Lochinvar FTXL FTX500 vs FTX600

Verdict in brief

The FTXL FTX500 and FTX600 share 2" water connections and 4" air/vent and both weigh 504 lb, but the 600 fires 85.7 to 600 MBH (585 MBH gross) at 7:1 turndown against the 500's 10:1, with submittal efficiency easing from 97.7% to 97.5%.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of Lochinvar FTXL FTX500 and Lochinvar FTXL FTX600
SpecificationLochinvar FTXL FTX500Lochinvar FTXL FTX600
Heating input, minimum50 MBH85.7 MBH
Heating input, maximum500 MBH600 MBH
Gross output489 MBH585 MBH
Net AHRI water rating425 MBH509 MBH
Efficiency (thermal)97.7 %97.5 %
Water content11.9 gal11.9 gal
Space-heating water connections2"2"
Gas connection1"1"
Air inlet size4"4"
Vent size4"4"
Shipping weight504 lb504 lb

What actually separates them

Both are FTXL Series 120 fire-tube boilers on 2" water and 1" gas connections with a 4" air intake and 4" vent, vented to 100 equivalent feet per the submittal, and both print the same 504 lb shipping weight.

The structural difference is turndown: the submittal rates the 500 at 10:1 and the 600 at 7:1, which the ratings table reflects in minimum inputs of 50 and 85.7 MBH. A building whose part loads sit near the boiler's minimum will cycle more on the 600.

Capacity steps from 500 to 600 MBH of maximum input, gross output from 489 to 585 MBH and the AHRI net rating from 425 to 509 MBH, while submittal thermal efficiency eases from 97.7% to 97.5%. Water content is identical at 11.9 gallons.

CurrentSold in Canada
Input
50–500 MBH
Output (max)
AFUE

The FTXL FTX500 fires 50 to 500 MBH with 489 MBH gross output and a 425 MBH AHRI net rating at 97.7% submittal thermal efficiency, keeping 2" water connections and 4" venting.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
85.7–600 MBH
Output (max)
AFUE

The FTXL FTX600 reaches 85.7 to 600 MBH input with 585 MBH gross output and a 509 MBH AHRI net rating at 97.5% submittal thermal efficiency, with 7:1 turndown.

Natural gasPropaneHeating-only

Frequently asked questions

Why does the FTX600 have lower turndown?

The FTXL submittal rates 7:1 turndown on the 600, 725 and 850 sizes against 10:1 on the 400, 500 and 1000; the ratings table minimums (85.7 MBH versus 50 MBH) match those ratios.

What do the FTX500 and FTX600 have in common?

2" water and 1" gas connections, 4" air intake and vent, an 11.9-gallon water content and a 504 lb shipping weight — the published differences are capacity, minimum fire and efficiency.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.