS ratings table.
Efficiency range87–98 %Efficiency range printed for every BMK row in the TDS ratings table.
Physical and connections
Gas connection (NPT)1"Gas Connections (NPT) per the TDS specifications table.
Water connection (flanged)3"Water Connect. (Flanged) per the TDS specifications table.
Weight, dry669 lbWeight (dry) per the TDS specifications table.
Shipping weight862 lbShipping Weight per the TDS specifications table.
Width (A)28 inDimension A in the TDS dimensions table.
Depth (B)24.5 inDimension B in the TDS dimensions table.
Height (C)78 inDimension C in the TDS dimensions table.
Operating limits and other
Turndown ratio15:1 (7%)As printed in the TDS specifications table.
Boiler categoryASME Sect. IVBoiler Category row of the TDS specifications table.
NOx emissionscapable of 9 ppm or less at all firing rates depending on capacityTDS feature list; the table notes BMK 5000/6000 at standard gas pressure (>14" W.C.) can achieve 9 ppm NOx.

Frequently asked questions

What are the Benchmark 750 ratings?

AERCO's TDS prints 50 MBH minimum input, 750 MBH maximum input, a 653–720 MBH output range and 95.6% thermal efficiency at 80º–180ºF, with 15:1 (7%) turndown.

What fuel does the Benchmark 750 use?

The TDS specifications table lists natural gas, propane or dual fuel, with a 1" NPT gas connection.

Is the Benchmark 750 condensing?

Yes — AERCO lists the Benchmark as a condensing boiler with a 439 stainless-steel firetube heat exchanger and an 87%–98% efficiency range.

Questions about the AERCO Benchmark 750?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate