Comparison

Lochinvar Crest FBN1001 vs FBN1251

Verdict in brief

The Crest FBN1001 and FBN1251 both run 20:1 turndown on 3" pipe, but the 1251 lifts input to 1250 MBH (1203 MBH gross), steps the gas inlet to 1-1/2" and the vent to 8", and grows water content from 77 to 87 gallons.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of Lochinvar Crest FBN1001 and Lochinvar Crest FBN1251
SpecificationLochinvar Crest FBN1001Lochinvar Crest FBN1251
Heating input, minimum50 MBH62.5 MBH
Heating input, maximum999 MBH1,250 MBH
Gross output961 MBH1,203 MBH
Net AHRI water rating834 MBH1,043 MBH
Water content77 gal87 gal
Pipe outlet connection3"3"
Pipe inlet connection3"3"
Gas connection1-1/4"1-1/2"
Air size6"6"
Vent size6"8"
Weight with water1,838 lb1,975 lb

What actually separates them

Both are Crest FB wave fire-tube boilers at 20:1 turndown per the I&O, sharing the 3" pipe outlet and inlet, the SMART TOUCH control with CON·X·US and venting to 100 equivalent feet in stainless steel, polypropylene, PVC or CPVC.

The 1251 is the first Crest size whose plant changes: maximum input rises from 999 to 1250 MBH with gross output from 961 to 1203 MBH, the gas inlet steps from 1-1/4" to 1-1/2" and the vent from 6" to 8" (air stays 6").

Water content grows from 77 to 87 gallons and weight with water from 1,838 to 1,975 lb per the ratings table. The FBN1001 remains the family's documented-efficiency size (96.2% headline on its page); Boilers.ca does not extend that figure to the 1251.

CurrentSold in Canada
Input
50–999 MBH
Output (max)
—
AFUE
—

The Crest FBN1001 fires 50 to 999 MBH with 961 MBH gross output and an 834 MBH AHRI net rating — the 96.2% thermal efficiency model whose page opens the Crest FB line, at 20:1 turndown.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
62.5–1250 MBH
Output (max)
—
AFUE
—

The Crest FBN1251 fires 62.5 to 1250 MBH with 1203 MBH gross output and a 1043 MBH AHRI net rating at 20:1 turndown, stepping the gas inlet to 1-1/2" and the vent to 8".

Natural gasPropaneHeating-only

Frequently asked questions

What changes at the FBN1251?

Maximum input rises from 999 to 1250 MBH, the gas inlet steps from 1-1/4" to 1-1/2" and the vent from 6" to 8"; the pipe connections stay 3". Turndown stays 20:1.

Are the FBN1001 and FBN1251 the same physical boiler?

No — the 1251 carries more capacity on the same 3" piping with a larger gas inlet and vent, plus 10 extra gallons of water content and 137 lb more weight with water.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.