Weil-McLain Ultra 299 vs Ultra 399

Verdict in brief

The Ultra 299 and 399 share the large Series 4 cabinet, 4" venting and 297 lb shipping weight; the 399 adds 100 MBH of input (299 to 399) for a 317 MBH net AHRI rating, but its 91.7% figure is asterisked combustion efficiency — the 399 carries no DOE AFUE of its own.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of Weil-McLain Ultra 299 and Weil-McLain Ultra 399
SpecificationWeil-McLain Ultra 299Weil-McLain Ultra 399
Input, maximum299 MBH399 MBH
Input, minimum62 MBH80 MBH
DOE heating capacity270 MBH364 MBH
Net AHRI water rating235 MBH317 MBH
Weight297 lb297 lb
Boiler water content2.1 gal2.1 gal
Venting4" PVC, CPVC, polypropylene or stainless steel (Category IV); 4" pipe only on the 2994" PVC, CPVC, polypropylene or stainless steel (Category IV); 4" pipe only on the 399

What actually separates them

Both models use the same large Ultra cabinet with 4" venting to 100 ft, 1-1/4" NPT supply and return tappings, 3/4" NPT gas and a 297 lb shipping weight, at 5:1 modulation. The 399 steps input from 299 to 399 MBH, low fire from 62 to 80 MBH and the net AHRI rating from 235 to 317 MBH.

The efficiency comparison stops at the 299: it is DOE-rated at 92.5% AFUE, while the 399's US table prints 91.7% and 364 MBH with asterisks and the footnote "Combustion efficiency and gross output (not an AFUE)". The CA page's 94.1% figure belongs to the Ultra 230, so no Ultra document rates the 399 by AFUE.

Water content is 2.1 gallons on both, and both need a 4" vent route and gas supply sized near 400 MBH. Choose the 399 when the calculated load genuinely exceeds the 299's 270 MBH of output; otherwise the 299 is the larger DOE-AFUE-rated Ultra.

CurrentSold in Canada
Input
62–299 MBH
Output (max)
270 MBH
AFUE
92.5 %

The Ultra 299 steps up to 4" venting and 1-1/4" tappings: 299 MBH input, a 62 MBH low fire, 270 MBH DOE heating capacity and 92.5% AFUE in the largest Ultra cabinet.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
80–399 MBH
Output (max)
364 MBH
AFUE
—

The Ultra 399 is the largest Series 4 Ultra: 399 MBH input from an 80 MBH low fire, with the US table's asterisked 91.7% combustion efficiency and 364 MBH gross output — the manual's footnote says those figures are not an AFUE.

Natural gasPropaneHeating-only

Frequently asked questions

Is the Ultra 399 rated 91.7% AFUE?

No. The asterisked 91.7% figure is combustion efficiency with 364 MBH gross output per the US Series 4 table — the footnote states it is not an AFUE.

How much capacity does the 399 add over the 299?

Input rises from 299 to 399 MBH and the net AHRI rating from 235 to 317 MBH, at the same 297 lb shipping weight.

What connects these two sizes?

Both use 4" venting to 100 ft, 1-1/4" NPT supply and return tappings and a 3/4" NPT gas connection.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate