HTP EFTU-150WBN vs EFTU-199WBN

Verdict in brief

The EFTU-199WBN tops the Elite Fire Tube Ultra heating-only line and is the first size with install trade-offs: it is the only boiler model that must vent in 3" pipe (6–150 ft exhaust, 0–150 ft intake), it deepens the cabinet from 17 to 18.5 in, ships at 131 lb (139.5 lb full) with 2.8 gal of water content, and it fires 19,900–199,000 BTU/hr to 184 MBH DOE heating capacity at 95% DOE AFUE.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of HTP EFTU-150WBN and HTP EFTU-199WBN
SpecificationHTP EFTU-150WBNHTP EFTU-199WBN
Central-heating input, minimum (natural gas)15 MBH19.9 MBH
Central-heating input, maximum (natural gas)150 MBH199 MBH
DOE AFUE95 %95 %
Heating capacity (DOE)138 MBH184 MBH
Net AHRI rating, water120 MBH160 MBH
Shipping weight120 lb131 lb
Approximate full boiler weight122 lb139.5 lb
Boiler water content2 gal2.8 gal
VentingExhaust 2" (6–100 ft) or 3" (6–150 ft); intake 2" (0–100 ft) or 3" (0–150 ft)Exhaust and intake 3" only — exhaust 6–150 ft, intake 0–150 ft

What actually separates them

The EFTU-150WBN fires 15,000–150,000 BTU/hr with 138 MBH DOE heating capacity and a 120 MBH net AHRI rating at 95% DOE AFUE, venting in 2" (6–100 ft) or 3" (6–150 ft). The EFTU-199WBN fires 19,900–199,000 BTU/hr to 184 MBH DOE heating capacity (160 MBH net AHRI) at the same 95% DOE AFUE.

The install costs of the 199 are printed in the submittal tables: LP-723 requires 3" diameter pipe on the 199/199C models, the cabinet deepens from 17 to 18.5 in, shipping weight rises from 120 to 131 lb (full weight 122 to 139.5 lb) and water content from 2.0 to 2.8 gal.

Both models keep the same CH connections (1-1/4" male NPT), 3/4" NPT gas, 50 psi heat-exchanger MAWP with a 30 psi relief valve, and the 15-year registered warranty. A vent route that cannot fit 3" pipe effectively rules out the 199 regardless of the load.

CurrentCanadian status unknown
Input
15–150 MBH
Output (max)
—
AFUE
95 %

The HTP EFTU-150WBN is the 150 MBH class wall-hung heating-only model of the Elite Fire Tube Ultra line: 15.0 to 150 MBH central-heating input at 95% DOE AFUE, 138 MBH DOE heating capacity and a 120 lb shipping weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
19.9–199 MBH
Output (max)
—
AFUE
95 %

The HTP EFTU-199WBN is the 199 MBH class wall-hung heating-only model of the Elite Fire Tube Ultra line: 19.9 to 199 MBH central-heating input at 95% DOE AFUE, 184 MBH DOE heating capacity and a 131 lb shipping weight.

Natural gasPropaneHeating-only

Frequently asked questions

Why is the EFTU-199WBN limited to 3" venting?

Per LP-723, 199/199C models must be vented in 3" diameter pipe — the submittal prints exhaust 6–150 ft and intake 0–150 ft in 3" only.

Is the 199 physically larger than the 150?

Yes — the cabinet deepens from 17 to 18.5 in, shipping weight rises from 120 to 131 lb and water content from 2.0 to 2.8 gal.

When does the 199 earn its install trade-offs?

When the heat-loss calculation needs more than the 150's 138 MBH DOE heating capacity and the vent route can accept 3" pipe.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.